§ 105.35-15 - Fire hose.


Latest version.
  • (a) One length of fire hose shall be provided for each fire hydrant required.

    (b) Fire hose may be commercial fire hose or equivalent of not over 112 -inch diameter or garden hose of not less than 58 -inch nominal inside diameter. Hose shall be in one piece not less than 25 feet and not more than 50 feet in length.

    (c) If 112 inch diameter fire hose is used after January 1, 1980, each length of hose must:

    (1) Be lined commercial fire hose that conforms to Underwriters' Laboratories, Inc. Standard 19 or Federal Specification ZZ-H-451E. A hose that bears the label of Underwriters' Laboratories, Inc. as lined fire hose is accepted as conforming to this requirement; and

    (2) Have a combination nozzle approved by the Commandant in accordance with §162.027-6 of this chapter.

    (d) If garden hose is used, it shall be of a good commercial grade constructed of an inner rubber tube, plies of braided cotton reinforcement and an outer rubber cover or of equivalent material, and shall be fitted with a commercial garden hose nozzle of good grade bronze or equivalent metal.

    (e) All fittings on fire hose shall be of brass, copper, or other suitable corrosion resistant metal.

    (f) A length of fire hose shall be attached to each fire hydrant at all times.

    [CGFR 69-53, 34 FR 11265, July 4, 1969, as amended by CGD 74-60, 41 FR 43151, Sept. 30, 1976]