Subpart 111.12 - Generator Construction and Circuits |
§ 111.12-1 - Prime movers.
-
§ 111.12-1 Prime movers. -
(a)Prime movers must meet
section 01–501–5 and
46 CFRsubpart 58.10 of this chapter except that those for mobile offshore drilling units must meet
Part 4, Chapter 3, sections 46–1–3/3.
173 and
46–1–3/3.
195 of the ABS
MODUMOU Rules (incorporated by reference; see
46 CFR 10–110–1 of this subchapter). Further requirements for emergency generator prime movers are in
46 CFRsubpart 112.50
.(b) Each generator prime mover must have an overspeed device that is independent of the normal operating governor and adjusted so that the speed cannot exceed the maximum rated speed by more than 15 percent.
[CGD 94–108, 61 FR 28277, June 4, 1996; 61 FR 33045, June 26, 1996, as amended at 62 FR 23907, May 1, 1997; USCG–2003–16630, 73 FR 65196, Oct. 31, 2008(c) Each prime mover must shut down automatically upon loss of lubricating pressure to the generator bearings if the generator is directly coupled to the engine. If the generator is operating from a power take-off, such as a shaft driven generator on a main propulsion engine, the generator must automatically declutch (disconnect) from the prime mover upon loss of lubricating pressure to generator bearings.