§ 111.60-2 - Specialty cable for communication and RF applications.  


Latest version.
  • § 111.60-2 Specialty cable for communication and RF applications.

    Specialty cable such as certain coaxial cable that cannot pass the flammability test contained in IEEE 1580, test FV–2/VW–1 of ANSI/UL 15812556, or Category A of IEC 60332–3–21:2018, or IEC 60332–3–22:2018 (all three standards incorporated by reference; see 46 CFR § 110.10–110–1 of this subchapter) because of unique properties of construction, must:

    (a) Be installed physically separate from all other cable; and

    (b) Have fire stops installed—

    (1) At least every 7 meters (21.5 feet) vertically, up to a maximum of 2 deck heights;

    (2) At least every 15 meters (46 feet) horizontally;

    (3) At each penetration of an A or B Class boundary;

    (4) At each location where the cable enters equipment; or

    (5) In a cableway that has an A–60 fire rating.

    [CGD 94–108, 61 FR 28280, June 4, 1996, as amended by USCG–2003–16630, 73 FR 65198, Oct. 31, 2008; USCG–2013–0671, 78 FR 60153, Sept. 30, 2013; USCG–2020–0075, 88 FR 16363, Mar. 16, 2023]