§ 161.002-6 - Testing requirements.  


Latest version.
  • § 161.002-6 Testing requirements.

    (a) Devices must be tested and listed for fire service by an accepted independent laboratory, as accepted in accordance with § 159.010 of this subchapter, or by a NRTL as set forth in 29 CFR 1910.7.

    (b) Each fire detection device must comply with the following standards (incorporated by reference, see § 161.002-1) as appropriate:

    (1) Control units - UL 864;

    (2) Heat detectors - UL 521;

    (3) Smoke detectors - UL 268;

    (4) Flame detectors - ANSI/FM 3260;

    (5) Audible alarms - UL 464 or UL 1480;

    (6) Visual alarms - UL 1971; and

    (7) Manual Signaling Boxes - UL 38.

    (c) All devices must be tested by an accepted independent laboratory, as defined in § 159.010 of this subchapter, to meet the marine environment testing requirements in Table 161.002-6(c) of this section. The test parameters are found in IEC 60092-504 (incorporated by reference, see § 161.002-1).

    Table 161.002-6(c) - Marine Environmental Testing Requirements

    IEC 60092-504 Environmental type test Category 1 Category 2 Category 3
    All spaces not Category 2 or 3 Open deck or open to weather Spaces containing navigation or communication equipment
    1 - Visual inspection X X X
    2 - Functional test X X X
    3 - High voltage test X X X
    4a - Power supply variations X X X
    4b - Power supply failure X X X
    5 - Insulation resistance X X X
    6 - Cold with gradual temp. change X (5 °C) X (−25 °C) X (5 °C)
    7 - Dry heat with gradual temp. change X (55 °C) X (55 °C) X (55 °C)
    8 - Damp heat, cyclic X X X
    9 - Salt mist X
    10 - Vibration (sinusoidal) X X X
    11b - Inclination, dynamic 1 X 1 X 1 X
    13 - Electrostatic discharge X X X
    14 - Electromagnetic field X X X
    15 - Conducted low frequency X X X
    16(a) - Conducted radio frequency (3 V rms) X
    16(b) - Conducted radio frequency (10 V rms) X X
    17 - Burst/fast transients X X X
    18 - Surge/slow transients X X X
    19(a) - Radiated emission (general power) X
    19(b) - Radiated emission (bridge and deck zone) X X
    20(a) - Conducted emission (general power) X
    20(b) - Conducted emission (bridge and deck zone) X X

    (d) All fire detection system control units and remote annunciators must have enclosure protection as outlined in part 5 of IEC 60092-504 (incorporated by reference, see § 161.002-1) if the requirements exceed those of 46 CFR 111.01-9. Otherwise, 46 CFR 111.01-9 must be complied with.