§ 434.512 - Internal loads.  


Latest version.
  • § 434.512 Internal loads.

    512.1 The systems and types of energy specified in this section are provided only for purposes of calculating the Energy Cost Budget. They are not requirements for either systems or the type of energy to be used in the Proposed Design or for calculation of Design Energy Cost.

    512.2 Internal loads for multi-family high-rise residential buildings are prescribed in Tables 512.2.a and b, Multi-Family High Rise Residential Building Schedules. Internal loads for other building types shall be modeled as noted in this subsection.

    Table 512.2. a - Multi-Family High Rise Residential Buildings Schedules - One-Zone Dwelling Unit

    [Internal loads per dwelling unit Btu/h]

    Hour Occupants Lights Equipment
    Sensible Latent Sensible Sensible Latent
    1 300 260 0 750 110
    2 300 260 0 750 110
    3 300 260 0 750 110
    4 300 260 0 750 110
    5 300 260 0 750 110
    6 300 260 0 750 110
    7 300 260 0 750 110
    8 210 260 980 1250 190
    9 100 80 840 2600 420
    10 100 80 0 1170 180
    11 100 80 0 1270 190
    12 100 80 0 2210 330
    13 100 80 0 2210 330
    14 100 80 0 1270 190
    15 100 80 0 1270 190
    16 100 80 0 1270 190
    17 100 80 0 1270 190
    18 300 260 0 3040 450
    19 300 260 0 3360 500
    20 300 260 960 1490 220
    21 300 260 960 1490 220
    22 300 260 960 1490 220
    23 300 260 960 1060 160
    24 300 260 960 1060 160

    Table 512.2. b - Multi-Family High Rise Residential Building Schedules-Two-Zone Dwelling Unit

    [Internal loads per dwelling unit Btu/h]

    Hour Bedrooms & bathrooms Other rooms
    Occupants Lights Equipment Occupants Lights Equipment
    Sensible Latent Sensible Sensible Latent Sensible Latent Sensible Sensible Latent
    1 300 260 0 750 110
    2 300 260 0 750 110
    3 300 260 0 750 110
    4 300 260 0 750 110
    5 300 260 0 750 110
    6 300 260 0 750 110
    7 300 260 0 750 110
    8 210 260 980 1250 190
    9 100 80 840 2600 420
    10 100 80 0 1170 180
    11 100 80 0 1270 190
    12 100 80 0 2210 330
    13 100 80 0 2210 330
    14 100 80 0 1270 190
    15 100 80 0 1270 190
    16 100 80 0 1270 190
    17 100 80 0 1270 190
    18 300 260 0 3040 450
    19 300 260 0 3360 500
    20 300 260 960 1490 220
    21 300 260 960 1490 220
    22 300 260 960 1490 220
    23 300 260 960 1060 160
    24 300 260 960 1060 160

    Table 512.2. b - Multi-Family High Rise Residential Building Schedules-Two-Zone Dwelling Unit

    [Internal loads per dwelling unit Btu/h]

    Hour Bedrooms & bathrooms Other rooms
    Occupants Lights Equipment Occupants Lights Equipment
    Sensible Latent Sensible Sensible Latent Sensible Latent Sensible Sensible Latent
    1 300 260 0 100 20 0 0 0 650 90
    2 300 260 0 100 20 0 0 0 650 90
    3 300 260 0 100 20 0 0 0 650 90
    4 300 260 0 100 20 0 0 0 650 90
    5 300 260 0 100 20 0 0 0 650 90
    6 300 260 0 100 20 0 0 0 650 90
    7 200 180 680 200 40 100 80 300 1050 150
    8 110 120 240 200 40 100 80 600 2400 380
    9 0 0 0 100 20 100 80 0 1070 160
    0 0 0 0 100 20 100 80 0 1170 170
    0 0 0 0 100 20 100 80 0 1170 170
    0 0 0 0 100 20 100 80 0 2110 310
    0 0 0 0 100 20 100 80 0 2110 310
    14 0 0 0 100 20 100 80 0 1170 170
    15 0 0 0 100 20 100 80 0 1170 170
    16 0 0 0 100 20 100 80 0 1170 170
    17 0 0 0 100 20 100 80 0 1170 170
    18 0 0 0 100 20 300 260 0 2940 430
    19 0 0 0 100 20 300 260 0 3260 480
    20 100 80 320 300 60 200 180 640 1190 160
    21 100 80 320 300 60 200 180 640 1190 160
    22 150 130 480 700 90 150 130 480 790 130
    23 300 260 640 410 70 0 0 320 650 90
    24 300 260 640 410 70 0 0 320 650 90