§ 169.672 - Wiring for power and lighting circuits.  


Latest version.
  • § 169.672 Wiring for power and lighting circuits.

    (a) Wiring for power and lighting circuits must have copper conductors, of 14 AWG or larger, and -

    (1) Meet Article 310-8 and Table 310-13 of the National Electrical Code;

    (2) Be listed as “50 volt boat cable”; or

    (3) Meet subpart 111.60 of this chapter.

    (b) Wiring for power and lighting circuits on new vessels must have stranded conductors.

    (c) Conductors must be sized so that -

    (1) They are adequate for the loads carried; and

    (2) The voltage drop at the load terminals is not more than 10 percent.