Code of Federal Regulations (Last Updated: July 5, 2024) |
Title 46 - Shipping |
Chapter I - Coast Guard, Department of Homeland Security |
SubChapter T - Small Passenger Vessels (Under 100 Gross Tons) |
Part 183 - Electrical Installation |
Subpart C - Power Sources and Distribution Systems |
§ 183.372 - Equipment and conductor grounding.
-
§ 183.372 Equipment and conductor grounding.
(a) All metallic enclosures and frames of electrical equipment must be permanently grounded to the hull on a metallic vessel. On a nonmetallic vessel, the enclosures and frames of electrical equipment must be bonded together to a common ground by a normally non-current carrying conductor. Metallic cases of instruments and secondary windings of instrument transformers must be grounded.
(b) On a nonmetallic vessel, where a ground plate is provided for radio equipment, it must be connected to the common ground.
(c) Equipment grounding conductors must be sized in accordance with Section 250-96 of NFPA 70 (incorporated by reference; see 46 CFR 175.600), or other standard specified by the Commandant.
(d) Each insulated grounding conductor of a cable must be identified by one of the following means:
(1) A green braid or green insulation;
(2) Stripping the insulation from the entire exposed length of the grounding conductor; or
(3) Marking the exposed insulation of the grounding conductor with green tape or green adhesive labels.
(e) Cable armor must not be used to ground electrical equipment or systems.
[CGD 85-080, 61 FR 997, Jan. 10, 1996, as amended by USCG-2003-16630, 73 FR 65210, Oct. 31, 2008]