§ 76.50-10 - Location.  


Latest version.
  • § 76.50-10 Location.

    (a) Approved portable and semi-portable extinguishers must be installed in accordance with table 76.50-10(a) of this section.

    (b) Table 76.50-10(a) indicates the minimum required number and type of extinguisher for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.

    Table 76.50 - 10(a) - Carriage of Portable and Semi-Portable Fire Extinguishers

    Space Fire extinguishing
    Minimum required rating Quantity and location
    Safety Area1
    Wheelhouse or fire control room 20-B:C 1 of each classification on vessels over 1,000 GT. (Not required in both spaces.) (Multiple classifications may be recognized.)
    Stairway and elevator enclosures None required.
    Communicating corridors 2-A 1 in each main corridor in each main vertical zone. (May be located in stairway enclosures.)
    Lifeboat embarkation and lowering stations None required.
    Radio room 20-B:C3 2 in the vicinity of the exit.2
    Accommodations1
    Staterooms, toilet spaces, isolated pantries, etc None required.
    Offices, lockers, and isolated storerooms None required.
    Public spaces 2-A 1 for each 2,500 sq ft or fraction thereof located in vicinity of the exits, except that none are required for spaces under 500 sq ft.
    Open decks or enclosed promenades None required.
    Service Spaces
    Galleys 40-B:C 1 for each 2,500 sq ft or fraction thereof suitable for hazards involved.
    Main pantries 2-A 1 for each 2,500 sq ft or fraction thereof located in the vicinity of the exits.
    Motion picture booths and film lockers 10-B:C3 1 outside in the vicinity of the exit.
    Paint and lamp rooms 40-B 1 outside space in the vicinity of the exit.
    Inaccessible baggage, mail, and specie rooms, and storerooms None required.
    Accessible baggage, mail, and specie rooms, and storerooms 2-A 1 for each 2,500 sq ft or fraction thereof located in the vicinity of the exits, either inside or outside the spaces.
    Refrigerated storerooms 2-A 1 for each 2,500 sq ft or fraction thereof located in the vicinity of the exits, outside the spaces.
    Carpenter, valet, photographic, printing shops sales rooms, etc 2-A 1 outside the space in the vicinity of the exit.
    Machinery Spaces
    Coal-fired boilers: Bunker and boiler space None required.
    Oil-fired boilers: Spaces, containing oil fired boilers, either main or auxiliary, or their fuel oil units 40-B 2 required.3
    160-B 1 required.4
    Internal combustion or gas turbine propelling machinery spaces 40-B 1 for each 1,000 brake horsepower, but not less than 2 or more than 6.
    120-B 1 required.5
    Electric propulsive motors or generators of open type 40-B:C 1 for each propulsion motor or generator unit.
    Enclosed ventilating systems for motors and generators of electric propelling machinery None required.
    Auxiliary spaces, internal combustion or gas turbine 40-B 1 outside the space in the vicinity of the exit.6
    Auxiliary spaces, electric emergency motors or generators 40-B:C 1 outside the space in the vicinity of the exit.6
    Auxiliary spaces, steam None required.
    Trunks to machinery spaces None required.
    Fuel tanks None required.
    Cargo Spaces
    Inaccessible during voyage, including trunks (excluding tanks) None required.
    Accessible during voyage 2-A 1 for each 1,200 sq ft or fraction thereof.
    Vehicular spaces (covered by a sprinkler system) 40-B 1, plus 1 for each 6,000 sq ft or fraction thereof.
    Vehicular spaces (not covered by a sprinkler system) 40-B 1, plus 1 for each 1,500 sq ft or fraction thereof.7
    Cargo oil tanks None required.
    Spare Units
    2-A 10 percent of the required number for public spaces rounded up.
    40-B 10 percent of the required number for cargo spaces rounded up.
    40-B:C 1.

    (c) Semi-portable fire extinguishing systems must be located in the open so as to be readily seen.

    (d) If portable fire extinguishers are not located in the open or behind glass so that they may be readily seen, they may be placed in enclosures together with the firehose, provided such enclosures are marked as required by § 78.47-20 of this subchapter.

    (e) Portable fire extinguishers and their stations must be numbered in accordance with § 78.47-30 of this subchapter.

    (f) Portable or semi-portable extinguishers, which are required on their nameplates to be protected from freezing, must not be located where freezing temperatures may be expected.

    [USCG-2012-0196, 81 FR 48259, July 22, 2016]