Code of Federal Regulations (Last Updated: October 10, 2024) |
Title 10 - Energy |
Chapter II - Department of Energy |
SubChapter D - Energy Conservation |
Part 431 - Energy Efficiency Program for Certain Commercial and Industrial Equipment |
Subpart K - Distribution Transformers |
Energy Conservation Standards |
§ 431.196 - Energy conservation standards and their effective dates.
-
§ 431.196 Energy conservation standards and their effective dates.
(a) Low-Voltage Dry-Type Distribution Transformers.
(1) The efficiency of a low-voltage, dry-type distribution transformer manufactured on or after January 1, 2007, but before January 1, 2016, shall be no less than that required for the applicable kVA rating in the table below. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase Three-phase kVA % kVA % 15 97.7 15 97.0 25 98.0 30 97.5 37.5 98.2 45 97.7 50 98.3 75 98.0 75 98.5 112.5 98.2 100 98.6 150 98.3 167 98.7 225 98.5 250 98.8 300 98.6 333 98.9 500 98.7 750 98.8 1000 98.9 Note 1 to paragraph (a)(1):All efficiency values are at 35 percent per-unit load.
(2) The efficiency of a low-voltage, dry-type distribution transformer manufactured on or after January 1, 2016, but before April 23, 2029, shall be no less than that required for their the applicable kVA rating in the following table below. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
2 to paragraph (a)(2)Table 2 to Paragraph (a)(1)
Single-phase Three-phase kVA Efficiency (%) kVA Efficiency (%) 15 97.70 15 97.89 25 98.00 30 98.23 37.5 98.20 45 98.40 50 98.30 75 98.60 75 98.50 112.5 98.74 100 98.60 150 98.83 167 98.70 225 98.94 250 98.80 300 99.02 333 98.90 500 99.14 750 99.23 1000 99.28 per(3) The efficiency of a low-voltage dry-type distribution transformer manufactured on or after April 23, 2029, shall be no less than that required for their kVA rating in the following table. Low-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 3 to Paragraph (a)(3)
Single-phase Three-phase kVA Efficiency
(%)kVA Efficiency
(%)15 98.39 15 98.31 25 98.60 30 98.58 37.5 98.74 45 98.72 50 98.81 75 98.88 75 98.95 112.5 98.99 100 99.02 150 99.06 167 99.09 225 99.15 250 99.16 300 99.22 333 99.23 500 99.31 750 99.38 1000 99.42 unit load(b) Liquid-Immersed Distribution Transformers.
(1) The efficiency of a liquid-immersed distribution transformer manufactured on or after January 1, 2010, but before January 1, 2016, shall be no less than that required for their kVA rating in the table below. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase Three-phase kVA Efficiency
(%)kVA Efficiency
(%)10 98.62 15 98.36 15 98.76 30 98.62 25 98.91 45 98.76 37.5 99.01 75 98.91 50 99.08 112.5 99.01 75 99.17 150 99.08 100 99.23 225 99.17 167 99.25 300 99.23 250 99.32 500 99.25 333 99.36 750 99.32 500 99.42 1000 99.36 667 99.46 1500 99.42 833 99.49 2000 99.46 2500 99.49 Note 3 to paragraph (b)(1):All efficiency values are at 50 percent per-unit load.
(2) The efficiency of a liquid-immersed distribution transformer, including submersible distribution transformers, manufactured on or after January 1, 2016, but before April 23, 2029, shall be no less than that required for their kVA rating in the following table below. Liquid-immersed distribution transformers, including submersible distribution transformers, with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 5 to Paragraph (b)(2)
Single-phase Three-phase kVA Efficiency
(%)kVA Efficiency
(%)10 98.70 15 98.65 15 98.82 30 98.83 25 98.95 45 98.92 37.5 99.05 75 99.03 50 99.11 112.5 99.11 75 99.19 150 99.16 100 99.25 225 99.23 167 99.33 300 99.27 250 99.39 500 99.35 333 99.43 750 99.40 500 99.49 1000 99.43 667 99.52 1500 99.48 833 99.55 2000 99.51 2500 99.53 (3) The efficiency of a liquid-immersed distribution transformer, that is not a submersible distribution transformer, manufactured on or after April 23, 2029, shall be no less than that required for their kVA rating in the following table. Liquid-immersed distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 6 to Paragraph (b)(3)
Single-phase Three-phase kVA Efficiency
(%)kVA Efficiency
(%)10 98.77 15 98.92 15 98.88 30 99.06 25 99.00 45 99.14 37.5 99.10 75 99.22 50 99.15 112.5 99.29 75 99.23 150 99.33 100 99.29 225 99.38 167 99.46 300 99.42 250 99.51 500 99.38 333 99.54 750 99.43 500 99.59 1000 99.46 667 99.62 1500 99.51 833 99.64 2000 99.53 2500 99.55 3750 99.54 5000 99.53 to paragraph(4
2)) The efficiency of a submersible distribution transformer, manufactured on or after April 23, 2029, shall be no less than that required for their kVA rating in the following table. Submersible distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 7 to Paragraph (b)(
per4)
Single-phase Three-phase kVA Efficiency
(%)kVA Efficiency
(%)10 98.70 15 98.65 15 98.82 30 98.83 25 98.95 45 98.92 37.5 99.05 75 99.03 50 99.11 112.5 99.11 75 99.19 150 99.16 100 99.25 225 99.23 167 99.33 300 99.27 250 99.39 500 99.35 333 99.43 750 99.40 500 99.49 1000 99.43 667 99.52 1500 99.48 833 99.55 2000 99.51 2500 99.53 unit load(c) Medium-Voltage Dry-Type Distribution Transformers.
(1) The efficiency of a medium-voltage dry-type distribution transformer manufactured on or after January 1, 2010, but before January 1, 2016, shall be no less than that required for their kVA and BIL rating in the table below. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Single-phase Three-phase kVA BIL* kVA BIL 20-45 kV 46-95 kV ≥96 kV 20-45 kV 46-95 kV ≥96 kV Efficiency
(%)Efficiency
(%)Efficiency
(%)Efficiency
(%)Efficiency
(%)Efficiency
(%)15 98.10 97.86 15 97.50 97.18 25 98.33 98.12 30 97.90 97.63 37.5 98.49 98.30 45 98.10 97.86 50 98.60 98.42 75 98.33 98.12 75 98.73 98.57 98.53 112.5 98.49 98.30 100 98.82 98.67 98.63 150 98.60 98.42 167 98.96 98.83 98.80 225 98.73 98.57 98.53 250 99.07 98.95 98.91 300 98.82 98.67 98.63 333 99.14 99.03 98.99 500 98.96 98.83 98.80 500 99.22 99.12 99.09 750 99.07 98.95 98.91 667 99.27 99.18 99.15 1000 99.14 99.03 98.99 833 99.31 99.23 99.20 1500 99.22 99.12 99.09 2000 99.27 99.18 99.15 2500 99.31 99.23 99.20 Note 5 to paragraph (c)(1):All efficiency values are at 50 percent per-unit load.
(2) The efficiency of a medium-voltage dry-type distribution transformer manufactured on or after January 1, 2016, but before April 23, 2029, shall be no less than that required for their kVA and BIL rating in the following table below. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
6 to paragraph (c)(2)Table 9 to Paragraph (c)(2)
kVA Single-phase kVA Three-phase kVA BIL* kVA 1 BIL 20-45 kV 46-95 kV ≥96 kV 20-45 kV 46-95 kV ≥96 kV Efficiency
(%)Efficiency
(%)Efficiency
(%)Efficiency
(%)Efficiency
(%)Efficiency
(%)15 98.10 97.86 15 97.50 97.18 25 98.33 98.12 30 97.90 97.63 37.5 98.49 98.30 45 98.10 97.86 50 98.60 98.42 75 98.33 98.13 75 98.73 98.57 98.53 112.5 98.52 98.36 100 98.82 98.67 98.63 150 98.65 98.51 167 98.96 98.83 98.80 225 98.82 98.69 98.57 250 99.07 98.95 98.91 300 98.93 98.81 98.69 333 99.14 99.03 98.99 500 99.09 98.99 98.89 500 99.22 99.12 99.09 750 99.21 99.12 99.02 667 99.27 99.18 99.15 1000 99.28 99.20 99.11 833 99.31 99.23 99.20 1500 99.37 99.30 99.21 2000 99.43 99.36 99.28 2500 99.47 99.41 99.33 per-unit load(3) The efficiency of a medium-voltage dry-type distribution transformer manufactured on or after April 23, 2029, shall be no less than that required for their kVA and BIL rating in the following table. Medium-voltage dry-type distribution transformers with kVA ratings not appearing in the table shall have their minimum efficiency level determined by linear interpolation of the kVA and efficiency values immediately above and below that kVA rating.
Table 10 to Paragraph (c)(3)
kVA Single-phase kVA Three-phase BIL1 BIL 20-45 kV 46-95 kV ≥96 kV 20-45 kV 46-95 kV ≥96 kV Efficiency
(%)Efficiency
(%)Efficiency
(%)Efficiency
(%)Efficiency
(%)Efficiency
(%)15 98.29 98.07 15 97.75 97.46 25 98.50 98.31 30 98.11 97.87 37.5 98.64 98.47 45 98.29 98.07 50 98.74 98.58 75 98.50 98.32 75 98.86 98.71 98.68 112.5 98.67 98.52 100 98.94 98.80 98.77 150 98.79 98.66 167 99.06 98.95 98.92 225 98.94 98.82 98.71 250 99.16 99.06 99.02 300 99.04 98.93 98.82 333 99.23 99.13 99.09 500 99.18 99.09 99.00 500 99.30 99.21 99.18 750 99.29 99.21 99.12 667 99.34 99.26 99.24 1000 99.35 99.28 99.20 833 99.38 99.31 99.28 1500 99.43 99.37 99.29 2000 99.49 99.42 99.35 2500 99.52 99.47 99.40 3750 99.50 99.44 99.40 5000 99.48 99.43 99.39 (d) Mining Distribution Transformers. [Reserved]
(e) Severability. The provisions of paragraphs (a) through (d) of this section are separate and severable from one another. Should a court of competent jurisdiction hold any provision(s) of this section to be stayed or invalid, such action shall not affect any other provision of this section.
[78 FR 23433, Apr. 18, 2013, as amended at 86 FR 51252, Sept. 14, 2021; 89 FR 30040, Apr. 22, 2024]