§ 513.1 - Occupancy.  


Latest version.
  • 5131Occupancy schedules are default assumptions. The same assumptions shall be made in computing Design Energy Consumption as were used in calculating the Energy Cost Budget.

    513.2Table 513.2.a, Occupancy Density, establishes the density, in ft2 person of conditioned floor area, to be used for each building type. Table 513.2.b, Building Schedule Percentage Multipliers, establishes the percentage of total occupants in the building by hour of the day for each building type.

    Table 513.2.a.—Occupancy DensityBuilding typeConditioned floor area Ft 2 personAssembly50Office275Retail300Warehouse15000School75Hotel/Motel250Restaurant100Health/Institutional200Multi-family High-rise Residential2 per unit .11 Heat generation: Btu/h per person: 230 Btu/h per person sensible, and 190 Btu/h per person latent. See Tables 512.2 a and b. ER06OC00.012 ER06OC00.013 ER06OC00.014 ER06OC00.015 ER06OC00.016