§ 460.204 - Mechanical ventilation fan efficacy.
Latest version.
-
§ 460.204 Mechanical ventilation fan efficacy.
(a) Whole-house mechanical ventilation system fans must meet the minimum efficacy requirements set forth in table 1 to 460.204(a), except as provided in paragraph (b) of this section. The mechanical ventilation fan efficacy requirements are adapted from section R403 of the 2021 IECC.
Table 1 to § 460.204(a) - Mechanical Ventilation System Fan Efficacy
Fan type description Airflow rate
minimum
(cfm)Minimum
efficacy
(cfm/watt)Heat recovery ventilator or energy recovery ventilator Any 1.2 In-line supply or exhaust fans Any 3.8 Other exhaust fan <90 2.8 Other exhaust fan ≥90 3.5 (b) Mechanical ventilation fans that are integral to heating, ventilating, and air conditioning equipment, including furnace fans as defined in § 430.2 of this subchapter, are not subject to the efficiency requirements in paragraph (a) of this section.