§ 18.24 - Electrical clearances.  


Latest version.
  • § 18.24 Electrical clearances.

    Minimum clearances between uninsulated electrical conductor surfaces, or between uninsulated conductor surfaces and grounded metal surfaces, within the enclosure shall be as follows:

    Minimum Clearances Between Uninsulated Surfaces

    Phase-to-Phase Voltage (rms) Clearances (inches)
    Phase-to-Phase Phase-to-Ground or Control Circuit
    0 to 250 0.25 0.25
    251 to 600 0.28 0.25
    601 to 1000 0.61 0.25
    1001 to 2400 1.4 0.6
    2401 to 4160 3.0 1.4

    [57 FR 61209, Dec. 23, 1992]