§ 627.48 - Toxins.


Latest version.
  • General requirements for all facilities in which toxins are used are as follows. Such facilities will—

    (a) Have a ventilation system that provides three to six air changes per hour, and that provides a directional airflow inward relative to the access halls.

    (b) Have a sink for handwashing.

    (c) Have an eyewash available.

    (d) Have bench tops that are impervious to water and resistant to acids, alkalis, organic solvents, and moderate heat.

    (e) Have furniture, furnishings, and surfaces that are sturdy and designed to be easily cleaned.

    (f) Be arranged so that items are accessible for cleaning.

    (g) Have a quick-drench shower available within the facility.

    (h) A fume hood, biological safety cabinet, glove box, or equivalent engineering control equipped with HEPA filters and with charcoal filters if volatile materials are being used.