§ 149.513 - Landing area with a fueling facility.
Latest version.
-
In addition to the requirements in § 149.483 each helicopter landing area on the PPC with a fueling facility must have:
(a) At least two USCG Type B:C, size II dry chemical extinguishers and at least one USCG Type B:C, size V dry chemical extinguisher; and
(b) A USCG Type B:C, size II dry chemical extinguisher at the emergency control station.