§ 149.660 - What are the requirements for emergency power?


Latest version.
  • § 149.660 What are the requirements for emergency power?

    (a) Each pumping platform complex must have emergency power equipment including a power source, associated transforming equipment, and a switchboard to provide power to simultaneously operate all of the following for a continuous period of 18 hours:

    (1) Emergency lighting circuits;

    (2) Aids to navigation equipment;

    (3) Communications equipment;

    (4) Radar equipment;

    (5) Alarm systems;

    (6) Electrically operated fire pumps; and

    (7) Other electrical equipment identified as emergency equipment in the operations manual for the deepwater port.

    (b) The equipment required by paragraph (a) of this section must:

    (1) All be located in the same space; and

    (2) Contain only machinery and equipment for the supply of emergency power (i.e., no oil or natural gas transfer pumping equipment) in accordance with 46 CFR 112.05.

    [USCG-1998-3884, 71 FR 57651, Sept. 29, 2006, as amended by USCG-2013-0397, 78 FR 39180, July 1, 2013]