§ 154.820 - Fire, explosion, and detonation protection.  


Latest version.
  • (a) A vapor control system with a single facility vapor connection that receives vapor only from a vessel with inerted cargo tanks and processes vapor with a vapor recovery unit must:

    (1) Be capable of inerting the vapor collection line in accordance with §154.824(a) of this subpart prior to receiving vapors from the vessel;

    (2) Have at least one oxygen analyzer that samples the vapor concentration continuously at a point not more than 6 meters (19.7 ft.) from the facility vapor connection; and

    (3) Meet §154.824 (f)(1), (f)(2), (g), (h)(2), and (h)(3) of this subpart.

    (b) A vapor control system with a single facility vapor connection that receives vapor only from a vessel with inerted cargo tanks and processes vapor with a vapor destruction unit must:

    (1) Have a detonation arrester located not more than 6 meters (19.7 ft.) from the facility vapor connection; or

    (2) Have an inerting system that meets the requirements of §154.824 of this subpart.

    (c) A vapor control system with a single facility vapor connection that receives vapor from a vessel with cargo tanks that are not inerted and processes vapor with a vapor recovery unit must:

    (1) Have a detonation arrester located not more than 6 meters (19.7 ft.) from the facility vapor connection; or

    (2) Have an inerting, enriching, or diluting system that meets the requirements of §154.824 of this subpart.

    (d) A vapor control system with a single facility vapor connection that receives vapor from a vessel with cargo tanks that are not inerted and processes the vapor with a vapor destruction unit must:

    (1) Have a detonation arrester located not more than 6 meters (19.7 ft.) from the facility vapor connection; and

    (2) Have an inerting, enriching, or diluting system that meets the requirements of §154.824 of this subpart.

    (e) A vapor control system with multiple facility vapor connections that processes vapor with a vapor recovery unit must have a detonation arrester located not more than 6 meters (19.7 ft.) from each facility vapor connection.

    (f) A vapor control system with multiple facility vapor connections that processes vapor with a vapor destruction unit must:

    (1) Have a detonation arrester located not more than 6 meters (19.7 ft.) from each facility vapor connection; and

    (2) Have an inerting, enriching, or diluting system that meets the requirements of §154.824 of this subpart.

    (g) A vapor control system that uses a vapor balancing system in which cargo vapor from a vessel is transferred through the facility vapor collection system to facility storage tanks must:

    (1) Have a detonation arrester located not more than 6 meters (19.7 ft.) from each facility vapor connection;

    (2) Have a detonation arrester located within the storage tank containment area as close as practical to the vapor return connection of each facility storage tank; and

    (3) Have facility storage tank high level alarm systems and facility storage tank overfill control systems arranged to prevent cargo from entering the vapor return line.

    (h) Except for a discharge vent from a vapor destruction unit, each outlet of a vapor control system that vents to atmosphere and is not isolated with a pressure-vacuum relief valve must have a flame arrester located at the outlet.