§ 154.828 - Vapor recovery and vapor destruction units.  


Latest version.
  • (a) The inlet to a vapor recovery unit which receives cargo vapor that has not been inerted, enriched, or diluted in accordance with § 154.824 of this subpart must be fitted with one of the following:

    (1) A detonation arrester;

    (2) A flame arrester; or

    (3) An explosion suppression system acceptable to the Commandant (CG-522).

    (b) The inlet to a vapor destruction unit must:

    (1) Have a liquid seal; and

    (2) Have two quick-closing stop valves installed in the vapor line.

    (c) A vapor destruction unit must:

    (1) Not be within 30 meters (98.8 ft.) of any tank vessel berth or mooring at the facility;

    (2) Have a flame arrester or detonation arrester fitted in the vapor line; and

    (3) Alarm and shut down when a flame is detected on the flame arrester or detonation arrester.

    (d) When a vapor destruction unit shuts down or has a flame-out condition the vapor destruction unit control system must:

    (1) Close the quick-closing stop valves required by paragraph (b)(2) of this section; and

    (2) Close the remotely operated cargo vapor shutoff valve required by § 154.810(a) of this subpart.

    [CGD 88-102, 55 FR 25429, June 21, 1990, as amended by CGD 96-026, 61 FR 33666, June 28, 1996; USCG-2010-0351, 75 FR 36284, June 25, 2010]