§ 17.217 - Domiciliary and nursing home care program.  


Latest version.
  • (a) Objective. Domiciliary and nursing home care facilities should provide a therapeutic, rehabilitative, safe and home-like environment to assist in maintaining or restoring veterans to the highest level of functioning. Long-term care facilities shall be designed to encourage and facilitate participation in therapeutic programs.

    (b) General. All newly constructed domiciliary beds shall meet nursing home care construction standards and be suitable to provide for future conversion to nursing home care if needed. The Department of Veterans Affairs may waive this requirement if the State shows that it will need domiciliary beds more than nursing home beds for eligible veterans. See § 17.222 of this part.

    (c) Nursing units. A nursing unit with related facilities will normally be constructed so that nurses may supervise 30 to 60 patients. If there are design limitations, fewer beds are permissible. A 30-bed unit with a centrally located nursing station is preferred on skilled care units to provide efficient use of staff. A design that minimizes the distance between rooms and nursing stations is recommended. Patient storage may be planned in each nursing unit for bulky clothing that will not fit into patients’ closets. A nurses’ call system shall be required for nursing units. Each patient shall be furnished with an audiovisual or visual nurses’ call system which will register a call from the patient with the signal light above the corridor door and at the nursing station in hospitals and nursing homes. An empty conduit system shall be installed for domiciliaries for use in a potential future conversion to a nursing home. A nursing call system shall also be provided in each patient's toilet room and bathroom. Wiring for a nurses’ call system shall be installed in conduit.

    (d) Bed configurations. At least 80 percent of the total beds should be in single and/or double bed rooms. Rooms shall have no more than four beds. Two large two-bed rooms are allowed for a 50-60 bed unit. Adequate space should be provided to allow access to three sides of each bed for the staff to work and utilize medical and emergency equipment.

    (e) Patient bedrooms. Each bedroom shall have direct access to an enclosed toilet and lavatory. The percentage of the patient bedrooms that shall be accessible to the physically handicapped must comply with UFAS requirements. These rooms must include UFAS clearances around beds and 5-foot wheelchair turning radius. Individual privacy should be provided by screens, privacy curtains, or similar approaches in bedrooms for more than one patient. No patient room shall be located on a floor which is more than 50 percent below grade level. It is desirable that patient rooms include:

    (1) Wardrobes with closets and drawers large enough to accommodate the personal clothing of patients who require care for an extended period of time.

    (2) Room for a desk, lounge chair, television, and other personal belongings.

    (3) Total electric beds.

    (4) A sink and mirror.

    (5) Piped oxygen and vacuum suction for patients as required.

    (6) Operable windows to allow access to air. The sill shall be low enough to permit patients to view the ground while sitting.

    (f) Patient room toilets. Patient toilets must be designed for maximum accessibility and safety for the patients and to facilitate staff assistance. One toilet/bathroom for each bedroom is preferred with a maximum of four beds for each bathroom. Shower/tub rooms should provide an area for setting clean clothes and supplies. Adequate ventilation should be provided to prevent condensation and mildew. The percentage of the patient toilets/bathrooms that are accessible to the physically handicapped must comply with UFAS requirements. These rooms must include UFAS clearances, grab bar configurations, and mounting heights. Alternative grab bar configurations may be used for the remaining percentage of patient toilets/bathrooms as approved by the Department of Veterans Affairs.

    (g) Reception and control. Information, telephone, switchboard, mailboxes, and control center facilities should be located adjacent to the main lobby entrance. The information desk serves as a first point of contract, information, and control area for those entering for admission, a visit, or business.

    (h) Administrator/Director's suite. The project may include an administrator/director's suite to include all administrative activities required by the Director, Assistant Director, and their immediate staffs, including secretaries, analysts, administrative assistants, and/or trainees.

    (i) Dietetic Service. Dietetic Service facilities such as an office for the dietitian, a kitchen, a dishwashing room, adequate refrigeration, dry storage, receiving area, and garbage facilities should be provided as required. It is desirable to have eating areas on each unit that have a sink, toilet facilities, and storage, that can accommodate wheelchairs and gerichairs, while still being attractive and appealing for dining. Tables should be able to accommodate three to four wheelchairs. Buffet lines may be provided on the unit to allow some choice for patients who cannot get to the main dining room.

    (1) Dining room, food preparation, and dishwashing facilities may be planned as separate facilities from Dietetic Service area, if appropriate.

    (2) Space for vending machines may be provided.

    (j) Therapy and treatment programs. Facilities for rehabilitation medicine, physical, occupational, and recreational therapies and other programs shall be planned by the State to meet program requirements and standards of care prescribed by the Department of Veterans Affairs. In addition to the patient therapy spaces, offices may be provided. Medical support areas should be planned to meet program requirements and standards and may include areas for rehabilitation, recreation, dental care and other medical support services.

    (k) Janitors closet. One janitors closet should be planned for each nursing unit, in the dietetic area, and in the general administrative and clinical space with at least one on each floor. The kitchen and other areas which generate waste or require special care should have their own janitors closet. Convenient storage for floor cleaning machines may also be provided.

    (l) Staff facilities. Staff toilets should be provided on each floor. Each facility should have an employee locker and lounge.

    (m) Conference room/In-service training. A conference room which may also be used for staff training and development may be provided. Family and group counseling rooms may also be provided.

    (n) Lounges/recreation. Two patient lounges which will accommodate large numbers of wheelchair/gerichairs should be considered. Lounges may be separated, one for smokers and one for non-smokers. Lounges should be directly visible from the nursing station or adjacent to the nursing station. Atriums may be planned on the nursing unit, or provisions may be made for access to an outdoor sundeck or patio. An outdoor recreation/patio space should be developed adjacent to a common use area. Every effort should be made to reduce the noise levels on the nursing unit by using noise reducing materials in construction and decorating.

    (o) Miscellaneous space. The State home may include space for a library, barber and/or beauty shop, retail sales, canteen, mailroom, chapel, and computer communications area. Space for a child day care center may be planned if it will primarily serve the needs of persons employed by the State home. Whirlpools and wheelchair scales may be provided for each State home built to nursing home standards. Other spaces in the State home must be fully justified by the applicant and approved by the Department of Veterans Affairs before the Department of Veterans Affairs can participate in funding the cost of the area.