Table 1 to Subpart CCCC of Part 60 - Emission Limitations for Incinerators for Which Construction Is Commenced After November 30, 1999, But No Later Than June 4, 2010, or for Which Modification or Reconstruction Is Commenced on or After June 1, 2001, But No Later Than August 7, 2013  


Latest version.
  • Table 1 to Subpart CCCC of Part 60 - Emission Limitations for Incinerators for Which Construction is Commenced After November 30, 1999, But no Later Than June 4, 2010, or for Which Modification or Reconstruction is Commenced on or After June 1, 2001, But no Later Than August 7, 2013

    For the air pollutant You must meet this
    emission limitation1
    Using this averaging time2 And determining compliance
    using this method2
    Cadmium 0.004 milligrams per dry standard cubic meter 3-run average (1 hour minimum sample time per run) Performance test (Method 29 of appendix A of this part).
    Carbon monoxide 157 parts per million by dry volume 3-run average (1 hour minimum sample time per run) Performance test (Method 10 at 40 CFR part 60, appendix A-4).
    Dioxin/Furan (toxic equivalency basis) 0.41 nanograms per dry standard cubic meter 3-run average (collect a minimum volume of 4 dry standard cubic meters per run) Performance test (Method 23 of appendix A-7 of this part).
    Hydrogen chloride 62 parts per million by dry volume 3-run average (For Method 26, collect a minimum volume of 120 liters per run. For Method 26A, collect a minimum volume of 1 dry standard cubic meter per run) Performance test (Method 26 or 26A at 40 CFR part 60, appendix A-8).
    Lead 0.04 milligrams per dry standard cubic meter 3-run average (1 hour minimum sample time per run) Performance test (Method 29 of appendix A of this part).
    Mercury 0.47 milligrams per dry standard cubic meter 3-run average (1 hour minimum sample time per run) Performance test (Method 29 of appendix A of this part).
    Nitrogen oxides 388 parts per million by dry volume 3-run average (for Method 7E, 1 hour minimum sample time per run) Performance test (Method 7 or 7E at 40 CFR part 60, appendix A-4).
    Opacity 10 percent 6-minute averages Performance test (Method 9 of appendix A of this part).
    Particulate matter 70 milligrams per dry standard cubic meter 3-run average (1 hour minimum sample time per run) Performance test (Method 5 or 29 of appendix A of this part).
    Sulfur dioxide 20 parts per million by dry volume 3-run average (For Method 6, collect a minimum volume of 20 liters per run. For Method 6C, collect sample for a minimum duration of 1 hour per run) Performance test (Method 6 or 6C at 40 CFR part 60, appendix A-4).