Table 3 to Subpart HHH of Part 62 - Operating Parameters To Be Monitored and Minimum Measurement and Recording Frequencies


Latest version.
  • Table 3 to Subpart HHH of Part 62 - Operating Parameters To Be Monitored and Minimum Measurement and Recording Frequencies

    Operating
    parameters
    to be
    monitored
    Minimum frequency HMIWI
    Data measurement Data recording HMIWI with combustion control only HMIWI with dry scrubber followed by FF HMIWI with wet scrubber HMIWI with dry scrubber followed by FF and wet scrubber HMIWI with SNCR system
    Maximum operating parameters:
    Maximum charge rate Once per charge Once per charge
    Maximum FF inlet temperature Continuous Once per minute
    Maximum flue gas temperature Continuous Once per minute
    Minimum operating parameters:
    Minimum secondary chamber temperature Continuous Once per minute
    Minimum dioxin/furan sorbent flow rate Hourly Once per hour
    Minimum HCl sorbent flow rate Hourly Once per hour
    Minimum mercury (Hg) sorbent flow rate Hourly Once per hour
    Minimum pressure drop across the wet scrubber or minimum horsepower or amperage to wet scrubber Continuous Once per minute
    Minimum scrubber liquor flow rate Continuous Once per minute
    Minimum scrubber liquor pH Continuous Once per minute
    Minimum reagent flow rate Hourly Once per hour