Code of Federal Regulations (Last Updated: November 8, 2024) |
Title 40 - Protection of Environment |
Chapter I - Environmental Protection Agency |
SubChapter C - Air Programs |
Part 63 - National Emission Standards for Hazardous Air Pollutants for Source Categories |
Subpart DDDDD - National Emission Standards for Hazardous Air Pollutants for Major Sources: Industrial, Commercial, and Institutional Boilers and Process Heaters |
Table 2 to Subpart DDDDD of Part 63 - Emission Limits for Existing Boilers and Process Heaters d
Latest version.
-
Table 2 to Subpart DDDDD of Part 63 - Emission Limits for Existing Boilers and Process Heaters
As stated in § 63.7500, you must comply with the following applicable emission limits:
[Units with heat input capacity of 10 million Btu per hour or greater]
If your boiler or process heater is in this subcategory . . . For the following
pollutants . . .The emissions must not exceed the following emission limits, except during startup and shutdown . . . The emissions must not exceed the following alternative output-based limits, except during startup and
shutdown . . .Using this specified sampling volume or test run
duration . . .1. Units in all subcategories designed to burn solid fuel a. HCl 2.2E-02 lb per MMBtu of heat input 2.5E-02 lb per MMBtu of steam output or 0.27 lb per MWh For M26A, Collect a minimum of 1 dscm per run; for M26, collect a minimum of 120 liters per run. b. Mercury 5.7E-06 lb per MMBtu of heat input 6.4E-06 lb per MMBtu of steam output or 7.3E-05 lb per MWh For M29, collect a minimum of 3 dscm per run; for M30A or M30B, collect a minimum sample as specified in the method; for ASTM D6784b collect a minimum of 3 dscm. 2. Units design to burn coal/solid fossil fuel a. Filterable PM (or TSM) 4.0E-02 lb per MMBtu of heat input; or (5.3E-05 lb per MMBtu of heat input) 4.2E-02 lb per MMBtu of steam output or 4.9E-01 lb per MWh; or (5.6E-05 lb per MMBtu of steam output or 6.5E-04 lb per MWh) Collect a minimum of 2 dscm per run. 3. Pulverized coal boilers designed to burn coal/solid fossil fuel a. CO (or CEMS) 130 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average; or (320 ppm by volume on a dry basis corrected to 3 percent oxygen,c 30-day rolling average) 0.11 lb per MMBtu of steam output or 1.4 lb per MWh; 3-run average 1 hr minimum sampling time. 4. Stokers/others designed to burn coal/solid fossil fuel a. CO (or CEMS) 160 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average; or (340 ppm by volume on a dry basis corrected to 3 percent oxygen,c 30-day rolling average) 0.14 lb per MMBtu of steam output or 1.7 lb per MWh; 3-run average 1 hr minimum sampling time. 5. Fluidized bed units designed to burn coal/solid fossil fuel a. CO (or CEMS) 130 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average; or (230 ppm by volume on a dry basis corrected to 3 percent oxygen,c 30-day rolling average) 0.12 lb per MMBtu of steam output or 1.4 lb per MWh; 3-run average 1 hr minimum sampling time. 6. Fluidized bed units with an integrated heat exchanger designed to burn coal/solid fossil fuel a. CO (or CEMS) 140 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average; or (150 ppm by volume on a dry basis corrected to 3 percent oxygen,c 30-day rolling average) 1.3E-01 lb per MMBtu of steam output or 1.5 lb per MWh; 3-run average 1 hr minimum sampling time. 7. Stokers/sloped grate/others designed to burn wet biomass fuel a. CO (or CEMS) 1,500 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average; or (720 ppm by volume on a dry basis corrected to 3 percent oxygen,c 30-day rolling average) 1.4 lb per MMBtu of steam output or 17 lb per MWh; 3-run average 1 hr minimum sampling time. b. Filterable PM (or TSM) 3.7E-02 lb per MMBtu of heat input; or (2.4E-04 lb per MMBtu of heat input) 4.3E-02 lb per MMBtu of steam output or 5.2E-01 lb per MWh; or (2.8E-04 lb per MMBtu of steam output or 3.4E-04 lb per MWh) Collect a minimum of 2 dscm per run. 8. Stokers/sloped grate/others designed to burn kiln-dried biomass fuel a. CO 460 ppm by volume on a dry basis corrected to 3 percent oxygen 4.2E-01 lb per MMBtu of steam output or 5.1 lb per MWh 1 hr minimum sampling time. b. Filterable PM (or TSM) 3.2E-01 lb per MMBtu of heat input; or (4.0E-03 lb per MMBtu of heat input) 3.7E-01 lb per MMBtu of steam output or 4.5 lb per MWh; or (4.6E-03 lb per MMBtu of steam output or 5.6E-02 lb per MWh) Collect a minimum of 1 dscm per run. 9. Fluidized bed units designed to burn biomass/bio-based solid a. CO (or CEMS) 470 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average; or (310 ppm by volume on a dry basis corrected to 3 percent oxygen,c 30-day rolling average) 4.6E-01 lb per MMBtu of steam output or 5.2 lb per MWh; 3-run average 1 hr minimum sampling time. b. Filterable PM (or TSM) 1.1E-01 lb per MMBtu of heat input; or (1.2E-03 lb per MMBtu of heat input) 1.4E-01 lb per MMBtu of steam output or 1.6 lb per MWh; or (1.5E-03 lb per MMBtu of steam output or 1.7E-02 lb per MWh) Collect a minimum of 1 dscm per run. 10. Suspension burners designed to burn biomass/bio-based solid a. CO (or CEMS) 2,400 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average; or (2,000 ppm by volume on a dry basis corrected to 3 percent oxygen,c 10-day rolling average) 1.9 lb per MMBtu of steam output or 27 lb per MWh; 3-run average 1 hr minimum sampling time. b. Filterable PM (or TSM) 5.1E-02 lb per MMBtu of heat input; or (6.5E-03 lb per MMBtu of heat input) 5.2E-02 lb per MMBtu of steam output or 7.1E-01 lb per MWh; or (6.6E-03 lb per MMBtu of steam output or 9.1E-02 lb per MWh) Collect a minimum of 2 dscm per run. 11. Dutch Ovens/Pile burners designed to burn biomass/bio-based solid a. CO (or CEMS) 770 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average; or (520 ppm by volume on a dry basis corrected to 3 percent oxygen,c 10-day rolling average) 8.4E-01 lb per MMBtu of steam output or 8.4 lb per MWh; 3-run average 1 hr minimum sampling time. b. Filterable PM (or TSM) 2.8E-01 lb per MMBtu of heat input; or (2.0E-03 lb per MMBtu of heat input) 3.9E-01 lb per MMBtu of steam output or 3.9 lb per MWh; or (2.8E-03 lb per MMBtu of steam output or 2.8E-02 lb per MWh) Collect a minimum of 1 dscm per run. 12. Fuel cell units designed to burn biomass/bio-based solid a. CO 1,100 ppm by volume on a dry basis corrected to 3 percent oxygen 2.4 lb per MMBtu of steam output or 12 lb per MWh 1 hr minimum sampling time. b. Filterable PM (or TSM) 2.0E-02 lb per MMBtu of heat input; or (5.8E-03 lb per MMBtu of heat input) 5.5E-02 lb per MMBtu of steam output or 2.8E-01 lb per MWh; or (1.6E-02 lb per MMBtu of steam output or 8.1E-02 lb per MWh) Collect a minimum of 2 dscm per run. 13. Hybrid suspension grate units designed to burn biomass/bio-based solid a. CO (or CEMS) 3,500 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average; or (900 ppm by volume on a dry basis corrected to 3 percent oxygen,c 30-day rolling average) 3.5 lb per MMBtu of steam output or 39 lb per MWh; 3-run average 1 hr minimum sampling time. b. Filterable PM (or TSM) 4.4E-01 lb per MMBtu of heat input; or (4.5E-04 lb per MMBtu of heat input) 5.5E-01 lb per MMBtu of steam output or 6.2 lb per MWh; or (5.7E-04 lb per MMBtu of steam output or 6.3E-03 lb per MWh) Collect a minimum of 1 dscm per run. 14. Units designed to burn liquid fuel a. HCl 1.1E-03 lb per MMBtu of heat input 1.4E-03 lb per MMBtu of steam output or 1.6E-02 lb per MWh For M26A, collect a minimum of 2 dscm per run; for M26, collect a minimum of 240 liters per run. b. Mercury 2.0E-06a lb per MMBtu of heat input 2.5E-06a lb per MMBtu of steam output or 2.8E-05 lb per MWh For M29, collect a minimum of 3 dscm per run; for M30A or M30B collect a minimum sample as specified in the method, for ASTM D6784,b collect a minimum of 2 dscm. 15. Units designed to burn heavy liquid fuel a. CO 130 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average 0.13 lb per MMBtu of steam output or 1.4 lb per MWh; 3-run average 1 hr minimum sampling time. b. Filterable PM (or TSM) 6.2E-02 lb per MMBtu of heat input; or (2.0E-04 lb per MMBtu of heat input) 7.5E-02 lb per MMBtu of steam output or 8.6E-01 lb per MWh; or (2.5E-04 lb per MMBtu of steam output or 2.8E-03 lb per MWh) Collect a minimum of 1 dscm per run. 16. Units designed to burn light liquid fuel a. CO 130 ppm by volume on a dry basis corrected to 3 percent oxygen 0.13 lb per MMBtu of steam output or 1.4 lb per MWh 1 hr minimum sampling time. b. Filterable PM (or TSM) 7.9E-03a lb per MMBtu of heat input; or (6.2E-05 lb per MMBtu of heat input) 9.6E-03a lb per MMBtu of steam output or 1.1E-01a lb per MWh; or (7.5E-05 lb per MMBtu of steam output or 8.6E-04 lb per MWh) Collect a minimum of 3 dscm per run. 17. Units designed to burn liquid fuel that are non-continental units a. CO 130 ppm by volume on a dry basis corrected to 3 percent oxygen, 3-run average based on stack test 0.13 lb per MMBtu of steam output or 1.4 lb per MWh; 3-run average 1 hr minimum sampling time. b. Filterable PM (or TSM) 2.7E-01 lb per MMBtu of heat input; or (8.6E-04 lb per MMBtu of heat input) 3.3E-01 lb per MMBtu of steam output or 3.8 lb per MWh; or (1.1E-03 lb per MMBtu of steam output or 1.2E-02 lb per MWh) Collect a minimum of 2 dscm per run. 18. Units designed to burn gas 2 (other) gases a. CO 130 ppm by volume on a dry basis corrected to 3 percent oxygen 0.16 lb per MMBtu of steam output or 1.0 lb per MWh 1 hr minimum sampling time. b. HCl 1.7E-03 lb per MMBtu of heat input 2.9E-03 lb per MMBtu of steam output or 1.8E-02 lb per MWh For M26A, collect a minimum of 2 dscm per run; for M26, collect a minimum of 240 liters per run. c. Mercury 7.9E-06 lb per MMBtu of heat input 1.4E-05 lb per MMBtu of steam output or 8.3E-05 lb per MWh For M29, collect a minimum of 3 dscm per run; for M30A or M30B, collect a minimum sample as specified in the method; for ASTM D6784b collect a minimum of 2 dscm. d. Filterable PM (or TSM) 6.7E-03 lb per MMBtu of heat input or (2.1E-04 lb per MMBtu of heat input) 1.2E-02 lb per MMBtu of steam output or 7.0E-02 lb per MWh; or (3.5E-04 lb per MMBtu of steam output or 2.2E-03 lb per MWh) Collect a minimum of 3 dscm per run. [78 FR 7195, Jan. 31, 2013, as amended at 80 FR 72821, Nov. 20, 2015]