Appendix H to Subpart G of Part 82 - Substitutes Subject to Use Restrictions and Unacceptable Substitutes, Effective May 28, 1999  


Latest version.
  • Appendix H to Subpart G of Part 82 - Substitutes Subject to Use Restrictions and Unacceptable Substitutes, Effective May 28, 1999

    CFC-12 Automobile and Non-automobile Motor Vehicle Air Conditioners, Retrofit and New

    Criteria for Uniqueness of Fittings

    (a) All fittings for alternative motor vehicle refrigerants must meet the following requirements:

    (1) High-side screw-on fittings for each refrigerant must differ from high-side screw-on fittings for all other refrigerants, including CFC-12, and from low-side screw-on fittings for CFC-12;

    (2) Low-side screw-on fittings for each refrigerant must differ from low-side screw-on fittings for all other refrigerants, including CFC-12;

    (3) High-side screw-on fittings for a given refrigerant must differ from low-side screw-on fittings for that refrigerant, to protect against connecting a low-pressure system to a high-pressure one;

    (4) High-side quick-connect fittings for each refrigerant must differ from high-side quick-connect fittings for all other refrigerants, including CFC-12 (if they exist);

    (5) Low-side quick-connect fittings for each refrigerant must differ from low-side quick-connect fittings for all other refrigerants, including CFC-12 (if they exist);

    (6) High-side quick-connect fittings for a given refrigerant must differ from low-side quick-connect fittings for that refrigerant, to protect against connecting a low-pressure system to a high-pressure one;

    (7) For each type of container, the fitting for each refrigerant must differ from the fitting for that type of container for all other refrigerants, including CFC-12.

    (b) For screw-on fittings, “differ” means that either the diameter must differ by at least 116 inch or the thread direction must be reversed (i.e. right-handed vs. left-handed). Simply changing the thread pitch is not sufficient. For quick-connect fittings, “differ” means that a person using normal force and normal tools (including wrenches) must not be able to cross-connect fittings.

    (c) The sole exception to the 116 inch difference requirement is the difference between the small can fittings for GHG-X4 and R-406A. The GHG-X4 small can fitting uses a metric measurement, and is slightly less than 116 inch larger than the small can fitting for R-406A. EPA has concluded that these fittings will not cross-connect, and therefore they may be used.

    Refrigeration and Air Conditioning - Unacceptable Substitutes

    End-use Substitute Decision Comments
    All HCFC-22 end-uses, retrofit and new NARM-22 Unacceptable This blend contains HCFC-22, and it is inappropriate to use such a blend as a substitute for HCFC-22. In addition, this blend contains HFC-23, which has an extremely high GWP and lifetime. Other substitutes for HCFC-22 exist that do not contain either HCFC-22 or HFC-23.

    Solvents Cleaning - Unacceptable Substitutes

    End-use Substitute Decision Comments
    Metals, Electronic, and Precision cleaning with CFC-113, methyl chloroform, and HCFC-141b Chlorobromo-methane Unacceptable Other alternatives exist with zero or much lower ODP.

    Fire Suppression and Explosion Protection - Acceptable Subject to Narrowed Use Limits: Total Flooding Agents

    End-use Substitute Decision Conditions Further information
    Total flooding HFC-236fa Acceptable subject to narrowed use limits. Acceptable when manufactured using any process that does not convert perfluoroisobutylene (PFIB) directly to HFC-236fa in a single step:
    for use in explosion suppression and explosion inertion applications, and
    for use in fire suppression applications where other non-PFC agents or alternatives are not technically feasible due to performance or safety requirements:
    (a) because of their physical or chemical properties, or
    (b) where human exposure to the extinguishing agents may result in failure to meet safety guidelines in the latest edition of the NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems.
    Use of this agent should be in accordance with the safety guidelines in the latest edition of the NFPA 2001 Standard for Clean Agent Fire Systems.
    Users should observe the limitations on HFC-236fa acceptability by taking the following measures:
    (i) conduct an evaluation of foreseeable conditions of end-use;
    (ii) determine that the physical or chemical properties, or other technical constraints of the other available agents preclude their use; and
    (iii) determine that human exposure to the other alternative extinguishing agents may result in failure to meet safety guidelines in the latest edition of the NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems.
    Documentation of such measures should be available for review upon request.
    The principal environmental characteristic of concern for HFC-236fa is its high GWP of 9400 and long atmospheric lifetime of 226 years. Actual contributions to global warming depend upon the quantities emitted.
    See additional comments 1, 2, 3, 4, 5.
    Total flooding C3F8 Acceptable subject to narrowed use limits. Acceptable for nonresidential uses where other alternatives are not technically feasible due to performance or safety requirements:
    (a) because of their physical or chemical properties, or
    (b) where human exposure to the extinguishing agents may result in failure to meet safety guidelines in the latest edition of the NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems.
    Use of this agent should be in accordance with the safety guidelines in the latest edition of the NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems.
    Users should observe the limitations on PFC acceptability by taking the following measures:
    (i) conduct an evaluation of foreseeable conditions of end-use;
    (ii) determine that the physical or chemical properties or other technical constraints of the other available agents preclude their use; and
    (iii) determine that human exposure to the other alternative extinguishing agents may result in failure to meet safety guidelines in the latest edition of the NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems.
    Documentation of such measures should be available for review upon request.
    The principal environmental characteristic of concern for PFCs is that they have high GWPs and long atmospheric lifetimes. Actual contributions to global warming depend upon the quantities of PFCs emitted.
    See additional comments 1, 2, 3, 4, 5.
    Total flooding C4F10 Acceptable subject to narrowed use limits Acceptable for nonresidential uses where other alternatives are not technically feasible due to performance or safety requirements:
    (a) because of their physical or chemical properties, or
    (b) where human exposure to the extinguishing agents may result in failure to meet safety guidelinesin the latest edition of the NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems
    Use of this agent should be in accordance with the safety guidelines in the latest edition of the NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems.
    Users should observe the limitations on PFC acceptability by taking the following measures:
    (i) conduct an evaluation of foreseeable conditions of end-use;
    (ii) determine that the physical or chemical properties or other technical constraints of the other available agents preclude their use; and
    (iii) determine that human exposure to the other alternative extinguishing agents may result in failure to meet safety guidelines in the latest edition of the NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems
    Documentation of such measures should be available for review upon request.
    The principal environmental characteristic of concern for PFCs is that they have high GWPs and long atmospheric lifetimes. Actual contributions to global warming depend upon the quantities of PFCs emitted.
    See additional comments 1, 2, 3, 4, 5.

    Fire Suppression and Explosion Protection - Streaming Agents - Acceptable Subject to Narrowed Use Limits

    End-use Substitute Decision Conditions Comments
    Halon 1211
    replacement
    C6F14 Acceptable for nonresidential uses where other alternatives are not technically feasible due to performance or safety requirements: (a) because of their physical or chemical properties, or (b) where human exposure to the extinguishing agents may result in failure to meet applicable use conditions. Users should observe the limitations on PFC acceptability by taking the following measures: (i) conduct an evaluation of foreseeable conditions of end-use; (ii) determine that the physical or chemical properties or other technical constraints of the other available agents preclude their use; and (iii) determine that human exposure to the other alternative extinguishing agents may result in failure to meet applicable use conditions Documentation of such measures should be available for review upon request. The principal environmental characteristic of concern for PFCs is that they have high GWPs and long atmospheric lifetimes. Actual contributions to global warming depend upon the quantities of PFCs emitted. For additional guidance regarding applications in which PFCs may be appropriate, users should consult the description of potential uses which is included in the March 18, 1994 Final Rule (59 FR 13044.) See comments 1, 2.
    Halon 1211 replacement HFC-236fa Acceptable in nonresidential uses when manufactured using any process that does not convert perfluoroisobutylene (PFIB) directly to HFC-236fa in a single step See comments 1, 2, 3.
    Halon 1211 replacement HFC-227ea Acceptable in nonresidential uses only See comments 1, 2.
    Additional comments:

    Fire Suppression and Explosion Protection - Total Flooding Agents - Unacceptable Substitutes

    End-use Substitute Decision Comments
    Halon 1301 replacement Chlorobromo-methane Unacceptable Other alternatives exist with zero or lower ODP; OSHA regulations prohibit its use as extinguishing agent in fixed extinguishing systems where employees may be exposed. See 29 CFR 1910.160(b)(11).

    Aerosols - Unacceptable Substitutes

    End-use Substitute Decision Comments
    Solvent in aerosols with CFC-113, MCF, or HCFC-141b Chlorobromo-methane Unacceptable Other alternatives exist with zero or much lower ODP.

    Adhesives, Coatings, and Inks - Unacceptable Substitutes

    End-use Substitute Decision Comments
    Solvent in adhesives, coatings, and inks with CFC-113 Chlorobromo-methane Unacceptable Other alternatives exist with zero or much lower ODP.
    Solvent in adhesives, coatings, and inks with MCF Chlorobromo-methane Unacceptable Other alternatives exist with zero or much lower ODP.
    Solvent in adhesives, coatings and inks with HCFC-141b Chlorobromo-methane Unacceptable Other alternatives exist with zero or much lower ODP.

    [64 FR 22996, Apr. 28, 1999, as amended at 67 FR 4201, Jan. 29, 2002]