§ 62.14442 - What must my inspection include?  


Latest version.
  • § 62.14442 What must my inspection include?

    (a) At a minimum, you must do the following during your HMIWI equipment inspection:

    (1) Inspect all burners, pilot assemblies, and pilot sensing devices for proper operation, and clean pilot flame sensor as necessary;

    (2) Check for proper adjustment of primary and secondary chamber combustion air, and adjust as necessary;

    (3) Inspect hinges and door latches, and lubricate as necessary;

    (4) Inspect dampers, fans, and blowers for proper operation;

    (5) Inspect HMIWI door and door gaskets for proper sealing;

    (6) Inspect motors for proper operation;

    (7) Inspect primary chamber refractory lining, and clean and repair/replace lining as necessary;

    (8) Inspect incinerator shell for corrosion and/or hot spots;

    (9) Inspect secondary/tertiary chamber and stack, and clean as necessary;

    (10) Inspect mechanical loader, including limit switches, for proper operation, if applicable;

    (11) Visually inspect waste bed (grates), and repair/ seal, as necessary;

    (12) For the burn cycle that follows the inspection, document that the incinerator is operating properly and make any necessary adjustments;

    (13) Inspect air pollution control device(s) for proper operation, if applicable;

    (14) Inspect waste heat boiler systems to ensure proper operation, if applicable;

    (15) Inspect bypass stack components;

    (16) Ensure proper calibration of thermocouples, sorbent feed systems and any other monitoring equipment; and

    (17) Include inspection elements according to manufacturer's recommendations; and

    (18) Generally observe that the equipment is maintained in good operating condition.

    (b) At a minimum, you must do the following during your air pollution control device inspection:

    (1) Inspect air pollution control device(s) for proper operation, if applicable;

    (2) Ensure proper calibration of thermocouples, sorbent feed systems and any other monitoring equipment; and

    (3) Include inspection elements according to manufacturer's recommendations; and

    (4) Generally observe that the equipment is maintained in good operating condition.

    [65 FR 49881, Aug. 15, 2000, as amended at 78 FR 28068, May 13, 2013]