§ 108.411 - Smoke detection system.  


Latest version.
  • § 108.411 Smoke detection system.

    Each smoke accumulator in a smoke detection system must be located on the overhead of the compartment protected by the system in a location -

    (a) Where no portion of the overhead of the compartment is more than 12 meters (40 feet) from an accumulator;

    (b) That is no closer to the opening of a ventilator than 3 times the diameter or equivalent size of the opening.

    (c) Where damage to the accumulator is unlikely to occur if it is not protected.