Code of Federal Regulations (Last Updated: July 5, 2024) |
![]() |
Title 46 - Shipping |
![]() |
Chapter I - Coast Guard, Department of Homeland Security |
![]() |
SubChapter I-A - Mobile Offshore Drilling Units |
![]() |
Part 108 - Design and Equipment |
![]() |
Subpart D - Fire Extinguishing Systems |
![]() |
Fixed Carbon Dioxide Fire Extinguishing Systems |
§ 108.455 - Enclosure openings.
Latest version.
-
§ 108.455 Enclosure openings.
(a) Mechanical ventilation for spaces protected by a CO2 system must be designed to shut down automatically when the system is activated.
(b) Each space that is protected by a CO2 system and that has natural ventilation must have a means for closing that ventilation.
(c) Each space protected by a CO2 system must have the following means for closing the openings to the space from outside the space:
(1) Doors, shutters, or dampers for closing each opening in the lower portion of the space.
(2) Doors, shutters, dampers or temporary means such as canvas or other material normally on board a unit may be used for closing each opening in the upper portion of the space.