Code of Federal Regulations (Last Updated: May 6, 2024) |
Title 46 - Shipping |
Chapter I - Coast Guard, Department of Homeland Security |
SubChapter I-A - Mobile Offshore Drilling Units |
Part 108 - Design and Equipment |
Subpart D - Fire Extinguishing Systems |
Hand Portable and Semiportable Fire Extinguishing Systems |
§ 108.493 - Location.
-
§ 108.493 Location.
(a) Each unit must have the hand portable and semiportable fire extinguishers prescribed in Table 108.495(a) of this subpart and installed in the locations prescribed in the table.
(b) Each portable and semi-portable fire extinguisher must be visible and readily accessible.
(c) The location, size, and number of each portable and semiportable fire extinguisher on a unit must be acceptable to the appropriate OCMI. The OCMI may require extinguishers in addition to those prescribed in Table 108.495(a) if he considers them necessary for fire protection on the unit.
(d) Each hand portable and semiportable fire extinguisher that has a nameplate which states that it is to be protected from freezing, must be located where freezing temperatures do not occur.