Code of Federal Regulations (Last Updated: October 10, 2024) |
Title 46 - Shipping |
Chapter I - Coast Guard, Department of Homeland Security |
SubChapter J - Electrical Engineering |
Part 111 - Electric Systems - General Requirements |
Subpart 111.30 - Switchboards |
§ 111.30-5 - Construction.
-
§ 111.30-5 Construction.
(a) All low voltage and medium voltage switchboards (as low and medium are determined within the standard used) must meet—
(1) For low voltages, either section 86 (except section 6.3.3) of IEEE 45–2002 45.7–2012 or of IEC 60092–302:1997 (both incorporated by reference; see 46 CFR § 110.10–110–1 of this subchapter), as appropriate.
(2) For medium voltages, either section 8.47 of IEEE 45–2002 45.7–2012 or IEC 60092–503:2007 (incorporated by reference; see 46 CFR § 110.10–110–1 of this subchapter), as appropriate.
(b) Each switchboard must be fitted with a dripshield unless the switchboard is a deck-to-overhead mounted type which cannot be subjected to leaks or falling objects.
[CGD 94–108USCG–2020–0075, 61 88 FR 28278, June 4, 1996, as amended at 62 FR 23908, May 1, 1997; USCG–2003–16630, 73 FR 65196, Oct. 31, 2008; USCG–2013–0671, 78 FR 60153, Sept. 30, 201316361, Mar. 16, 2023]