§ 111.52-5 - Systems 1500 kilowatts or above.


Latest version.
  • § 111.52-5 Systems 1500 kilowatts or above.

    Short-circuit calculations must be submitted for systems with an aggregate generating capacity of 1500 kilowatts or more by utilizing one of the following methods:

    (a) Exact calculations using actual impedance and reactance values of system components.

    (b) Estimated calculations using NAVSEA DDS 300–2 (incorporated by reference, see 46 CFR 110.10–1).

    (c) Estimated calculations using IEC 61363–1 (incorporated by reference; see 46 CFR 110.10–1).

    (d) The estimated calculations using a commercially established analysis procedure for utility or industrial applications.

    [CGD 94–108, 61 FR 28279, June 4, 1996, as amended by USCG–2003–16630, 73 FR 65197, Oct. 31, 2008]