§ 154.1170 - Hand hose line: General.


Latest version.
  • § 154.1170 Hand hose line: General.

    Each dry chemical hand hose line must:

    (a) Not be longer than 33m (108 ft.);

    (b) Be stored on a hose reel or in a hose cabinet and be one that is operable whether or not it is unwound from a hose reel or removed from a hose cabinet;

    (c) Be non-kinkable;

    (d) Have a nozzle with a valve to start and stop the flow of chemical;

    (e) Have a capacity of at least 3.5 kg/sec (7.7 lb./sec); and

    (f) Be one that can be operated by one person.