§ 154.805 - Vent masts.  


Latest version.
  • § 154.805 Vent masts.

    Relief valves or common vent headers from relief valves must discharge to a vent mast that:

    (a) Discharges vertically upward;

    (b) Has a rain cap or other means of preventing the entrance of rain or snow;

    (c) Has a screen with 25mm (1 inch) wire mesh or bars not more than 25mm (1 in.) apart on the discharge port;

    (d) Extends at least to a height of B/3 or 6m (19.7 ft.), whichever is greater, above the weather deck and 6m (19.7 ft.) above the working level;

    (e) For a cargo tank, does not exhaust cargo vapors within a radius of B or 25m (82 ft.), whichever is less, from any forced or natural ventilation intake or other opening to an accommodation, service, control station, or other gas-safe space, except that for vessels less than 90m (295 ft.) in length, shorter distances may be specially approved by the Commandant (CG-OES);

    (f) For a containment system, except a cargo tank, does not exhaust vapor within a radius of 10m (32.8 ft.) or less from any forced or natural ventilation intake or other opening to an accommodation, service, control station, or other gas-safe space;

    (g) Has drains to remove any liquid that may accumulate; and

    (h) Prevents accumulations of liquid at the relief valves.

    [CGD 74-289, 44 FR 26009, May 3, 1979, as amended by CGD 82-063b, 48 FR 4782, Feb. 3, 1983]