§ 181.420 - Pre-engineered fixed gas fire extinguishing systems.  


Latest version.
  • § 181.420 Pre-engineered fixed gas fire extinguishing systems.

    (a) A pre-engineered fixed gas fire extinguishing system must:

    (1) Be approved by the Commandant;

    (2) Be capable of manual actuation from outside the space in addition to automatic actuation by a heat detector;

    (3) Automatically shut down all power ventilation systems and all engines that draw intake air from within the protected space; and

    (4) Be installed in accordance with the manufacturer's instructions.

    (b) A vessel on which a pre-engineered fixed gas fire extinguishing system is installed must have the following equipment at the operating station:

    (1) A light to indicate discharge;

    (2) An audible alarm that sounds upon discharge; and

    (3) A means to reset devices used to automatically shut down ventilation systems and engines as required by paragraph (a)(3) of this section.

    (c) Only one pre-engineered fixed gas fire extinguishing system is allowed to be installed in each space protected by such a system.