§ 39.20-7 - Tankship liquid overfill protection—T/ALL.  


Latest version.
  • (a) Each cargo tank of a tankship must be equipped with an intrinsically safe high level alarm and a tank overfill alarm.

    (b) The high level alarm and tank overfill alarm required by paragraph (a) of this section, if installed after July 23, 1990 must:

    (1) Be independent of each other;

    (2) Alarm in the event of loss of power to the alarm system or failure of electrical circuitry to the tank level sensor; and

    (3) Be able to be checked at the tank for proper operation prior to each transfer or contain an electronic self-testing feature which monitors the condition of the alarm circuitry and sensor.

    (c) The high level alarm required by paragraph (a) of this section must:

    (1) Alarm before the tank overfill alarm, but no lower than 95 percent of tank capacity;

    (2) Be identified with the legend “High Level Alarm” in black letters at least 50 millimeters (2 inches) high on a white background; and

    (3) Have audible and visible alarm indications that can be seen and heard on the vessel where cargo transfer is controlled.

    (d) The tank overfill alarm required by paragraph (a) of this section must:

    (1) Be independent of the cargo gauging system;

    (2) Have audible and visible alarm indications that can be seen and heard on the vessel where cargo transfer is controlled and in the cargo deck area;

    (3) Be identified with the legend “TANK OVERFILL ALARM” in black letters at least 50 millimeters (2 inches) high on a white background; and

    (4) Alarm early enough to allow the person in charge of transfer operations to stop the transfer operation before the cargo tank overflows.

    (e) If a spill valve is installed on a cargo tank fitted with a vapor collection system, it must meet the requirements of §39.20–9(c) of this part.

    (f) If a rupture disk is installed on a cargo tank fitted with a vapor collection system, it must meet the requirements of §39.20–9(d) of this part.