§ 76.25-15 - Pumps and water supply.  


Latest version.
  • Link to an amendment published at 81 FR 48255, July 22, 2016.

    (a) An automatically controlled pump shall be provided to supply the sprinkling system and shall be used for no other purpose. The size and capacity of the pump shall be governed by the zone having the greatest capacity need for any one deck, and shall be suitable to operate at least the number of heads noted in table 76.25-15(a) with a Pitot tube pressure of at least 15 p.s.i. at all heads (approximately 20 GPM per head). There shall also be sufficient pumping capacity available, either from the automatic pump, the fire pumps, or other source, so that in conjunction with the automatic pump the total number of heads noted in table 76.25-15(a) may be operated with the same efficiency as noted above, and at the same time to deliver water from the two highest fire hose outlets in a manner similar to that described in §76.10-5(c). Intermediate values may be obtained by interpolation.

    Table 76.25-15(a)

    Maximum number of heads on one deck in one zoneNumber of heads automatic pump to supplyNumber of heads additional pumps to supply
    55
    1010
    201010
    301216
    401518
    501525
    602025
    802030
    1002040
    1202050
    1502060
    2002075
    25020100

    (b) [Reserved]