§ 192.375 - Service lines: Plastic.  


Latest version.
  • § 192.375 Service lines: Plastic.

    (a) Each plastic service line outside a building must be installed below ground level, except that -

    (1) It may be installed in accordance with § 192.321(g); and

    (2) It may terminate above ground level and outside the building, if -

    (i) The above ground level part of the plastic service line is protected against deterioration and external damage; and

    (ii) The plastic service line is not used to support external loads; and

    (iii) The riser portion of the service line meets the design requirements of § 192.204.

    (b) Each plastic service line inside a building must be protected against external damage.

    [35 FR 13257, Aug. 19, 1970, as amended by Amdt. 192-78, 61 FR 28785, June 6, 1996; Amdt. 192-124, 83 FR 58719, Nov. 20, 2018]