§ 193.2127 - Piping.  


Latest version.
  • (a) Piping must be designed, manufactured, and tested to comply with ASME/ANSI B 31.3.

    (b) All cryogenic and hazardous fluid piping must have connections to facilitate blowdown and purge as required by this part.

    (c) Each cryogenic or hazardous fluid piping system that is aboveground must be identified by color coding, painting, or labeling.

    (d) Seamless pipe or pipe with a longitudinal joint efficiency of 1.0 determined in accordance with ASME/ANSI B31.3, or pipe with a design pressure less than two-thirds of the mill-proof test pressure or subsequent shop or field hydrostatic test pressure must be used for process and transfer piping handling cryogenic or other hazardous fluids with a service temperature below −22° F (−30° C).

    (e) For longitudinal or spiral weld piping handling LNG or cryogenic fluids, the heat affected zone must comply with section 323.2.2 of ASME/ANSI B31.3.

    (f) Threaded piping used in hazardous fluid service must be at least Schedule 80.