§ 193.2149 - Impoundment required.  


Latest version.
  • (a) An impounding system must be provided for storage tanks to contain a potential spill of LNG or other hazardous liquid.

    (b) Grading or drainage or an impounding system must be provided to ensure that accidental spills or leaks from the following components and areas do not endanger components or adjoining property or enter navigable waterways:

    (1) Liquefaction and other process equipment;

    (2) Vaporizers;

    (3) Transfer systems;

    (4) Parking areas for tank cars or tank trucks; and

    (5) Areas for loading, unloading, or storing portable containers and dewar vessels.

    (c) Impounding systems for LNG must be designed and constructed in accordance with this subpart. Impounding systems intended for containment of hazardous liquids other than LNG must meet the requirements of ANSI/NFPA-30.