  • (a) Each operator shall establish the external design pressure at the top of each LNG storage tank, including a suitable margin below the minimum allowable working pressure.

    (b) The external design pressure may not be higher than the lowest vapor pressure in the vapor space resulting from each of the following events or combinations thereof that predictably might occur, giving consideration to gas makeup systems, vacuum relief devices in accordance with § 193.2429, and any other mitigating measures.

    (1) Withdrawing liquid from the tank;

    (2) Withdrawing gas from the tank;

    (3) Adding subcooled LNG to the tank; and

    (4) Rise in barometric pressure, based on the worst combination of amount of rise and rate of rise which predictably might occur.