§ 193.2411 - Relief devices.  


Latest version.
  • The capacity of pressure relief devices required for vaporizers by § 193.2429 is governed by the following:

    (a) For heated vaporizers, the capacity must be at least 110 percent of rated natural gas flow capacity without allowing the pressure to rise more than 10 percent above the vaporizer's maximum allowable working pressure.

    (b) For ambient vaporizers, the capacity must be at least 150 percent of rated natural gas flow capacity without allowing the pressure to rise more than 10 percent above the vaporizer's maximum allowable working pressure.