§ 193.2433 - Sensing devices.  


Latest version.
  • (a) Each operator shall determine the appropriate location for and install sensing devices as necessary to—

    (1) Monitor the operation of components to detect a malfunction which could cause a hazardous condition if permitted to continue; and

    (2) Detect the presence of fire or combustible gas in areas determined in accordance with section 500-5 of ANSI/NFPA 70 to have a potential for presence of flammable fluids.

    (b) Buildings in which potentially hazardous quantities of flammable fluids are used or handled must be continuously monitored by gas sensing devices set to activate audible and visual alarms in the building and at the control center when the concentration of the fluid in air is not more than 25 percent of the lower flammable limit.