97-11316. RUS Standard for Acceptance Tests and Measurements of Telecommunications Plant  

  • [Federal Register Volume 62, Number 85 (Friday, May 2, 1997)]
    [Rules and Regulations]
    [Pages 23958-24008]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 97-11316]
    
    
    -----------------------------------------------------------------------
    
    DEPARTMENT OF AGRICULTURE
    
    Rural Utilities Service
    
    7 CFR Part 1755
    
    
    RUS Standard for Acceptance Tests and Measurements of 
    Telecommunications Plant
    
    AGENCY: Rural Utilities Service, USDA.
    
    ACTION: Final rule.
    
    -----------------------------------------------------------------------
    
    SUMMARY: The Rural Utilities Service (RUS) amends its regulations on 
    Telecommunications Standards and Specifications for Materials, 
    Equipment and Construction, by rescinding RUS Bulletin 345-63, RUS 
    Standard for Acceptance Tests and Measurements of Telephone Plant, PC-
    4, and codifying the revised RUS standard at 7 CFR 1755.400 through 7 
    CFR 1755.407, in the Code of Federal Regulations. The revised standard: 
    Updates the acceptance tests and measurements for copper conductor 
    telecommunications plant; includes a section on acceptance tests and 
    measurements for fiber optic cable plant; includes a section on 
    acceptance tests and measurements for voiceband data transmission; and 
    includes a shield or armor ground resistance test to determine outer 
    jacket cable damage.
    
    DATES: Effective date: June 2, 1997.
        Incorporation by reference: Incorporation by reference of certain 
    publications listed in this final rule is approved by the Director of 
    the Federal Register as of June 2, 1997.
    
    FOR FURTHER INFORMATION CONTACT: Charlie I. Harper, Jr., Chief, Outside 
    Plant Branch, Telecommunications Standards Division, Rural Utilities 
    Service, room 2837, STOP 1598, South Building, U.S. Department of 
    Agriculture, Washington, DC 20250-1598, telephone number (202) 720-
    0667.
    
    SUPPLEMENTARY INFORMATION:
    
    Executive Order 12866
    
        This final rule has been determined to be not significant and 
    therefore has not been reviewed by the Office of Management and Budget.
    
    Executive Order 12988
    
        This final rule has been reviewed under Executive Order 12988, 
    Civil Justice Reform. RUS has determined that this final rule meets the 
    applicable standards provided in section 3 of that Executive Order.
    
    Regulatory Flexibility Act Certification
    
        The Administrator of RUS has determined that this final rule will 
    not have a significant economic impact on a substantial number of small 
    entities, as defined by the Regulatory Flexibility Act (5 U.S.C. 601 et 
    seq.). This final rule involves standards and specifications, which may 
    increase the direct short-term costs to RUS borrowers. However, the 
    long-term direct economic costs are reduced through greater durability 
    and lower maintenance cost over time.
    
    Information Collection and Recordkeeping Requirements
    
        The reporting and recordkeeping requirements contained in the final 
    rule were approved by the Office of Management and Budget (OMB) 
    pursuant to the Paperwork Reduction Act of 1995 (44 U.S.C. Chapter 35, 
    as amended) under control number 0572-0059.
        Send questions or comments regarding this burden or any aspect of 
    these collections of information, including suggestions for reducing 
    the burden, to F. Lamont Heppe, Jr., Director, Program Support and 
    Regulatory Analysis, Rural Utilities Service, U.S. Department of 
    Agriculture,
    
    [[Page 23959]]
    
    Stop 1522, Washington, DC 20250-1522, Fax: (202) 720-4120.
    
    National Environmental Policy Act Certification
    
        The Administrator of RUS has determined that this final rule will 
    not significantly affect the quality of the human environment as 
    defined by the National Environmental Policy Act of 1969 (42 U.S.C. 
    4321 et seq.) Therefore, this action does not require an environmental 
    impact statement or assessment.
    
    Catalog of Federal Domestic Assistance
    
        The program described by this final rule is listed in the Catalog 
    of Federal Domestic Assistance programs under No. 10.851, Rural 
    Telephone Loans and Loan Guarantees; and No. 10.852, Rural Telephone 
    Bank Loans. This catalog is available on a subscription basis from the 
    Superintendent of Documents, the United States Government Printing 
    Office, Washington, DC 20402.
    
    Executive Order 12372
    
        This final rule is excluded from the scope of Executive Order 
    12372, Intergovernmental Consultation, which may require consultation 
    with State and local officials. A Notice of Final rule titled 
    Department Programs and Activities Excluded from Executive Order 12372 
    (50 FR 47034) exempts RUS and RTB loans and loan guarantees, and RTB 
    bank loans, to governmental and nongovernmental entities from coverage 
    under this Order.
    
    Background
    
        RUS issues publications titled ``Bulletin'' which serve to guide 
    borrowers regarding already codified policy, procedures, and 
    requirements needed to manage loans, loan guarantee programs, and the 
    security instruments which provide for and secure RUS financing. RUS 
    issues standards and specifications for the construction of telephone 
    facilities financed with RUS Loan Funds. RUS is rescinding Bulletin 
    345-63, ``RUS Standard for Acceptance Tests and Measurements of 
    Telephone Plant, PC-4,'' and to codifying this standard in 7 CFR 
    1755.400 through 7 CFR 1755.407, RUS Standard for Acceptance Tests and 
    Measurements of Telecommunications Plant.
        This standard is used to determine the acceptability of installed 
    telecommunications plant. The current standard with regard to copper 
    cable plant acceptance tests and measurements has become outdated as a 
    result of technological advancements made in copper cable plant 
    acceptance test methods during the past fourteen years. Therefore to 
    assure RUS borrowers that their installed copper cable plant is of the 
    highest quality, the revised standard will update acceptance test and 
    measurement methods for copper cable plant.
        There is currently a need to include into the standard a section 
    dealing with standardized test methods and measurements for installed 
    fiber optic cable plant. Presently acceptance test methods and 
    measurements for fiber optic cable plant are developed by each 
    consulting engineer resulting in a variety of test methods and 
    measurements which in turn results in higher construction costs to RUS 
    borrowers. By providing standardized acceptance test methods and 
    measurements for fiber optic cable plant, RUS will be assisting its 
    borrowers by decreasing their construction costs for fiber optic cable 
    installation.
        There is currently a need to include into the standard a section 
    dealing with standardized test methods and measurements for voiceband 
    data transmission. Because RUS borrowers are increasing their usage of 
    modems to transmit data over telecommunications transmission 
    facilities, standardized test methods and measurements are needed to 
    ensure that the transmission facilities are acceptable for data 
    transmission.
        There is presently a need to include into the current standard a 
    standardized shield or armor ground resistance test method and a 
    minimum requirement to determine when the outer cable jacket is damaged 
    as a result of the installation procedures. This standard test method 
    and minimum requirement will result in cost savings to RUS borrowers 
    because the variety of test methods and minimum requirements presently 
    being used by consulting engineers and contractors will be eliminated.
        This action establishes RUS standardized acceptance test methods 
    and measurements to determine acceptability of installed 
    telecommunications plant. These standardized acceptance test methods 
    and measurements will afford RUS telephone borrowers an economical and 
    efficient means of reducing their construction costs.
        On August 28, 1996, RUS published a proposed rule (61 FR 44195) to 
    rescind RUS Bulletin 345-63, RUS Standard for Acceptance Tests and 
    Measurements of Telephone Plant, PC-4, and to codify the revised RUS 
    Standard for Acceptance Tests and Measurements of Telecommunications 
    Plant in 7 CFR 1755.400 through 7 CFR 1755.407. Comments on this 
    proposed rule were due October 28, 1996. No comments were received by 
    this due date.
    
    List of Subjects in 7 CFR Part 1755
    
        Incorporation by reference, Loan programs--communications, 
    Reporting and recordkeeping requirements, Rural areas, Telephone.
    
        For the reasons set out in the preamble, RUS amends chapter XVII of 
    title 7 of the Code of Federal Regulations as follows:
    
    Part 1755--Telecommunications Standards and Specifications for 
    Materials, Equipment and Construction
    
        1. The authority citation for part 1755 continues to read as 
    follows:
    
        Authority: 7 U.S.C. 901 et seq., 1921 et seq., 6941 et seq.
    
    
    Sec. 1755.97  [Amended]
    
        2. Section 1755.97 is amended by removing the entry RUS Bulletin 
    345-63 from the table.
        3. Section 1755.98 is amended by adding the entry 1755.400 through 
    1755.407 to the table in numerical order to read as follows:
    
    
    Sec. 1755.98  List of telephone standards and specifications included 
    in other 7 CFR parts.
    
    * * * * *
    
    ------------------------------------------------------------------------
               Section                 Issue date               Title       
    ------------------------------------------------------------------------
                                                                            
    *                  *                  *                  *              
                      *                  *                  *               
    1755.400 through 1755.407...  [Effective date of    RUS Standard for    
                                   final rule].          Acceptance Tests   
                                                         and Measurements of
                                                         Telecommunications 
                                                         Plant.             
                                                                            
    *                  *                  *                  *              
                      *                  *                  *               
    ------------------------------------------------------------------------
    
    
    [[Page 23960]]
    
        4. Sections 1755.400 through 1755.407 are added to read as follows:
    
    
    Sec. 1755.400  RUS standard for acceptance tests and measurements of 
    telecommunications plant.
    
        Sections 1755.400 through 1755.407 cover the requirements for 
    acceptance tests and measurements on installed copper and fiber optic 
    telecommunications plant and equipment.
    
    
    Sec. 1755.401  Scope.
    
        (a) Acceptance tests outlined in Secs. 1755.400 through 1755.407 
    are applicable to plant constructed by contract or force account. This 
    testing standard provides for the following:
        (1) Specific types of tests or measurements for the different types 
    of telecommunications plant and equipment;
        (2) The method of measurement and types of measuring equipment;
        (3) The expected results and tolerances permitted to meet the 
    acceptable standards and objectives;
        (4) Suggested formats for recording the results of the measurements 
    and tests; and
        (5) Some probable causes of nonconformance and methods for 
    corrective action, where possible.
        (b) Alternative methods of measurements that provide suitable 
    alternative results shall be permitted with the concurrence of the 
    Rural Utilities Service (RUS).
        (c) For the purpose of this testing standard, a ``measurement'' 
    shall be defined as an evaluation where quantitative data is obtained 
    (e.g., resistance in ohms, structural return loss in decibels (dB), 
    etc.) and a ``test'' shall be defined as an evaluation where no 
    quantitative data is obtained (e.g., a check mark indicating 
    conformance is usually the result of the test).
        (d) The sequence of tests and measurements described in this 
    standard have been prepared as a guide. Variations from the sequence 
    may be necessary on an individual application basis.
        (e) There is some overlap in the methods of testing shown; also, 
    the extent of each phase of testing may vary on an individual basis. 
    The borrower shall determine the overall plan of testing, the need and 
    extent of testing, and the responsibility for each phase of testing.
    
    
    Sec. 1755.402  Ground resistance measurements.
    
        (a) The resistance of the central office (CO) and the remote 
    switching terminal (RST) ground shall be measured before and after it 
    has been bonded to the master ground bar (MGB) where it is connected to 
    the building electric service ground.
        (b) The ground resistance of electronic equipment such as span line 
    repeaters, carrier terminal equipment, concentrators, etc. shall be 
    measured.
        (c) Method of measurement. The connection of test equipment for the 
    ground resistance measurement shall be as shown in Figure 1. Refer to 
    RUS Bulletin 1751F-802, ``Electrical Protection Grounding 
    Fundamentals,'' for a comprehensive discussion of ground resistance 
    measurements.
        (d) Test equipment. The test equipment for making this measurement 
    is shown in Figure 1 as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23961]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.023
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23962]]
    
        (e) Applicable results. (1) For the CO and RST, the resistance 
    after the bond has been made to the MGB electric service ground shall 
    not exceed 5 ohms. Where the measured ground resistance exceeds 5 ohms, 
    the borrower shall determine what additional grounding, if any, shall 
    be provided.
        (2) For electronic equipment, the ground resistance shall not 
    exceed 25 ohms. Where the measured ground resistance exceeds 25 ohms, 
    the borrower shall determine what additional grounding, if any, shall 
    be provided.
        (3) When ground resistance measurements exceed the ground 
    resistance requirements of paragraphs (e)(1) and (e)(2) of this 
    section, refer to RUS Bulletin 1751F-802, ``Electrical Protection 
    Grounding Fundamentals,'' for suggested methods of reducing the ground 
    resistance.
        (f) Data record. Results of the CO and RST ground resistance 
    measurements shall be recorded. A suggested format similar to Format I, 
    Outside Plant Acceptance Tests--Subscriber Loops, in Sec. 1755.407 or a 
    format specified in the applicable construction contract may be used. 
    Results of the electronic equipment ground resistance measurements 
    shall be recorded. A suggested format similar to Format II, Outside 
    Plant Acceptance Tests--Trunk Circuits, in Sec. 1755.407 or a format 
    specified in the applicable construction contract may be used. Data 
    showing approximate moisture content of the soil at the time of 
    measurement, the temperature, the type of soil and a description of the 
    test equipment used shall also be included.
        (g) Probable causes for nonconformance. Refer to RUS Bulletin 
    1751F-802, ``Electrical Protection Grounding Fundamentals,'' and 
    Telecommunications Engineering and Construction Manual (TE&CM) Section 
    810, ``Electrical Protection of Electronic Analog and Digital Central 
    Office Equipment,'' for possible causes of nonconformance and suggested 
    methods for corrective action.
    
    
    Sec. 1755.403  Copper cable telecommunications plant measurements.
    
        (a) Shield or shield/armor continuity. (1) Tests and measurements 
    shall be made to ensure that cable shields or shield/armors are 
    electrically continuous. There are two areas of concern. The first is 
    shield or shield/armor bonding within a pedestal or splice and the 
    second is shield or shield/armor continuity between pedestals or 
    splices.
        (2) Measurement techniques outlined here for verification of shield 
    or shield/armor continuity are applicable to buried cable plant. 
    Measurements of shield continuity between splices in aerial cable plant 
    should be made prior to completion of splicing. Conclusive results 
    cannot be obtained on aerial plant after all bonds have been completed 
    to the supporting strand, multigrounded neutral, etc.
        (3) Method of measurement. (i) The shield or shield/armor 
    resistance measurements shall be made between pedestals or splices 
    using either a Wheatstone bridge or a volt-ohm meter. For loaded plant, 
    measurements shall be made on cable lengths that do not exceed one load 
    section. For nonloaded plant, measurements shall be made on cable 
    lengths that do not exceed 5,000 feet (ft) (1,524 meters (m)). All 
    bonding wires shall be removed from the bonding lugs at the far end of 
    the cable section to be measured. The step-by-step measurement 
    procedure shall be as shown in Figure 2.
        (ii) Cable shield or shield/armor continuity within pedestals or 
    splices shall be measured with a cable shield splice continuity test 
    set. The step-by-step measurement procedure outlined in the 
    manufacturer's operating instructions for the specific test equipment 
    being used shall be followed.
        (4) Test equipment. (i) The test equipment for measuring cable 
    shield or shield/armor resistance between pedestals or splices is shown 
    in Figure 2 as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23963]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.024
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23964]]
    
        (ii) A cable shield splice continuity tester shall be used to 
    measure shield or shield/armor continuity within pedestals or splices.
        (5) Applicable results. (i) The shield or shield/armor resistance 
    per 1000 ft and per kilometer (km) for cable diameters and types of 
    shielding materials are given in Table 1 (English Units) and Table 2 
    (Metric Units), respectively as follows:
    
                 Table 1.--Shield Resistance @ 68  deg.F (20 deg.C) Cable Diameters Versus Shield Types             
                                                     [English Units]                                                
    ----------------------------------------------------------------------------------------------------------------
                                                               Nominal resistance ohm/1000 ft.                      
       Outside diameter inches (in.)   -----------------------------------------------------------------------------
                                             A            B            C            D            E            F     
    ----------------------------------------------------------------------------------------------------------------
    0.40-0.49.........................         0.77         1.54         1.65         1.96         2.30         5.51
    0.50-0.59.........................         0.64         1.28         1.37         1.63         1.91         4.58
    0.60-0.69.........................         0.51         1.03         1.10         1.31         1.53         3.67
    0.70-0.79.........................         0.44         0.88         0.94  ...........         1.31         3.14
    0.80-0.89.........................         0.38         0.77         0.82  ...........         1.14         2.74
    0.90-0.99.........................         0.35         0.69         0.74  ...........         1.03         2.47
    1.00-1.09.........................         0.31         0.62         0.66  ...........         0.92         2.20
    1.10-1.19.........................         0.28         0.56         0.60  ...........         0.84         2.00
    1.20-1.29.........................         0.26         0.51         0.55  ...........         0.77         1.84
    1.30-1.39.........................         0.24         0.48         0.51  ...........         0.71         1.70
    1.40-1.49.........................         0.22         0.44         0.47  ...........         0.65         1.57
    1.50-1.59.........................         0.21         0.41         0.44  ...........         0.61         1.47
    1.60-1.69.........................         0.19         0.38         0.41  ...........         0.57         1.37
    1.70-1.79.........................         0.18         0.37         0.39  ...........         0.54         1.30
    1.80-1.89.........................         0.17         0.35         0.37  ...........         0.51         1.24
    1.90-1.99.........................         0.16         0.33         0.35  ...........         0.49         1.17
    2.00-2.09.........................         0.15         0.31         0.33  ...........         0.46         1.10
    2.10-2.19.........................         0.15         0.29         0.31  ...........         0.43         1.03
    2.20-2.29.........................         0.14         0.28         0.30  ...........         0.42         1.00
    2.30-2.39.........................         0.14         0.27         0.29  ...........         0.40         0.97
    2.40-2.49.........................         0.13         0.25         0.27  ...........         0.38         0.90
    2.50-2.59.........................         0.12         0.24         0.26  ...........         0.36         0.87
    2.60-2.69.........................         0.12         0.23         0.25  ...........         0.35         0.83
    2.70-2.79.........................         0.11         0.22         0.24  ...........         0.33         0.80
    2.80-2.89.........................         0.11         0.22         0.24  ...........         0.33         0.80
    2.90-2.99.........................         0.11         0.22         0.23  ...........         0.32         0.77
    3.00-3.09.........................         0.10         0.21         0.22  ...........         0.31         0.73
    3.10-3.19.........................         0.10         0.20         0.21  ...........         0.29         0.70
    3.20-3.29.........................         0.10         0.20         0.21  ...........         0.29         0.70
    3.30-3.39.........................         0.09         0.19         0.20  ...........         0.28         0.67
    3.40-3.49.........................         0.09         0.18         0.19  ...........         0.26         0.63
    3.50-3.59.........................         0.09         0.18         0.19  ...........         0.26         0.63
    3.60-3.69.........................         0.08         0.17         0.18  ...........         0.25         0.60
    3.70-3.79.........................         0.08         0.17         0.18  ...........         0.25         0.60
    3.80-3.89.........................         0.08         0.16         0.17  ...........         0.24         0.57
    3.90-3.99.........................         0.08         0.16         0.17  ...........         0.24         0.57
    4.00-4.99.........................         0.07         0.15         0.16  ...........         0.22         0.53
    ----------------------------------------------------------------------------------------------------------------
    Where: Column A-10 mil Copper shield.                                                                           
    Column B--5 mil Copper shield.                                                                                  
    Column C--8 mil Coated Aluminum and 8 mil Coated Aluminum/6 mil Coated Steel shields.                           
    Column D--7 mil Alloy 194 shield.                                                                               
    Column E--6 mil Alloy 194 and 6 mil Copper Clad Stainless Steel shields.                                        
    Column F--5 mil Copper Clad Stainless Steel and 5 mil Copper Clad Alloy Steel shields.                          
    
    
                  Table 2.--Shield Resistance @ 68 deg.F (20 deg.C) Cable Diameters Versus Shield Types             
                                                     [Metric Units]                                                 
    ----------------------------------------------------------------------------------------------------------------
                                                                  Nominal Resistance ohm/km                         
     Outside diameter millimeters (mm) -----------------------------------------------------------------------------
                                             A            B            C            D            E            F     
    ----------------------------------------------------------------------------------------------------------------
    10.2--12.5........................         2.53         5.05         5.41         6.43         7.55        18.08
    12.7--15.0........................         2.10         4.20         4.49         5.35         6.27        15.03
    15.2--17.5........................         1.67         3.38         3.61         4.30         5.02        12.04
    17.8--20.1........................         1.44         2.89         3.08  ...........         4.30        10.30
    20.3--22.6........................         1.25         2.53         2.69  ...........         3.74         8.99
    22.9--25.1........................         1.15         2.26         2.43  ...........         3.38         8.10
    25.4--27.7........................         1.02         2.03         2.16  ...........         3.02         7.22
    27.9--30.2........................         0.92         1.84         1.97  ...........         2.76         6.56
    30.5--32.8........................         0.85         1.67         1.80  ...........         2.53         6.04
    33.0--35.3........................         0.79         1.57         1.67  ...........         2.33         5.58
    35.6--37.8........................         0.72         1.44         1.54  ...........         2.13         5.15
    38.1--40.4........................         0.69         1.34         1.44  ...........         2.00         4.82
    
    [[Page 23965]]
    
                                                                                                                    
    40.6--42.9........................         0.62         1.25         1.34  ...........         1.87         4.49
    43.2--45.5........................         0.59         1.21         1.28  ...........         1.77         4.26
    45.7--48.0........................         0.56         1.15         1.21  ...........         1.67         4.07
    48.3--50.5........................         0.52         1.08         1.15  ...........         1.61         3.84
    50.8--53.1........................         0.49         1.02         1.08  ...........         1.51         3.61
    53.3--55.6........................         0.49         0.95         1.02  ...........         1.41         3.38
    55.9--58.2........................         0.46         0.92         0.98  ...........         1.38         3.28
    58.4--60.7........................         0.46         0.89         0.95  ...........         1.31         3.18
    61.0--63.2........................         0.43         0.82         0.89  ...........         1.25         2.95
    63.5--65.8........................         0.39         0.79         0.85  ...........         1.18         2.85
    66.0--68.3........................         0.39         0.75         0.82  ...........         1.15         2.72
    68.6--70.9........................         0.36         0.72         0.79  ...........         1.08         2.62
    71.1--73.4........................         0.36         0.72         0.79  ...........         1.08         2.62
    73.7--75.9........................         0.36         0.72         0.75  ...........         1.05         2.53
    76.2--78.5........................         0.33         0.69         0.72  ...........         1.02         2.39
    78.7--81.0........................         0.33         0.66         0.69  ...........         0.95         2.30
    81.3--83.6........................         0.33         0.66         0.69  ...........         0.95         2.30
    83.6--86.1........................         0.29         0.62         0.66  ...........         0.92         2.20
    86.4--88.6........................         0.29         0.59         0.62  ...........         0.85         2.07
    88.9--91.2........................         0.29         0.59         0.62  ...........         0.85         2.07
    91.4--93.7........................         0.26         0.56         0.59  ...........         0.82         1.97
    94.0--96.3........................         0.26         0.56         0.59  ...........         0.82         1.97
    96.5--98.8........................         0.26         0.52         0.56  ...........         0.79         1.87
    99.1--101.3.......................         0.26         0.52         0.56  ...........         0.79         1.87
    101.6--103.9......................         0.23         0.49         0.52  ...........         0.72        1.74 
    ----------------------------------------------------------------------------------------------------------------
    Where: Column A--10 mil Copper shield.                                                                          
    Column B--5 mil Copper shield.                                                                                  
    Column C--8 mil Coated Aluminum and 8 mil Coated Aluminum/6 mil Coated Steel shields.                           
    Column D--7 mil Alloy 194 shield.                                                                               
    Column E--6 mil Alloy 194 and 6 mil Copper Clad Stainless Steel shields.                                        
    Column F--5 mil Copper Clad Stainless Steel and 5 mil Copper Clad Alloy Steel shields.                          
    
        (ii) All values of shield and shield/armor resistance provided in 
    Tables 1 and 2 in (a)(5)(i) of this section are considered 
    approximations. If the measured value corrected to 68 deg.F (20 deg.C) 
    is within 30 percent (%) of the value shown in Table 1 or 
    2, the shield and shield/armor shall be assumed to be continuous.
        (iii) To correct the measured shield resistance to the reference 
    temperature of 68 deg.F (20 deg.C) use the following formulae:
    
    R68=Rt/[1+A(t-68)] for English Units
    R20=Rt/[1+A(t-20)] for Metric Units
    
    Where:
    
    R68=Shield resistance corrected to 68 deg.F in ohms.
    R20=Shield resistance corrected to 20 deg.C in ohms.
    Rt=Shield resistance at measurement temperature in ohms.
    A=Temperature coefficient of the shield tape.
    t=Measurement temperature in  deg.F or ( deg.C).
    
        (iv) The temperature coefficients (A) for the shield tapes to be 
    used in the formulae referenced in paragraph (a)(5)(iii) of this 
    section are as follows:
        (A) 5 and 10 mil copper = 0.0021 for English units and 0.0039 for 
    Metric units;
        (B) 8 mil coated aluminum and 8 mil coated aluminum/6 mil coated 
    steel = 0.0022 for English units and 0.0040 for Metric units;
        (C) 5 mil copper clad stainless steel and 5 mil copper clad alloy 
    steel = 0.0024 for English units and 0.0044 for Metric units;
        (D) 6 mil copper clad stainless steel = 0.0019 for English units 
    and 0.0035 for Metric units; and
        (E) 6 and 7 mil alloy 194 = 0.0013 for English units and 0.0024 for 
    Metric units.
        (v) When utilizing shield continuity testers to measure shield and 
    shield/armor continuity within pedestals or splices, refer to the 
    manufacturer's published information covering the specific test 
    equipment to be used and for anticipated results.
        (6) Data record. Measurement data from shield continuity tests 
    shall be recorded together with anticipated Table 1 or 2 values (see 
    paragraph (a)(5)(i) of this section) in an appropriate format to permit 
    comparison. The recorded data shall include specific location, cable 
    size, cable type, type of shield or shield/armor, if known, etc.
        (7) Probable causes for nonconformance. Among probable causes for 
    nonconformance are broken or damaged shields or shield/armors, bad 
    bonding harnesses, poorly connected bonding clamps, loose bonding lugs, 
    etc.
        (b) Conductor continuity. After placement of all cable and wire 
    plant has been completed and joined together in continuous lengths, 
    tests shall be made to ascertain that all pairs are free from grounds, 
    shorts, crosses, and opens, except for those pairs indicated as being 
    defective by the cable manufacturer. The tests for grounds, shorts, 
    crosses, and opens are not separate tests, but are inherent in other 
    acceptance tests discussed in this section. The test for grounds, 
    shorts, and crosses is inherent when conductor insulation resistance 
    measurements are conducted per paragraph (c) of this section, while 
    tests for opens are inherent when tests are conducted for loop 
    resistance, insertion loss, noise, or return loss measurements, per 
    paragraphs (d), (e), or (f) of this section. The borrower shall make 
    certain that all defective pairs are corrected, except
    
    [[Page 23966]]
    
    those noted as defective by the cable manufacturer in accordance with 
    the marking provisions of the applicable cable and wire specifications. 
    All defective pairs that are not corrected shall be reported in writing 
    with details of the corrective measures attempted.
        (c) Dc insulation resistance (IR) measurement. (1) IR measurements 
    shall be made on completed lengths of insulated cable and wire plant.
        (2) Method of measurement. (i) The IR measurement shall be made 
    between each conductor and all other conductors, sheath, shield and/or 
    shield/armor, and/or support wire electrically connected together and 
    to the main distributing frame (MDF) ground. The measurement shall be 
    made from the central office with the entire length of the cable under 
    test and, where used with all protectors and load coils connected. For 
    COs containing solid state arresters, the solid state arresters shall 
    be removed before making the IR measurements. Field mounted voice 
    frequency repeaters, where used, may be left connected for the IR test 
    but all carrier frequency equipment, including carrier repeaters and 
    terminals, shall be disconnected. Pairs used to feed power remote from 
    the CO shall have the power disconnected and the tip and ring 
    conductors shall be opened before making IR tests. All conductors shall 
    be opened at the far end of the cable being measured.
        (ii) IR tests are normally made from the MDF with all CO equipment 
    disconnected at the MDF, but this test may be made on new cables at 
    field locations before they are spliced to existing cables. The method 
    of measurement shall be as shown in Figure 3 as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23967]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.025
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23968]]
    
        (iii) If the IR of the conductor cannot be measured because of 
    breakdown of lightning arresters by the test voltage, the arrester 
    units shall be removed and the conductor IR retested. If the IR then 
    meets the minimum requirements, the conductor will be considered 
    satisfactory. Immediately following the IR tests, all arrester units 
    which have been removed shall be reinstalled.
        (3) Test equipment. (i) IR measurements shall be made with either 
    an insulation resistance test set or a direct current (dc) bridge type 
    megohmmeter.
        (ii) The IR test set shall have an output voltage not to exceed 500 
    volts dc and shall be of the hand cranked or battery operated type.
        (iii) The dc bridge type megohmmeter, which may be alternating 
    current (ac) powered, shall have scales and multiplier which make it 
    possible to accurately read IR from 1 megohm to 1 gigohm. The voltage 
    applied to the conductors under test shall not exceed ``250 volts dc'' 
    when using an instrument having adjustable test voltage levels. This 
    will help to prevent breakdown of lightning arresters.
        (4) Applicable results. (i) For all new insulated cable or wire 
    facilities, the expected IR levels are normally greater than 1,000 to 
    2,000 megohm-mile (1,609 to 3,218 megohm-km). A value of 500 megohm-
    mile (805 megohm-km) at 68 deg.F (20 deg.C) shall be the minimum 
    acceptable value of IR. IR varies inversely with the length and the 
    temperature.
        (ii) The megohm-mile (megohm-km) value for a conductor may be 
    computed by multiplying the actual scale reading in megohms on the test 
    set by the length in miles (km) of the conductor under test.
        (iii) The objective insulation resistance may be determined by 
    dividing 500 by the length in miles (805 by the length in km) of the 
    cable or wire conductor being tested. The resulting value shall be the 
    minimum acceptable meter scale reading in megohms.
        (iv) Due to the differences between various insulating materials 
    and filling compounds used in manufacturing cable or wire, it is 
    impractical to provide simple factors to predict the magnitude of 
    variation in insulation resistance due to temperature. The variation 
    can, however, be substantial for wide excursions in temperature from 
    the ambient temperature of 68  deg.F (20  deg.C).
        (v) Borrowers should be certain that tip and ring IR measurements 
    of each pair are approximately the same. Borrowers should also be 
    certain that IR measurements are similar for cable or wire sections of 
    similar length and cable or wire type. If some pairs measure 
    significantly lower, borrowers should attempt to improve these pairs in 
    accordance with cable manufacturer's recommendations.
    
        Note: Only the megohm-mile (megohm-km) requirement shall be 
    cause for rejection, not individual measurement differences.
    
        (5) Data record. The measurement data shall be recorded. Suggested 
    formats similar to Format I, Outside Plant Acceptance Tests--Subscriber 
    Loops, or Format II, Outside Plant Acceptance Tests--Trunk Circuits, in 
    Sec. 1755.407 or formats specified in the applicable construction 
    contract may be used.
        (6) Probable causes for nonconformance. (i) When an IR measurement 
    is below 500 megohm-mile (805 megohm-km), the cable or wire temperature 
    at the time of testing must then be taken into consideration. If this 
    temperature is well above 68  deg.F (20  deg.C), the measurement shall 
    be disregarded and the cable or wire shall be remeasured at a time when 
    the temperature is approximately 68  deg.F (20  deg.C). If the result 
    is then 500 megohm-mile (805 megohm-km) or greater, the cable or wire 
    shall be considered satisfactory.
        (ii) Should the cable or wire fail to meet the 500 megohm-mile (805 
    megohm-km) requirement when the temperature is known to be 
    approximately 68  deg.F (20  deg.C) there is not yet justification for 
    rejection of the cable or wire. Protectors, lightning arresters, etc., 
    may be a source of low insulation resistance. These devices shall be 
    removed from the cable or wire and the cable or wire IR measurement 
    shall be repeated. If the result is acceptable, the cable or wire shall 
    be considered acceptable. The removed devices which caused the low 
    insulation resistance value shall be identified and replaced, if found 
    defective.
        (iii) When the cable or wire alone is still found to be below the 
    500 megohm-mile (805 megohm-km) requirement after completing the steps 
    in paragraph (c)(6)(i) and/or paragraph (c)(6)(ii) of this section, the 
    test shall be repeated to measure the cable or wire in sections to 
    isolate the piece(s) of cable or wire responsible. The cable or wire 
    section(s) that is found to be below the 500 megohm-mile (805 megohm-
    km) requirement shall be either repaired in accordance with the cable 
    or wire manufacturer's recommended procedure or shall be replaced as 
    directed by the borrower.
        (d) Dc loop resistance and dc resistance unbalance measurement. (1) 
    When specified by the borrower, dc loop resistance and dc resistance 
    unbalance measurements shall be made on all cable pairs used as trunk 
    circuits. The dc loop resistance and dc resistance unbalance 
    measurements shall be made between CO locations. Measurements shall 
    include all components of the cable path.
        (2) Dc loop resistance and dc resistance unbalance measurements 
    shall be made on all cable pairs used as subscriber loop circuits when:
        (i) Specified by the borrower;
        (ii) A large number of long loops terminate at one location 
    (similar to trunk circuits); or
        (iii) Circuit balance is less than 60 dB when computed from noise 
    measurements as described in paragraph (e) of this section.
        (3) Dc resistance unbalance is controlled to the maximum possible 
    degree by the cable specification. Allowable random unbalance is 
    specified between tip and ring conductors within each reel. Further 
    random patterns should occur when the cable conductor size changes. 
    Cable meeting the unbalance requirements of the cable specification may 
    under some conditions result in unacceptable noise levels as discussed 
    in paragraph (d)(6)(iii) of this section.
        (4) Method of measurement. The method of measurement shall be as 
    detailed in Figures 4 and 5.
        (5) Test equipment. The test equipment is shown in Figures 4 and 5 
    as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23969]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.026
    
    
    
    [[Page 23970]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.027
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23971]]
    
        (6) Applicable results. (i) The measured dc loop resistance shall 
    be within  5% of the calculated dc loop resistance when 
    corrected for temperature.
        (ii) The calculated dc loop resistance is computed as follows:
        (A) Multiply the length of each different gauge by the applicable 
    resistance per unit length as shown in Table 3 as follows:
    
               Table 3.--DC Loop Resistance @ 68 deg.F (20 deg.C)           
    ------------------------------------------------------------------------
                                                      Loop resistance       
            American wire gauge (AWG)        -------------------------------
                                               ohms/1000 ft       ohms/km   
    ------------------------------------------------------------------------
    19......................................            16.1            52.8
    22......................................            32.4           106.3
    24......................................            51.9           170.3
    26......................................            83.3           273.3
    ------------------------------------------------------------------------
    
        (B) Add the individual resistances for each gauge to give the total 
    calculated dc loop resistance at a temperature of 68 deg.F (20 deg.C).
        (C) Correct the total calculated dc loop resistance at the 
    temperature of 68 deg.F (20 deg.C) to the measurement temperature by 
    the following formulae:
    
    Rt=R68 x [1+0.0022 x t--68)] for English Units
    Rt=R20 x [1+0.0040 x (t--20)] for Metric Units
    
    Where:
    
    Rt = Loop resistance at the measurement temperature in ohms.
    R68 = Loop resistance at a temperature of 68 deg.F in ohms.
    R20 = Loop resistance at a temperature of 20 deg.C in ohms.
    t = Measurement temperature in  deg.F or ( deg.C).
        (D) Compare the calculated dc loop resistance at the measurement 
    temperature to the measured dc loop resistance to determine compliance 
    with the requirement specified in paragraph (d)(6)(i) of this section.
        (iii) Resistance varies directly with temperature change. For 
    copper conductor cables, the dc resistance changes by  1% 
    for every  5 deg.F (2.8 deg.C) change in temperature from 
    68 deg.F (20 deg.C).
        (iv) The dc resistance unbalance between the individual conductors 
    of a pair shall not exceed that value which will result in a circuit 
    balance of less than 60 dB when computed from noise measurements as 
    described in paragraph (e) of this section. It is impractical to 
    establish a precise limit for overall circuit dc resistance unbalance 
    due to the factors controlling its contribution to circuit noise. These 
    factors include location of the resistance unbalance in relation to a 
    low impedance path to ground (close to the central office) and the 
    magnitude of unbalance in short lengths of cable making up the total 
    circuit length. The objective is to obtain the minimum unbalance 
    throughout the entire circuit when it is ascertained through noise 
    measurements that dc resistance unbalance may be contributing to poor 
    cable balance.
        (v) Pairs with poor noise balance may be improved by reversing tip 
    and ring conductors of pairs at cable splices. Where dc resistance 
    unbalances are systematic over the total trunk circuit or loop circuit 
    length, tip and ring reversals may be made at frequent intervals. Where 
    the unbalances are concentrated in a shorter section of cable, only one 
    tip and ring reversal should be required. Concentrated dc resistance 
    unbalance produces maximum circuit noise when located adjacent to the 
    central office. Concentrated dc resistance unbalance will contribute to 
    overall circuit noise at a point approximately two-thirds (\2/3\) of 
    the distance to the subscriber. All deliberate tip and ring reversals 
    shall be tagged and identified to prevent plant personnel from removing 
    the reversals when resplicing these connections in the future. The 
    number of tip and ring reversals shall be held to a minimum.
        (vi) A systematic dc resistance unbalance can sometimes be 
    accompanied by other cable parameters that are marginal. Among these 
    are pair-to-pair capacitance unbalance, capacitance unbalance-to-
    ground, and 150 kilohertz (kHz) crosstalk loss. Engineering judgment 
    has to be applied in each case. Rejection of cable for excessive dc 
    resistance unbalance shall only apply to a single reel length, or 
    shorter.
    
    [[Page 23972]]
    
        (7) Data record. The measurement data for dc loop resistance and dc 
    resistance unbalance shall be recorded. Suggested formats similar to 
    Format I for subscriber loops and Format II for trunk circuits in 
    Sec. 1755.407 or formats specified in the applicable construction 
    contract may be used.
        (8) Probable causes for nonconformance. Dc loop resistance and dc 
    resistance unbalance are usually the result of the resistance of 
    individual conductors used in the manufacture of the cable. Resistance 
    unbalance can be worsened by defective splicing of the conductors 
    (splicing connectors, improper crimping tool, etc.).
        (e) Subscriber loop measurement (loop checking). (1) When specified 
    by the borrower, insertion loss and noise measurements shall be 
    performed on subscriber loops after connection of a line circuit to the 
    loop by the one person method using loop checking equipment from the 
    customer access location. For this method, the central office should be 
    equipped with a 900 ohm plus two microfarad quiet termination and a 
    milliwatt generator having the required test frequencies; or a portable 
    milliwatt generator having the desired frequencies may be used, 
    especially, where several small offices are involved.
        (2) At a minimum, insertion loss and frequency response of 
    subscriber loop plant shall be measured at 1,000, 1,700, 2,300, and 
    2,800 Hertz (Hz). When additional testing frequencies are desired, the 
    additional frequencies shall be specified in the applicable 
    construction contract.
        (3) Measurements of insertion loss and noise shall be made on five 
    percent or more of the pairs. A minimum of five pairs shall be tested 
    on each route. Pairs shall be selected on a random basis with greater 
    consideration in the selection given to the longer loops. Consideration 
    shall be given to measuring a large percentage, up to 100 percent, of 
    all loops.
        (4) Method of measurement--(i) Insertion loss. The step-by-step 
    measurement procedure shall be as shown in Figure 6. The output level 
    of the milliwatt generator tones shall be determined prior to leaving 
    the CO. This shall be accomplished by dialing the milliwatt generator 
    number from a spare line at the MDF and measuring with the same 
    equipment to be used in the tests at customer access locations. The 
    output levels shall be recorded for reference later. Insertion loss 
    measurements shall be made across the tip and ring terminals of the 
    pair under test. Figure 6 is as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23973]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.028
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23974]]
    
        (ii) Noise. The step-by-step measurement procedure shall be as 
    shown in Figure 7. Prior to leaving the CO for testing, dial the 900 
    ohm plus two microfarad quiet termination from a spare pair and measure 
    the termination to determine that it actually is quiet. Circuit noise 
    (noise-metallic) shall be measured at the customer access location 
    across the tip and ring terminals of the pair under test. Power 
    influence (direct reading with loop checking equipment) shall be 
    measured at the customer access location from tip and ring conductors-
    to-ground (this connection is completed via the test unit). The power 
    influence measurement includes the entire talking connection from the 
    quiet termination to the customer. (That is, the power influence 
    measurement includes all the CO equipment which normally makes up the 
    connection.) Figure 7 is as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23975]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.029
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23976]]
    
        (5) Test equipment. (i) Loop checking equipment which is available 
    from several manufacturers may be used for these measurements. The 
    equipment should have the capability of measuring loop current, 
    insertion loss, circuit noise (NM) and power influence (PI). The test 
    equipment manufacturer's operating instructions shall be followed.
        (ii) There should be no measurable transmission loss when testing 
    through loop extenders.
        (6) Applicable results--(i) Insertion loss. (A) For D66 loaded 
    cables (a specific loading scheme using a 66 millihenry inductor spaced 
    nominally at 4,500 ft [1,371 m] intervals) measured at a point one-half 
    section length beyond the last load point, the measured nonrepeated 
    insertion loss shall be within  10% at 1000, 1700, 2300, 
    and 2800 Hz,  15% at 3400 Hz and  20% at 4000 
    Hz of the calculated insertion loss at the same frequencies and 
    temperature.
        (B) For H88 loaded cables (a specific loading scheme using an 88 
    millihenry inductor spaced nominally at 6,000 ft [1,829 m] intervals) 
    measured at a point one-half section length beyond the last load point, 
    the measured nonrepeatered insertion loss shall be within  
    10% at 1000, 1700, and 2300 Hz,  15% at 2800 Hz, and 
     20% at 3400 Hz of the calculated insertion loss at the 
    same frequencies and temperature.
        (C) For nonloaded cables, the measured insertion loss shall be 
    within  10% at 1000, 1700, 2300, and 2800 Hz,  
    15% at 3400 Hz and  20% at 4000 Hz of the calculated 
    insertion loss at the same frequencies and temperature.
        (D) For loaded cables, the calculated loss at each desired 
    frequency shall be computed as follows:
        (1) Multiply the length in miles (km) of each different gauge in 
    the loaded portion of the loop (between the office and a point one-half 
    load section beyond the furthest load point) by the applicable decibel 
    (dB)/mile (dB/km) value shown in Table 4 or 5. This loss represents the 
    total loss for each gauge in the loaded portion of the loop;
        (2) Multiply the length in miles (km) of each different gauge in 
    the end section or nonloaded portion of the cable (beyond a point one-
    half load section beyond the furthest load point) by the applicable dB/
    mile (dB/km) value shown in Table 6. This loss represents the total 
    loss for each gauge in the nonloaded portion of the loop; and
        (3) The total calculated insertion loss is computed by adding the 
    individual losses determined in paragraphs (e)(6)(i)(D)(1) and 
    (e)(6)(i)(D)(2) of this section.
        (E) For nonloaded cables, the calculated loss at each desired 
    frequency shall be computed by multiplying the length in miles (km) of 
    each different gauge by the applicable dB/mile (dB/km) value shown in 
    Table 6 and then adding the individual losses for each gauge to 
    determine the total calculated insertion loss for the nonloaded loop.
        (F) The attenuation information in Tables 4, 5, and 6 are based on 
    a cable temperature of 68  deg.F (20  deg.C). Insertion loss varies 
    directly with temperature. To convert measured losses for loaded cables 
    to a different temperature, use the following value for copper 
    conductors: For each 5  deg.F ( 2.8  deg.C) 
    change in the temperature from 68  deg.F (20  deg.C), change the 
    insertion loss at any frequency by 1%. To convert measured 
    losses for nonloaded cables to a different temperature, use the 
    following value for copper conductors: For each 10  deg.F 
    (5.6  deg.C) change in the temperature from 68  deg.F (20 
    deg.C), change the insertion loss at any frequency by 1%. 
    Tables 4, 5, and 6 are as follows:
    
    Table 4.--Frequency Attenuation @ 68  deg.F (20  deg.C) D66 Loaded Exchange Cables 83 nanofarad (nF)/mile (52 nF/
                                                     km) (See Note)                                                 
    ----------------------------------------------------------------------------------------------------------------
                                                                    Attenuation dB/mile (dB/km) AWG                 
                   Frequency (Hz)                -------------------------------------------------------------------
                                                         19               22               24               26      
    ----------------------------------------------------------------------------------------------------------------
    200.........................................      0.41 (0.26)      0.67 (0.42)      0.90 (0.56)      1.21 (0.75)
    400.........................................      0.43 (0.26)      0.77 (0.48)      1.09 (0.68)      1.53 (0.95)
    600.........................................      0.44 (0.27)      0.80 (0.49)      1.17 (0.73)      1.70 (1.06)
    800.........................................      0.44 (0.27)      0.81 (0.50)      1.21 (0.75)      1.80 (1.12)
    1000........................................      0.44 (0.27)      0.82 (0.51)      1.23 (0.76)      1.86 (1.15)
    1200........................................      0.45 (0.28)      0.83 (0.52)      1.24 (0.77)      1.91 (1.19)
    1400........................................      0.45 (0.28)      0.83 (0.52)      1.26 (0.78)      1.94 (1.20)
    1600........................................      0.45 (0.28)      0.84 (0.52)      1.26 (0.78)      1.96 (1.22)
    1800........................................      0.45 (0.28)      0.84 (0.52)      1.27 (0.78)      1.98 (1.23)
    2000........................................      0.46 (0.29)      0.85 (0.53)      1.28 (0.79)      1.99 (1.24)
    2200........................................      0.46 (0.29)      0.85 (0.53)      1.29 (0.80)      2.01 (1.25)
    2400........................................      0.47 (0.29)      0.86 (0.53)      1.30 (0.81)      2.02 (1.26)
    2600........................................      0.47 (0.29)      0.87 (0.54)      1.31 (0.81)      2.04 (1.27)
    2800........................................      0.48 (0.30)      0.88 (0.55)      1.32 (0.82)      2.07 (1.29)
    3000........................................      0.49 (0.30)      0.89 (0.55)      1.34 (0.83)      2.10 (1.30)
    3200........................................      0.50 (0.31)      0.91 (0.57)      1.36 (0.84)      2.13 (1.32)
    3400........................................      0.52 (0.32)      0.93 (0.58)      1.40 (0.87)      2.19 (1.36)
    3600........................................      0.54 (0.34)      0.97 (0.60)      1.45 (0.90)      2.26 (1.40)
    3800........................................      0.57 (0.35)      1.02 (0.63)      1.52 (0.94)      2.36 (1.47)
    4000........................................      0.62 (0.38)      1.10 (0.68)      1.63 (1.01)      2.53 (1.57)
    ----------------------------------------------------------------------------------------------------------------
    Note: Between end-section lengths of 2,250 ft (686 m) for D66 loading.                                          
    
    
     Table 5.--Frequency Attenuation @ 68  deg.F (20  deg.C) H88 Loaded Exchange Cables 83 nF/ mile (52 nF/km) (See 
                                                          Note)                                                     
    ----------------------------------------------------------------------------------------------------------------
                                                                    Attenuation dB/mile (dB/km) AWG                 
                   Frequency (Hz)                -------------------------------------------------------------------
                                                         19               22               24               26      
    ----------------------------------------------------------------------------------------------------------------
    200.........................................      0.40 (0.25)      0.66 (0.41)      0.90 (0.56)      1.20 (0.75)
    
    [[Page 23977]]
    
                                                                                                                    
    400.........................................      0.42 (0.26)      0.76 (0.47)      1.08 (0.67)      1.53 (0.95)
    600.........................................      0.43 (0.27)      0.79 (0.49)      1.16 (0.72)      1.70 (1.06)
    800.........................................      0.43 (0.27)      0.80 (0.50)      1.20 (0.75)      1.80 (1.12)
    1000........................................      0.43 (0.27)      0.81 (0.50)      1.23 (0.76)      1.86 (1.15)
    1200........................................      0.44 (0.27)      0.82 (0.51)      1.24 (0.77)      1.91 (1.19)
    1400........................................      0.44 (0.28)      0.82 (0.51)      1.25 (0.78)      1.94 (1.20)
    1600........................................      0.44 (0.27)      0.83 (0.52)      1.26 (0.78)      1.97 (1.22)
    1800........................................      0.45 (0.28)      0.84 (0.52)      1.28 (0.79)      1.99 (1.24)
    2000........................................      0.46 (0.29)      0.85 (0.53)      1.29 (0.80)      2.02 (1.26)
    2200........................................      0.47 (0.29)      0.86 (0.53)      1.31 (0.81)      2.06 (1.28)
    2400........................................      0.48 (0.30)      0.89 (0.55)      1.34 (0.83)      2.10 (1.30)
    2600........................................      0.50 (0.31)      0.92 (0.57)      1.39 (0.86)      2.18 (1.35)
    2800........................................      0.53 (0.33)      0.97 (0.60)      1.47 (0.91)      2.29 (1.42)
    3000........................................      0.59 (0.37)      1.07 (0.66)      1.60 (0.99)      2.48 (1.54)
    3200........................................      0.71 (0.44)      1.26 (0.78)      1.87 (1.16)      2.86 (1.78)
    3400........................................      1.14 (0.71)      1.91 (1.19)      2.64 (1.64)      3.71 (2.30)
    3600........................................      4.07 (2.53)      4.31 (2.68)      4.65 (2.90)      5.30 (3.29)
    3800........................................      6.49 (4.03)      6.57 (4.08)      6.72 (4.18)      7.06 (4.39)
    4000........................................      8.22 (5.11)      8.27 (5.14)      8.36 (5.19)     8.58 (5.33) 
    ----------------------------------------------------------------------------------------------------------------
    Note: Between end-section lengths of 3,000 ft (914 m) for H88 loading.                                          
    
    
      Table 6.--Frequency Attenuation @ 68  deg.F (20  deg.C) Nonloaded Exchange Cables 83 nF/ mile (52 nF/km) AWG  
    ----------------------------------------------------------------------------------------------------------------
                                                                    Attenuation dB/mile (dB/km) AWG                 
                   Frequency (Hz)                -------------------------------------------------------------------
                                                         19               22               24               26      
    ----------------------------------------------------------------------------------------------------------------
    200.........................................      0.58 (0.36)      0.82 (0.51)      1.03 (0.64)      1.30 (0.81)
    400.........................................      0.81 (0.51)      1.15 (0.71)      1.45 (0.90)      1.84 (1.14)
    600.........................................      0.98 (0.61)      1.41 (0.87)      1.77 (1.10)      2.26 (1.40)
    800.........................................      1.13 (0.70)      1.62 (1.01)      2.04 (1.27)      2.60 (1.61)
    1000........................................      1.25 (0.78)      1.80 (1.12)      2.28 (1.42)      2.90 (1.80)
    1200........................................      1.36 (0.84)      1.97 (1.22)      2.50 (1.55)      3.17 (1.97)
    1400........................................      1.46 (0.91)      2.12 (1.32)      2.69 (1.67)      3.42 (2.12)
    1600........................................      1.55 (0.96)      2.26 (1.40)      2.87 (1.78)      3.65 (2.27)
    1800........................................      1.63 (1.01)      2.39 (1.48)      3.04 (1.89)      3.87 (2.40)
    2000........................................      1.71 (1.06)      2.51 (1.56)      3.20 (1.99)      4.08 (2.53)
    2200........................................      1.78 (1.11)      2.62 (1.63)      3.35 (2.08)      4.27 (2.65)
    2400........................................      1.85 (1.15)      2.73 (1.70)      3.49 (2.17)      4.45 (2.76)
    2600........................................      1.91 (1.19)      2.83 (1.76)      3.62 (2.25)      4.63 (2.88)
    2800........................................      1.97 (1.22)      2.93 (1.82)      3.75 (2.33)      4.80 (2.98)
    3000........................................      2.03 (1.26)      3.02 (1.88)      3.88 (2.41)      4.96 (3.08)
    3200........................................      2.08 (1.29)      3.11 (1.93)      4.00 (2.48)      5.12 (3.18)
    3400........................................      2.13 (1.32)      3.19 (1.98)      4.11 (2.55)      5.27 (3.27)
    3600........................................      2.18 (1.35)      3.28 (2.04)      4.22 (2.62)      5.41 (3.36)
    3800........................................      2.22 (1.38)      3.36 (2.09)      4.33 (2.69)      5.55 (3.45)
    4000........................................      2.27 (1.41)      3.43 (2.13)      4.43 (2.75)      5.69 (3.53)
    ----------------------------------------------------------------------------------------------------------------
    
        (G) For loaded subscriber loops, the 1 kHz loss shall be 
    approximately 0.45 dB per 100 ohms of measured dc loop resistance. This 
    loss shall be the measured loss less the net gain of any voice 
    frequency repeaters in the circuit. Testing shall also be conducted to 
    verify that the loss increases gradually as the frequency increases. 
    The loss on H88 loaded loops should be down only slightly at 2.8 kHz 
    but drop rapidly above 2.8 kHz. The loss on D66 loaded loops shall be 
    fairly constant to about 3.4 kHz and there shall be good response at 
    4.0 kHz. When voice frequency repeaters are in the circuit there will 
    be some frequency weighting in the build-out network and the loss at 
    the higher frequencies will be greater than for nonrepeatered loops.
        (H) For nonloaded subscriber loops, the 1 kHz loss shall be 
    approximately 0.9 dB per 100 ohms of measured dc loop resistance. 
    Testing shall also be conducted to verify that the loss is 
    approximately a straight line function with no abrupt changes. The 3 
    kHz loss should be approximately 70% higher than the 1 kHz loss.
        (ii) Noise. The principal objective related to circuit noise 
    (noise-metallic) and the acceptance of new plant is that circuit noise 
    levels be 20 dBrnc or less (decibels above reference noise, C-message 
    weighted (a weighting derived from listening tests, to indicate the 
    relative annoyance or speech impairment by an interfering signal of 
    frequency (f) as heard through a ``500-type'' telephone set)). For most 
    new, properly installed, plant construction, circuit noise will usually 
    be considerably less than 20 dBrnc unless there are unusually long 
    sections of telephone plant in parallel with electric power facilities 
    and/or power influence of paralleling electric facilities is abnormally 
    high. When circuit noise is
    
    [[Page 23978]]
    
    20 dBrnc or less, the loop plant shall be considered acceptable. When 
    measured circuit noise is greater than 20 dBrnc, loop plant shall still 
    be considered acceptable providing circuit balance (power influence 
    reading minus circuit noise readings) is 60 dB or greater and power 
    influence readings are 85 dBrnc or greater. When circuit noise is 
    greater than 20 dBrnc and circuit balance is less than 60 dB and/or 
    power influence is less than 85 dBrnc, loop plant shall not be 
    considered acceptable and the loop plant shall be remedied to make 
    circuit balance equal to or greater than 60 dB.
        (7) Data record. Measurement data shall be recorded. A suggested 
    format similar to Format I for subscriber loops in Sec. 1755.407 or a 
    format specified in the applicable construction contract may be used.
        (8) Probable causes for nonconformance.--(i) Insertion loss. Some 
    of the more common causes for failing to obtain the desired results may 
    be due to reversed load coil windings, missing load coils, bridge taps 
    between load coils, load coil spacing irregularities, excessive end 
    sections, cables having high or low mutual capacitance, load coils 
    having the wrong inductance, load coils inadvertently installed in 
    nonloaded loops, moisture or water in cable, split pairs, and 
    improperly spliced connections. The above factors can occur singularly 
    or in combination. Experience to date indicates that the most common 
    problems are missing load coils, reversed load coil windings or bridge 
    taps.
        (ii) Noise. Some of the common causes for failing to obtain the 
    desired results may be due to high power influence from paralleling 
    electrical power systems, poor telephone circuit balance, discontinuous 
    cable shields, inadequate bonding and grounding of cable shields, high 
    capacitance unbalance-to-ground of the cable pairs, high dc loop 
    resistance unbalance, dc loop current less than 20 milliamperes, etc. 
    The above factors can occur singularly or in combination. See TE&CM 
    Section 451, Telephone Noise Measurement and Mitigation, for steps to 
    be taken in reducing telecommunications line noise.
        (f) One-person open circuit measurement (subscriber loops). (1) 
    When specified by the borrower, open circuit measurements shall be made 
    on all loaded and nonloaded subscriber loops upon completion of the 
    cable work to verify that the plant is free from major impedance 
    irregularities.
        (2) For loaded loops, open circuit measurements shall be made using 
    one of the following methods:
        (i) Impedance or pulse return pattern, with cable pair trace 
    compared to that of an artificial line of the same length and gauge. 
    For best results, a level tracer or fault locator with dual trace 
    capability is required;
        (ii) Return loss using a level tracer, with cable pair compared to 
    an artificial line of the same length and gauge connected in lieu of a 
    Precision Balance Network (PBN). This method can be made with level 
    tracers having only single trace capability; or
        (iii) Open circuit structural return loss using a level tracer. 
    This method can be made with level tracer having only single trace 
    capability.
        (3) Of the three methods suggested for loaded loops, the method 
    specified in paragraph (f)(2)(ii) of this section is the preferred 
    method because it can yield both qualitative and quantitative results. 
    The methods specified in paragraphs (f)(2)(i) and (f)(2)(iii) of this 
    section can be used as trouble shooting tools should irregularities be 
    found during testing.
        (4) For nonloaded loops, open circuit measurements shall be made 
    using the method specified in paragraph (f)(2)(i) of this section.
        (5) Method of measurement. Open circuit measurements shall be made 
    at the CO on each loaded and nonloaded pair across the tip and ring 
    terminals of the pair under test. All CO equipment shall be 
    disconnected at the MDF for this test. For loaded loops containing 
    voice frequency repeaters installed in the CO or field mounted, the 
    open circuit measurement shall be made after the repeaters have been 
    disconnected. Where field mounted repeaters are used, the open circuit 
    measurement shall be made at the repeater location in both directions.
        (i) Impedance or pulse return pattern. The step-by-step measurement 
    procedure using the impedance or pulse return pattern for loaded and 
    nonloaded loops shall be as shown in Figure 8. An artificial line of 
    the same makeup as the cable to be tested shall be set up. The traces 
    of the impedance or pulse return pattern from the cable pair and the 
    artificial line shall be compared and should be essentially identical. 
    If the impedance or pulse return traces from the cable pair are 
    different than the artificial line trace, cable faults are possible. 
    When the cable pair trace indicates possible defects, the defects 
    should be identified and located. One method of identifying and 
    locating defects involves introducing faults into the artificial line 
    until its trace is identical with the cable trace.
        (ii) Return loss balanced to artificial line. The step-by-step 
    measurement procedure using the return loss balanced to artificial line 
    for loaded loops shall be as shown in Figure 9. An artificial line of 
    the same makeup as the cable to be tested shall be set up. The 
    artificial line is connected to the external network terminals of the 
    test set. The cable pair under test is compared to this standard. When 
    defects are found, they should be identified and located by introducing 
    faults into the artificial line. This is more difficult than with the 
    method referenced in paragraph (f)(5)(i) of this section since this 
    measurement is more sensitive to minor faults and only a single trace 
    is used.
        (iii) Open circuit structural return loss using level tracer. The 
    step-by-step measurement procedure using the level tracer for loaded 
    loops shall be as shown in Figure 10. The cable pair is compared to a 
    PBN.
        (6) Test equipment. Equipment for performing these tests is shown 
    in Figures 8 through 10. For loaded loops, artificial loaded lines must 
    be of the same gauge and loading scheme as the line under test. For 
    nonloaded loops, artificial nonloaded lines must be of the same gauge 
    as the line under test. Artificial lines should be arranged using 
    switches or other quick connect arrangements to speed testing and 
    troubleshooting. Figures 8 through 10 are as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23979]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.030
    
    
    
    [[Page 23980]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.031
    
    
    
    [[Page 23981]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.032
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23982]]
    
        (7) Applicable results. (i) For loaded and nonloaded loops, the two 
    traces in the pulse return pattern or impedance method (paragraph 
    (f)(5)(i) of this section) shall be essentially identical. The degree 
    of comparison required of the two traces is to be determined by 
    experience.
        (ii) For loaded loops, results for return loss measurements using a 
    level tracer, with artificial line, in lieu of a PBN (paragraph 
    (f)(5)(ii) of this section) shall meet the following requirements:
        (A) For D66 and H88 loaded cables the structural return loss (SRL) 
    values shall range between 28 and 39 dB, respectively, at the critical 
    frequency of structural return loss (CFSRL) within the pass band of the 
    loading system being used. The minimum SRL value for uniform gauge 
    shall be 25 dB CFSRL. These SRL values apply for loaded cables of 
    uniform gauge for the entire length of the subscriber loop circuit. 
    Subscriber loop circuits shall meet the loading spacing deviations and 
    the cable mutual capacitance requirements in the applicable RUS cable 
    specifications;
        (B) For mixed gauge loaded cables the SRL values shall be 25 and 27 
    dB CFSRL, respectively, and the minimum SRL value shall be 22 dB CFSRL; 
    and
        (C) The two traces in the pulse return pattern should be 
    essentially identical. The degree of comparison required of the two 
    traces is determined by experience.
        (iii) For loaded loops, the results of open circuit structural 
    return loss measurements using a level tracer (paragraph (f)(5)(iii) of 
    this section) shall meet the following requirements. For D66 and H88 
    loaded cables with uniform or mixed gauges, the worst value allowed for 
    measured open circuit structural return loss between 1,000-3,500 Hz and 
    1,000-3,000 Hz, respectively, shall be approximately 0.9 dB (round 
    trip) for each 100 ohms outside plant dc loop resistance including the 
    resistance of the load coils. The value of 0.9 dB per 100 ohms for the 
    round trip loss remains reasonably accurate as long as:
        (A) The subscriber end section of the loaded pair under test is 
    approximately 2,250 ft (685 m) for D66 loading or 3,000 ft (914 m) for 
    H88 loading in length; and
        (B) The one-way 1,000 Hz loss does not exceed 10 dB.
        (iv) For loaded loops, the measured value of open circuit 
    structural return loss can only be as accurate as the degree to which 
    the dc loop resistance of the loaded pair under test is known. Most 
    accurate results shall be obtained when the dc loop resistance is known 
    by actual measurements as described in paragraph (d) of this section. 
    Furthermore, where the dc loop resistance is measured at the same time 
    as the open circuit structural return loss, no correction for 
    temperature is needed because the loss is directly proportional to the 
    loop resistance. Where it is not practical to measure the dc loop 
    resistance, it shall be calculated and corrected for temperature as 
    specified in paragraph (d)(6)(ii) of this section. When measuring 
    existing plant, care shall be taken to verify the accuracy of the 
    records, if they are used for the calculation of the dc loop 
    resistance. For buried plant, the temperature correction shall be based 
    at the normal depth of the cable in the ground. (Temperature can be 
    measured by boring a hole to cable depth with a ground rod, placing a 
    thermometer in the ground at the cable depth, and taking and averaging 
    several readings during the course of the resistance measurements.) For 
    aerial cable it shall be based on the temperature inside the cable 
    sheath.
        (v) For loaded loops, the best correlation between the measured and 
    the expected results shall be obtained when the cable is of one gauge, 
    one size, and the far end section is approximately 2,250 ft (685 m) for 
    D66 loading or 3,000 ft (914 m) for H88 loading. Mixing gauges and 
    cable sizes will result in undesirable small reflections whose 
    frequency characteristics and magnitude cannot be accurately predicted. 
    In subscriber loop applications, cable gauge may be somewhat uniform 
    but the cable pair size most likely will not be uniform as cable pair 
    sizes taper off toward the customer access location and a downward 
    adjustment of 1 dB of the allowed value shall be acceptable. ``Long'' 
    end sections (as defined in TE&CM Section 424, ``Guideline for 
    Telecommunications Subscriber Loop Plant'') lower the expected value, a 
    further downward adjustment of 3 dB in the allowed value shall be 
    acceptable.
    
    [[Page 23983]]
    
        (vi) For loaded loops, the limiting factor when making open circuit 
    structural return loss measurements is when the 1,000 Hz one-way loss 
    of the loaded cable pair under test becomes 10 dB or greater; it 
    becomes difficult to detect the presence of irregularities beyond the 
    10 dB point on the loop. To overcome this difficulty, loaded loops 
    having a one-way loss at 1,000 Hz greater than 10 dB shall be opened at 
    some convenient point (such as a pedestal or ready access enclosure) 
    and loss measurements at the individual portions measuring less than 10 
    dB one-way shall be made separately. When field mounted voice frequency 
    repeaters are used, the measurement shall be made at the repeater 
    location in both directions.
        (8) Data record. (i) When performing a pulse return pattern or 
    impedance open circuit measurement on loaded and nonloaded loops, a 
    ``check mark'' indicating that the pair tests good or an ``X'' 
    indicating that the pair does not test good shall be recorded in the 
    SRL column. A suggested format similar to Format I for subscriber loops 
    in Sec. 1755.407 or a format specified in the applicable construction 
    contract may be used.
        (ii) When performing open circuit return loss measurements using 
    the return loss balanced to an artificial line or return loss using a 
    level tracer on loaded loops, the value of the poorest (lowest 
    numerical value) SRL and its frequency in the proper column between 
    1,000 and 3,500 Hz for D66 loading or between 1,000 and 3,000 Hz for 
    H88 loading shall be recorded. A suggested format similar to Format I 
    for subscriber loops in Sec. 1755.407 or a format specified in the 
    applicable construction contract may be used.
        (9) Probable causes for nonconformance. Some of the more common 
    causes for failing to obtain the desired results may be due to reversed 
    load coil windings, missing load coils, bridge taps between load coils, 
    load coil spacing irregularities, excessive end sections, cables having 
    high or low mutual capacitance, load coils inadvertently installed in 
    nonloaded loops, moisture or water in the cable, load coils having the 
    wrong inductance, split pairs, and improperly spliced connectors. The 
    above can occur singularly or in combination. Experience to date 
    indicates that the most common problems are missing load coils, 
    reversed load coil windings or bridge taps.
        (g) Cable insertion loss measurement (carrier frequencies). (1) 
    When specified by the borrower, carrier frequency insertion loss 
    measurements shall be made on cable pairs used for T1, T1C, and/or 
    station carrier systems. Carrier frequency insertion loss shall be made 
    on a minimum of three pairs. Select at least one pair near the outside 
    of the core unit layup. If the three measured pairs are within 10% of 
    the calculated loss in dB corrected for temperature, no further testing 
    is necessary. If any of the measured pairs of a section are not within 
    10% of the calculated loss in dB, all pairs in that section used for 
    carrier transmission shall be measured.
        (2) Method of measurement. The step-by-step method of measurement 
    shall be as shown in Figure 11.
        (3) Test equipment. The test equipment is shown in Figure 11 as 
    follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23984]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.033
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23985]]
    
        (4) Applicable results. (i) The highest frequency to be measured is 
    determined by the type of carrier system. For T1 type carrier, the 
    highest frequency is normally 772 kHz. For T1C type carrier, the 
    highest frequency is normally 1576 kHz. The highest frequency to be 
    measured for station carrier is 140 kHz.
        (ii) The measured insertion loss of the cable shall be within 
    10% of the calculated loss in dB when the loss is corrected 
    for temperature.
        (iii) The calculated insertion loss is computed as follows:
        (A) Multiply the length of each different gauge by the applicable 
    dB per unit length as shown in Table 7 or 8 as follows:
    
    
                   Table 7.--Cable Attenuation @ 68  deg.F (20  deg.C) Filled Cables--Solid Insulation              
    ----------------------------------------------------------------------------------------------------------------
                   Frequency (kHz)                              Attenuation dB/mile (dB/km) Gauge (AWG)             
    ----------------------------------------------------------------------------------------------------------------
                                                         19               22               24               26      
    ----------------------------------------------------------------------------------------------------------------
    10..........................................        2.8 (1.7)        4.8 (2.9)        6.4 (3.9)        8.5 (5.3)
    20..........................................        3.2 (2.0)        5.8 (3.6)        8.2 (5.1)       11.2 (6.9)
    40..........................................        3.6 (2.2)        6.5 (4.0)        9.6 (6.0)       13.9 (8.6)
    60..........................................        4.0 (2.5)        6.9 (4.2)       10.3 (6.4)       15.2 (9.4)
    80..........................................        4.5 (2.8)        7.3 (4.5)       10.7 (6.6)       16.0 (9.9)
    100.........................................        4.9 (3.0)        7.7 (4.7)       11.1 (6.8)      16.5 (10.2)
    112.........................................        5.2 (3.2)        8.0 (4.9)       11.3 (7.0)      16.8 (10.5)
    120.........................................        5.4 (3.3)        8.1 (5.0)       11.5 (7.1)      17.0 (10.6)
    140.........................................        5.8 (3.6)        8.6 (5.3)       11.9 (7.4)      17.4 (10.8)
    160.........................................        6.2 (3.8)        9.0 (5.6)       12.3 (7.6)      17.8 (11.1)
    180.........................................        6.6 (4.1)        9.5 (5.9)       12.7 (7.9)      18.2 (11.3)
    200.........................................        7.0 (4.3)       10.0 (6.2)       13.2 (8.2)      18.6 (11.5)
    300.........................................        8.7 (5.4)       12.2 (7.5)       15.4 (9.6)      20.6 (12.8)
    400.........................................       10.0 (6.2)       14.1 (8.8)      17.7 (11.0)      22.9 (14.2)
    500.........................................       11.2 (6.9)       15.9 (9.8)      19.8 (12.3)      25.2 (15.6)
    600.........................................       12.2 (7.5)      17.5 (10.9)      21.8 (13.6)      27.4 (17.0)
    700.........................................       13.2 (8.2)      19.0 (11.8)      23.6 (14.7)      29.6 (18.4)
    772.........................................       13.8 (8.5)      19.9 (12.4)      24.8 (15.4)      31.4 (19.5)
    800.........................................       14.2 (8.8)      20.1 (12.5)      27.4 (17.1)      31.7 (19.7)
    900.........................................       14.8 (9.2)      21.6 (13.4)      29.0 (18.0)      33.8 (21.0)
    1000........................................       15.8 (9.8)      22.7 (14.1)      31.1 (19.3)      35.9 (22.3)
    1100........................................      16.4 (10.2)      23.8 (14.8)      32.7 (20.3)      38.0 (23.6)
    1200........................................      17.4 (10.8)      24.8 (15.4)      34.3 (21.3)      40.0 (24.9)
    1300........................................      17.9 (11.1)      25.9 (16.1)      35.4 (22.0)      41.7 (25.9)
    1400........................................      19.0 (11.8)      26.9 (16.7)      37.0 (23.0)      43.3 (26.9)
    1500........................................      19.5 (12.1)      28.0 (17.4)      38.0 (23.6)      44.3 (27.6)
    1576........................................      20.1 (12.4)      29.0 (18.0)      39.0 (24.3)      44.4 (28.2)
    ----------------------------------------------------------------------------------------------------------------
    
    
                 Table 8.--Cable Attenuation @ 68  deg.F (20  deg.C) Filled Cables--Expanded Insulation             
    ----------------------------------------------------------------------------------------------------------------
                                                                Attenuation dB/mile (dB/km) Gauge (AWG)             
                   Frequency (kHz)               -------------------------------------------------------------------
                                                         19               22               24               26      
    ----------------------------------------------------------------------------------------------------------------
    10..........................................        3.0 (1.8)        4.9 (3.0)        6.5 (4.0)        8.6 (5.3)
    20..........................................        3.5 (2.1)        6.0 (4.1)        8.5 (5.2)       11.5 (7.1)
    40..........................................        4.0 (2.5)        7.0 (4.3)       10.2 (6.3)       14.4 (8.9)
    60..........................................        4.5 (2.8)        7.5 (4.6)       11.1 (6.8)       16.0 (9.9)
    80..........................................        5.2 (3.3)        7.9 (4.9)       11.3 (6.9)      16.2 (10.1)
    100.........................................        5.8 (3.6)        8.4 (5.2)       11.6 (7.2)      16.4 (10.2)
    112.........................................        6.0 (3.8)        8.8 (5.4)       11.9 (7.4)      16.6 (10.3)
    120.........................................        6.2 (3.9)        9.0 (5.6)       12.1 (7.5)      16.9 (10.5)
    140.........................................        6.6 (4.1)        9.5 (5.9)       12.7 (7.9)      17.2 (10.7)
    160.........................................        6.9 (4.3)       10.0 (6.2)       13.2 (8.2)      17.4 (10.8)
    180.........................................        7.4 (4.6)       10.6 (6.6)       13.7 (8.5)      17.9 (11.1)
    200.........................................        7.9 (4.9)       11.1 (6.9)       14.2 (8.8)      18.5 (11.5)
    300.........................................        9.5 (5.9)       13.2 (8.2)      16.8 (10.5)      21.6 (13.4)
    400.........................................       11.1 (6.9)       15.3 (9.5)      19.5 (12.1)      24.3 (15.1)
    500.........................................       12.1 (7.5)      17.9 (11.1)      22.2 (13.8)      27.4 (17.1)
    600.........................................       13.7 (8.5)      19.5 (12.1)      24.3 (15.1)      29.6 (18.4)
    700.........................................       14.8 (9.2)      21.1 (13.1)      26.4 (16.4)      32.2 (20.0)
    772.........................................       15.3 (9.5)      21.6 (13.4)      27.4 (17.1)     33.8 (21.90)
    800.........................................       15.8 (9.8)      22.2 (13.8)      28.0 (17.4)      34.4 (21.3)
    900.........................................      17.0 (10.5)      23.8 (14.8)      29.6 (18.4)      36.4 (22.6)
    1000........................................      17.4 (10.8)      24.8 (15.4)      31.1 (19.3)      38.5 (23.9)
    1100........................................      17.9 (11.1)      26.4 (16.4)      33.3 (20.7)      40.6 (25.3)
    1200........................................      19.0 (11.8)       27.4 (17.1      34.3 (21.3)      42.2 (26.2)
    1300........................................      19.5 (12.1)      28.5 (17.7)      35.9 (22.3)      43.8 (27.2)
    1400........................................       20.1 (12.5      29.6 (18.4)      37.0 (23.0)      45.9 (28.5)
    1500........................................      20.6 (12.8)      30.6 (19.0)      38.5 (23.9)      47.5 (29.5)
    1576........................................      21.6 (13.4)      31.1 (19.3)      39.1 (24.3)      48.6 (30.2)
    ----------------------------------------------------------------------------------------------------------------
    
    
    [[Page 23986]]
    
        (B) Add the individual losses for each gauge to give the total 
    calculated insertion loss at a temperature of 68 deg.F (20 deg.C);
        (C) Correct the total calculated insertion loss at the temperature 
    of 68 deg.F (20 deg.C) to the measurement temperature by the following 
    formulae:
        At = A68 x [1 + 0.0012 x (t -- 68)] for 
    English Units
        At = A20 x [1 + 0.0022 x (t--20)] for Metric 
    Units
    Where:
        At = Insertion loss at the measurement temperature in 
    dB.
        A68 = Insertion loss at a temperature of 68 deg.F in dB.
        A20 = Insertion loss at a temperature of 20 deg.C in dB.
        t = Measurement temperature in  deg.F or ( deg.C); and
        (D) Compare the calculated insertion loss at the measurement 
    temperature to the measured insertion loss to determine compliance with 
    the requirement specified in paragraph (g)(4)(ii) of this section. 
    (Note: Attenuation varies directly with temperature. For each 
    10 deg.F (5.6 deg.C) change in temperature increase or 
    decrease the attenuation by 1%.)
        (iv) If the measured value exceeds the 10% allowable 
    variation, the cause shall be determined and corrective action shall be 
    taken to remedy the problem.
        (5) Data record. Results of carrier frequency insertion loss 
    measurements for station, T1, and/or T1C type carrier shall be 
    recorded. Suggested formats similar to Format III, Outside Plant 
    Acceptance Tests--T1 or T1C Carrier Pairs, and Format IV, Outside Plant 
    Acceptance Tests--Station Carrier Pairs, in Sec. 1755.407 or formats 
    specified in the applicable construction contract may be used.
        (6) Probable causes for nonconformance. If the measured loss is 
    low, the cable records are likely to be in error. If the measured loss 
    is high, there may be bridge taps, load coils or voice frequency build-
    out capacitors connected to the cable pairs or the cable records may be 
    in error. Figures 12 and 13 are examples that show the effects of 
    bridge taps and load coils in the carrier path. Figures 12 and 13 are 
    as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23987]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.034
    
    
    
    [[Page 23988]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.035
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23989]]
    
    Sec. 1755.404  Fiber optic cable telecommunications plant measurements.
    
        (a) Armor continuity. (1) Tests and measurements shall be made to 
    ensure that the armor of fiber optic cables is continuous. There are 
    two areas of concern. The first is armor bonding within a splice and 
    the second is armor continuity between splices.
        (2) Measurement techniques outlined here for verification of armor 
    continuity are applicable to buried fiber optic cable plant. 
    Measurements of armor continuity between splices in aerial, armored, 
    fiber optic cable should be made prior to completion of splicing. 
    Conclusive results cannot be obtained on aerial plant after all bonds 
    have been completed to the supporting strand, multigrounded neutral, 
    etc.
        (3) Method of measurement. Armor continuity within splices shall be 
    measured with a cable shield splice continuity test set. The step-by-
    step measurement procedure outlined in the manufacturer's operating 
    instructions for the specific test equipment being used shall be 
    followed.
        (4) Test equipment. A cable shield splice continuity tester shall 
    be used to measure armor continuity within splices.
        (5) Applicable results. When utilizing shield continuity testers to 
    measure armor continuity within splices, refer to the manufacturer's 
    published information covering the specific test equipment to be used 
    and for anticipated results.
        (6) Data record. Measurement data from armor continuity tests shall 
    be recorded together with anticipated values in an appropriate format 
    to permit comparison. The recorded data shall include specific 
    location, cable size, and cable type, if known, etc.
        (7) Probable causes for nonconformance. Among probable causes for 
    nonconformance are broken or damaged armors, bad bonding harnesses, 
    poorly connected bonding clamps, loose bonding lugs, etc.
        (b) Fiber optic splice loss measurement. (1) After placement of all 
    fiber optic cable plant has been completed and spliced together to form 
    a continuous optical link between end termination points, splice loss 
    measurements shall be performed on all field and central office splice 
    points.
        (2) Method of measurement. (i) Field splice loss measurements shall 
    be made between the end termination points at 1310 and/or 1550 
    nanometers for single mode fibers and in accordance with Figure 14. Two 
    splice loss measurements shall be made between the end termination 
    points. The first measurement shall be from termination point A to 
    termination point B. The second measurement shall be from termination 
    point B to termination point A.
        (ii) CO splice loss measurements shall be made at 1310 and/or 1550 
    nanometers for single mode fibers and in accordance with Figure 15. Two 
    splice loss measurements shall be made between the end termination 
    points. The first measurement shall be from termination point A to 
    termination point B. The second measurement shall be from termination 
    point B to termination point A.
        (3) Test equipment. The test equipment is shown in Figures 14 and 
    15. The optical time domain reflectometer (OTDR) used for the testing 
    should have dual wave length capability. Figures 14 and 15 are as 
    follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23990]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.036
    
    
    
    [[Page 23991]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.037
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23992]]
    
        (4) Applicable results. (i) The splice loss for each single mode 
    field splice shall be the bi-directional average of the two OTDR 
    readings. To calculate the actual splice loss, substitute the OTDR 
    readings maintaining the sign of the loss (+) or apparent gain (-) into 
    the following equation:
    [GRAPHIC] [TIFF OMITTED] TR02MY97.021
    
        (ii) When specified in the applicable construction contract, the 
    splice loss of each field splice at 1310 and/or 1550 nanometers shall 
    not exceed the limit specified in the contract.
        (iii) When no limit is specified in the applicable construction 
    contract, the splice loss of each field splice shall not exceed 0.2 dB 
    at 1310 and/or 1550 nanometers.
        (iv) The splice loss for each single mode CO splice shall be the 
    bi-directional average of the two OTDR reading. To calculate actual 
    splice loss, substitute the OTDR reading, maintaining the sign of the 
    loss (+) or apparent gain (-), into the equation specified in paragraph 
    (b)(4)(i) of this section.
        (v) When specified in the applicable construction contract, the 
    splice loss of each central office splice at 1310 and/or 1550 
    nanometers shall not exceed the limit specified in the contract.
        (vi) When no limit is specified in the applicable construction 
    contract, the splice loss of each central office splice shall not 
    exceed 1.2 dB at 1310 and/or 1550 nanometers.
        (5) Data record. The measurement data shall be recorded. A 
    suggested format similar to Format V, Outside Plant Acceptance Test--
    Fiber Optic Telecommunications Plant, in Sec. 1755.407 or a format 
    specified in the applicable construction contract may be used.
        (6) Probable causes for nonconformance. When the results of the 
    splice loss measurements exceed the specified limits the following 
    factors should be checked:
        (i) Proper end preparation of the fibers;
        (ii) End separation between the fiber ends;
        (iii) Lateral misalignment of fiber cores;
        (iv) Angular misalignment of fiber cores;
        (v) Fresnel reflection;
        (vi) Contamination between fiber ends;
        (vii) Core deformation; or
        (viii) Mode-field diameter mismatch.
        (c) End-to-end attenuation measurement. (1) After placement of all 
    fiber optic cable plant has been completed and spliced together to form 
    a continuous optical link between end termination points, end-to-end 
    attenuation measurements shall be performed on each optical fiber 
    within the cable.
        (2) Method of measurement. For single mode fibers, the end-to-end 
    attenuation measurements of each optical fiber at 1310 and/or 1550 
    nanometers in each direction between end termination points shall be 
    performed in accordance with Figure 16.
        (3) Test equipment. The test equipment is shown in Figure 16 as 
    follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23993]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.038
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23994]]
    
        (4) Applicable results. The end-to-end attenuation of each single 
    mode optical fiber at 1310 and/or 1550 nanometers shall not exceed the 
    limits specified in the applicable construction contract.
        (5) Data record. The measurement data shall be recorded. A 
    suggested format similar to Format V for fiber optic telecommunications 
    plant in Sec. 1755.407 or on a format specified in the applicable 
    construction contract may be used.
        (6) Probable causes for nonconformance. Failure of each optical 
    fiber to meet the end-to-end attenuation limit could be attributed to 
    the following:
        (i) Excessive field or central office splice loss;
        (ii) Excessive cable attenuation; or
        (iii) Damage to the fiber optic cable during installation.
        (d) End-to-end fiber signature measurement. (1) After placement of 
    all fiber optic cable plant has been completed and spliced together to 
    form a continuous optical link between end termination points, end-to-
    end fiber signature testing shall be performed on each optical fiber 
    within the cable.
        (2) Method of measurement. For single mode fibers, the end-to-end 
    fiber signature measurement of each optical fiber in each direction 
    shall be performed between end termination points at 1310 and/or 1550 
    nanometers in accordance with Figure 17.
        (3) Test equipment. The test equipment is shown in Figure 17 as 
    follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23995]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.039
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 23996]]
    
        (4) Applicable results. The appearance of each optical fiber 
    between end termination points.
        (5) Data record. Plot the trace of each optical fiber and retain as 
    a permanent record for future comparison if needed.
        (6) Probable causes for nonconformance. None.
    
    
    Sec. 1755.405  Voiceband data transmission measurements.
    
        (a) The data transmission measurements listed in this section shall 
    be used to determine the acceptability of trunk and nonloaded 
    subscriber loop circuits for data modem transmission.
        (b) Signal-to-C notched noise (S/CNN) measurement. (1) When 
    specified by the borrower, S/CNN measurements shall be made on trunk 
    circuits and nonloaded subscriber loops. For trunk circuits, the 
    measurement shall be made between CO locations. For nonloaded 
    subscriber loops, the measurement shall be made from the CO to the 
    station protector of the NID at the customer's access location.
        (2) S/CNN is the logarithmic ratio expressed in dB of a 1,004 Hz 
    holding tone signal compared to the C-message weighted noise level. S/
    CNN is one of the most important transmission parameters affecting the 
    performance of data transmission because proper modem operation 
    requires low noise relative to received power level. Since modulated 
    carriers are used in data communication systems, noise measurements 
    need to be performed with power on the connection to activate equipment 
    having signal-level-dependent noise sources. For 4 kHz channels, a 
    1,004 Hz holding tone is used to activate the signal-dependent 
    equipment on the channel or connection.
        (3) Method of measurement. The S/CNN measurement shall be made 
    using a 1,004 Hz holding tone at -13 dBm0 (decibels relative to one 
    milliwatt, referred to a zero transmission level point) and performed 
    in accordance with American National Standards Institute (ANSI) T1.506-
    1990, American National Standard for Telecommunications--Network 
    Performance--Transmission Specifications for Switched Exchange Access 
    Network including supplement ANSI T1.506a-1992, and American National 
    Standards Institute/Institute of Electrical and Electronics Engineers 
    (ANSI/IEEE) 743-1984, IEEE Standard Methods and Equipment for Measuring 
    the Transmission Characteristics of Analog Voice Frequency Circuits. 
    The ANSI T1.506-1990, American National Standard for 
    Telecommunications--Network Performance--Transmission Specifications 
    for Switched Exchange Access Network is incorporated by reference in 
    accordance with 5 U.S.C. 522(a) and 1 CFR part 51. Copies of ANSI 
    T1.506-1990 are available for inspection during normal business hours 
    at RUS, room 2845, U.S. Department of Agriculture, STOP 1598, 
    Washington, DC 20250-1598 or at the Office of the Federal Register, 800 
    North Capitol Street, NW., suite 700, Washington, DC. Copies are 
    available from ANSI, Customer Service, 11 West 42nd Street, New York, 
    New York 10036, telephone number (212) 642-4900. The ANSI/IEEE 743-
    1984, IEEE Standard Methods and Equipment for Measuring the 
    Transmission Characteristics of Analog Voice Frequency Circuits is 
    incorporated by reference in accordance with 5 U.S.C. 522(a) and 1 CFR 
    part 51. Copies of ANSI/IEEE 743-1984 are available for inspection 
    during normal business hours at RUS, room 2845, U.S. Department of 
    Agriculture, STOP 1598, Washington, DC 20250-1598 or at the Office of 
    the Federal Register, 800 North Capitol Street, NW., suite 700, 
    Washington, DC. Copies are available from ANSI, Customer Service, 11 
    West 42nd Street, New York, New York 10036, telephone number (212) 642-
    4900.
        (4) Test equipment. The equipment for performing the measurement 
    shall be in accordance with ANSI/IEEE 743-1984.
        (5) Applicable results. The S/CNN for both trunk and nonloaded 
    subscriber loop circuits shall not be less than 31 dB.
        (6) Data record. The measurement data shall be recorded. Suggested 
    formats similar to Format VI, Voiceband Data Transmission Tests--
    Nonloaded Subscriber Loops, and Format VII, Voiceband Data Transmission 
    Tests--Trunk Circuits, in Sec. 1755.407 or formats specified in the 
    applicable construction contract may be used.
        (7) Probable causes for nonconformance. Some of the causes for 
    failing to obtain the desired results may be due to excessive harmonic 
    distortion, quantizing noise, phase and amplitude jitter, and loss in 
    digital pads used for level settings.
        (c) Signal-to-intermodulation distortion (S/IMD) measurement. (1) 
    When specified by the borrower, S/IMD measurements shall be made on 
    trunk circuits and nonloaded subscriber loops. For trunk circuits, the 
    measurement shall be made between CO locations. For nonloaded 
    subscriber loops, the measurement shall be made from the CO to the 
    station protector of the NID at the customer's access location.
        (2) S/IMD is a measure of the distortion produced by extraneous 
    frequency cross products, known as intermodulation products, when a 
    multi-tone tone signal is applied to a system.
        (3) Intermodulation distortion (IMD) is caused by system 
    nonlinearities acting upon the harmonic frequencies produced from an 
    input of multiple tones. The products resulting from IMD can be more 
    damaging than noise in terms of producing data transmission errors.
        (4) IMD is measured as a signal to distortion ratio and is 
    expressed as the logarithmic ratio in dB of the composite power of four 
    resulting test frequencies to the total power of specific higher order 
    distortion products that are produced. The higher order products are 
    measured at both the 2nd order and 3rd order and are designated R2 and 
    R3, respectively. The four frequency testing for IMD is produced with 
    four tones of 857, 863, 1,372, and 1,388 Hz input at a composite power 
    level of -13 dBm0.
        (5) Method of measurement. The S/IMD measurement shall be performed 
    in accordance with ANSI T1.506-1990 and ANSI/IEEE 743-1984.
        (6) Test equipment. The equipment for performing the measurement 
    shall be in accordance with ANSI/IEEE 743-1984.
        (7) Applicable results. The 2nd order (R2) S/IMD for both trunk and 
    nonloaded subscriber loop circuits shall not be less than 40 dB. The 
    3rd order (R3) S/IMD for both trunk and nonloaded subscriber loop 
    circuits shall not be less than 40 dB.
        (8) Data record. The measurement data shall be recorded. Suggested 
    formats similar to Format VI for nonloaded subscriber loops and Format 
    VII for trunk circuits in Sec. 1755.407 or formats specified in the 
    applicable construction contract may be used.
        (9) Probable causes for nonconformance. Some of the causes for 
    failing to obtain the desired results may be due to channel 
    nonlinearities, such as compression and clipping, which cause harmonic 
    and intermodulation distortion in a voiceband signal.
        (d) Envelope delay distortion (EDD) measurement. (1) When specified 
    by the borrower, EDD measurements shall be made on trunk circuits and 
    nonloaded subscriber loops. For trunk circuits, the measurement shall 
    be made between CO locations. For nonloaded subscriber loops, the 
    measurement shall be made from the CO to the station protector of the 
    NID at the customer's access location.
    
    [[Page 23997]]
    
        (2) EDD is a measure of the linearity or uniformity of the phase 
    versus frequency characteristics of a transmission facility. EDD is 
    also known as relative envelope delay (RED).
        (3) EDD is specifically defined as the delay relative to the 
    envelope delay at the reference frequency of 1,704 Hz. EDD is typically 
    measured at two frequencies, one low and one high in the voiceband. The 
    low frequency measurement is made at 604 Hz. The high frequency 
    measurement is made at 2,804 Hz.
        (4) Method of measurement. The EDD measurement shall be performed 
    in accordance with ANSI T1.506-1990 and ANSI/IEEE 743-1984.
        (5) Test equipment. The equipment for performing the measurement 
    shall be in accordance with ANSI/IEEE 743-1984.
        (6) Applicable results. The EDD for both trunk and nonloaded 
    subscriber loop circuits at the low frequency of 604 Hz shall not 
    exceed 1,500 microseconds. The EDD for both trunk and nonloaded 
    subscriber loop circuits at the high frequency of 2,804 Hz shall not 
    exceed 1,000 microseconds.
        (7) Data record. The measurement data shall be recorded. Suggested 
    formats similar to Format VI for nonloaded subscriber loops and Format 
    VII for trunk circuits in Sec. 1755.407 or formats specified in the 
    applicable construction contract may be used.
        (8) Probable causes for nonconformance. Some of the causes for 
    failing to obtain the desired results may be due to nonlinearity of the 
    phase versus frequency characteristic of the transmission facility. 
    This nonlinear phase versus frequency characteristic of the 
    transmission facility causes the various frequency components to travel 
    at different transit times which results in successively transmitted 
    data pulses to overlap at the receive end. The overlapping of the 
    pulses at the receive end results in distortion of the received signal. 
    Excessive EDD on the transmission facility may be reduced using data 
    modems with equalization or by conditioning the transmission line.
        (e) Amplitude jitter (AJ) measurement. (1) When specified by the 
    borrower, AJ measurements shall be made on trunk circuits and nonloaded 
    subscriber loops. For trunk circuits, the measurement shall be made 
    between CO locations. For nonloaded subscriber loops, the measurement 
    shall be made from the CO to the station protector of the NID at the 
    customer's access location.
        (2) AJ is any fluctuation in the peak amplitude value of a fixed 
    tone signal at 1,004 Hz from its nominal value. AJ is expressed in peak 
    percent amplitude modulation.
        (3) AJ is measured in two separate frequency bands, 4-300 Hz and 
    20--300 Hz. The 4--300 Hz band is important for modems employing echo 
    canceling capabilities. The 20-300 Hz band is used for modems that do 
    not employ echo cancelers.
        (4) Amplitude modulation can affect the error performance of 
    voiceband data modems. The measurement of amplitude jitter indicates 
    the total effect on the amplitude of the holding tone of incidental 
    amplitude modulation and other sources including quantizing and message 
    noise, impulse noise, gain hits, phase jitter, and additive tones such 
    as single-frequency interference.
        (5) Method of measurement. The AJ measurement shall be performed in 
    accordance with ANSI T1.506-1990 and ANSI/IEEE 743-1984.
        (6) Test equipment. The equipment for performing the measurement 
    shall be in accordance with ANSI/IEEE 743-1984.
        (7) Applicable results. The AJ for both trunk and nonloaded 
    subscriber loop circuits in the 4--300 Hz frequency band shall not 
    exceed 6%. The AJ for both trunk and nonloaded subscriber loop circuits 
    in the 20--300 Hz frequency band shall not exceed 5%.
        (8) Data record. The measurement data shall be recorded. Suggested 
    formats similar to Format VI for nonloaded subscriber loops and Format 
    VII for trunk circuits in Sec. 1755.407 or formats specified in the 
    applicable construction contract may be used.
        (9) Probable causes for nonconformance. Some of the causes for 
    failing to obtain the desired results may be due to excessive S/CNN, 
    impulse noise, and phase jitter.
        (f) Phase jitter (PJ) measurement. (1) When specified by the 
    borrower, PJ measurements shall be made on trunk circuits and nonloaded 
    subscriber loops. For trunk circuits, the measurement shall be made 
    between CO locations. For nonloaded subscriber loops, the measurement 
    shall be made from the CO to the station protector of the NID at the 
    customer's access location.
        (2) PJ is any fluctuation in the zero crossings of a fixed tone 
    signal (usually 1,004 Hz) from their nominal position in time within 
    the voiceband. PJ is expressed in terms of either degrees peak-to-peak 
    ( deg.p-p) or in terms of a Unit Interval (UI). One UI is equal to 
    360 deg. p-p.
        (3) PJ measurements are typically performed in two nominal 
    frequency bands. The frequency bands are 20-300 Hz band and either the 
    2-300 Hz band or the 4-300 Hz band. The 20-300 Hz band is important to 
    all phase-detecting modems. The 4-300 Hz band or the 2-300 Hz band is 
    important for modems employing echo canceling capabilities.
        (4) Phase jitter can affect the error performance of voiceband data 
    modems that use phase detection techniques. The measurement of phase 
    jitter indicates the total effect on the holding tone of incidental 
    phase modulation and other sources including quantizing and message 
    noise, impulse noise, phase hits, additive tones such as single-
    frequency interference, and digital timing jitter.
        (5) Method of measurement. The PJ measurement shall be performed in 
    accordance with ANSI T1.506-1990 and ANSI/IEEE 743-1984.
        (6) Test equipment. The equipment for performing the measurement 
    shall be in accordance with ANSI/IEEE 743-1984.
        (7) Applicable results. The PJ for both trunk and nonloaded 
    subscriber loop circuits in the 4-300 Hz frequency band shall not 
    exceed 6.5 deg. p-p. The PJ for both trunk and nonloaded subscriber 
    loop circuits in the 20-300 Hz frequency band shall not exceed 
    10.0 deg. p-p.
        (8) Data record. The measurement data shall be recorded. Suggested 
    formats similar to Format VI for nonloaded subscriber loops and Format 
    VII for trunk circuits in Sec. 1755.407 or formats specified in the 
    applicable construction contract may be used.
        (9) Probable causes for nonconformance. Some of the causes for 
    failing to obtain the desired results may be due to excessive S/CNN, 
    impulse noise, and amplitude jitter.
        (g) Impulse noise measurement. (1) When specified by the borrower, 
    impulse noise measurements shall be made on trunk circuits and 
    nonloaded subscriber loops. For trunk circuits, the measurement shall 
    be made between CO locations. For nonloaded subscriber loops, the 
    measurement shall be made from the CO to the station protector of the 
    NID at the customer's access location.
        (2) Impulse noise is a measure of the presence of unusually large 
    noise excursions of short duration that are beyond the normal 
    background noise levels on a facility. Impulse noise is typically 
    measured by counting the number of occurrences beyond a particular 
    noise reference threshold in a given time interval. The noise reference 
    level is C-message weighted.
        (3) Method of measurement. The impulse noise measurement shall be 
    performed using a 1,004 Hz tone at -13 dBm0 and in accordance with ANSI 
    T1.506-1990 and ANSI/IEEE 743-1984.
    
    [[Page 23998]]
    
        (4) Test equipment. The equipment for performing the measurement 
    shall be in accordance with ANSI/IEEE 743-1984.
        (5) Applicable results. The impulse noise for both trunk and 
    nonloaded subscriber loop circuits shall not exceed 65 dBrnC0 (decibels 
    relative to one picowatt reference noise level, measured with C-message 
    frequency weighting, referred to a zero transmission level point). The 
    impulse noise requirement shall be based upon a maximum of 5 counts in 
    a 5 minute period at equal to or greater than the indicated noise 
    thresholds.
        (6) Data record. The measurement data shall be recorded. Suggested 
    formats similar to Format VI for nonloaded subscriber loops and Format 
    VII for trunk circuits in Sec. 1755.407 or formats specified in the 
    applicable construction contract may be used.
        (7) Probable causes for nonconformance. Some of the causes for 
    failing to obtain the desired results may be due to excessive transient 
    signals originating from the various switching operations.
    
    
    Sec. 1755.406  Shield or armor ground resistance measurements.
    
        (a) Shield or armor ground resistance measurements shall be made on 
    completed lengths of copper cable and wire plant and fiber optic cable 
    plant.
        (b) Method of measurement. (1) The shield or armor ground 
    resistance measurement shall be made between the copper cable and wire 
    shield and ground and between the fiber optic cable armor and ground, 
    respectively. The measurement shall be made either on cable and wire 
    lengths before splicing and before any ground connections are made to 
    the cable or wire shields or armors. Optionally, the measurement may be 
    made on cable and wire lengths after splicing, but all ground 
    connections must be removed from the section under test.
        (2) The method of measurement using either an insulation resistance 
    test set or a dc bridge type megohmmeter shall be as shown in Figure 18 
    as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 23999]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.040
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 24000]]
    
        (c) Test equipment. (1) The shield or armor ground resistance 
    measurements may be made using an insulation resistance test set, a dc 
    bridge type megohmmeter, or a commercially available fault locator.
        (2) The insulation resistance test set should have an output 
    voltage not to exceed 500 volts dc and may be hand cranked or battery 
    operated.
        (3) The dc bridge type megohmmeter, which may be ac powered, should 
    have scales and multipliers which make it possible to accurately read 
    resistance values of 50,000 ohms to 10 megohms. The voltage that is 
    applied to the shield or armor during the test should not be less than 
    ``250 volts dc'' nor greater than ``1,000 volts dc'' when using an 
    instrument having adjustable test voltage levels.
        (4) Commercially available fault locators may be used in lieu of 
    the above equipment, if the devices are capable of detecting faults 
    having resistance values of 50,000 ohms to 10 megohms. Operation of the 
    devices and method of locating the faults should be in accordance with 
    manufacturer's instructions.
        (d) Applicable results. (1) For all new copper cable and wire 
    facilities and all new fiber optic cable facilities, the shield or 
    armor ground resistance levels normally exceed 1 megohm-mile (1.6 
    megohm-km) at 68 deg.F (20 deg.C). A value of 100,000 ohm-mile (161,000 
    ohm-km) at 68 deg.F (20 deg.C) shall be the minimum acceptable value of 
    the shield or armor ground resistance.
        (2) Shield or armor ground resistance varies inversely with length 
    and temperature. In addition other factors which may affect readings 
    could be soil conditions, faulty test equipment and incorrect test 
    procedures.
        (3) For the resistance test method and dc bridge type megohmmeter, 
    the ohm-mile (ohm-km) value for the shield or armor ground resistance 
    shall be computed by multiplying the actual scale reading in ohms on 
    the test set by the length in miles (km) of the cable or wire under 
    test.
        (4)(i) The objective shield or armor ground resistance may be 
    determined by dividing 100,000 by the length in miles (161,000 by the 
    length in km) of the cable or wire under test. The resulting value is 
    the minimum acceptable meter scale reading in ohms. Examples for 
    paragraphs (d)(3) and (d)(4) of this section are as follows:
    
    Equation 1. Test Set: Scale Reading * Length = Resistance-Length
        75,000 ohms * 3 miles = 225,000 ohm-mile
        (75,000 ohms * 4.9 km = 367,000 ohm-km)
    Equation 2. 100,000 ohm-mile ' Length = Minimum Acceptable 
    Meter Scale Reading
        100,000 ohm-mile ' 3 miles = 33,333 ohms
        (161,000 ohm-km ' 4.9 km = 32,857 ohms)
    
        (ii) Since the 33,333 ohms (32,857 ohms) is the minimum acceptable 
    meter scale reading and the meter scale reading was 75,000 ohms, the 
    cable is considered to have met the 100,000 ohm-mile (161,000 ohm-km) 
    requirement.
        (5) Due to the differences between various jacketing materials used 
    in manufacturing cable or wire and to varying soil conditions, it is 
    impractical to provide simple factors to predict the magnitude of 
    variation in shield or armor to ground resistance due to temperature. 
    The variations can, however, be substantial for wide excursions in 
    temperature from the ambient temperature of 68 deg.F (20 deg.C).
        (e) Data record. The data shall be corrected to the length 
    requirement of ohm-mile (ohm-km) and a temperature of 68 deg.F 
    (20 deg.C) and shall be recorded on a form specified in the applicable 
    construction contract.
        (f) Probable causes for nonconformance. (1) When results of 
    resistance measurements are below the 100,000 ohm-mile (161,000 ohm-km) 
    requirement at 68 deg.F (20 deg.C), the jacket temperature, soil 
    conditions, test equipment and method shall be reviewed before the 
    cable or wire is considered a failure. If the temperature is 
    approximately 68 deg.F (20 deg.C) and soil conditions are acceptable, 
    and a reading of less than 100,000 ohm-mile (161,000 ohm-km) is 
    indicated, check the calibration of the equipment; as well as, the test 
    method. If the equipment was found to be out of calibration, 
    recalibrate the equipment and remeasure the cable or wire. If the 
    temperature was 86 deg.F (30 deg.C) or higher, the cable or wire shall 
    be remeasured at a time when the temperature is approximately 68 deg.F 
    (20 deg.C). If the test was performed in unusually wet soil, the cable 
    or wire shall be retested after the soil has reached normal conditions. 
    If after completion of the above steps, the resistance value of 100,000 
    ohm-mile (161,000 ohm-km) or greater is obtained, the cable or wire 
    shall be considered acceptable.
        (2) When the resistance value of the cable or wire is still found 
    to be below 100,000 ohm-mile (161,000 ohm-km) requirement after 
    completion of the steps listed in paragraph (f)(1) of this section, the 
    fault shall be isolated by performing shield or armor ground resistance 
    measurements on individual cable or wire sections.
        (3) Once the fault or faults have been isolated, the cable or wire 
    jacket shall be repaired in accordance with Sec. 1755.200, RUS Standard 
    for Splicing Copper and Fiber Optic Cables or the entire cable or wire 
    section may be replaced at the request of the borrower.
    
    
    Sec. 1755.407  Data formats.
    
        The following suggested formats listed in this section may be used 
    for recording the test data:
    
    BILLING CODE 3410-15-P
    
    [[Page 24001]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.041
    
    
    
    [[Page 24002]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.042
    
    
    
    [[Page 24003]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.043
    
    
    
    [[Page 24004]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.044
    
    
    
    [[Page 24005]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.045
    
    
    
    [[Page 24006]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.046
    
    
    
    [[Page 24007]]
    
    [GRAPHIC] [TIFF OMITTED] TR02MY97.047
    
    
    
    
    [[Page 24008]]
    
    
        Dated: April 24, 1997.
    Jill Long Thompson,
    Under Secretary, Rural Development.
    [FR Doc. 97-11316 Filed 5-1-97; 8:45 am]
    BILLING CODE 3410-15-C
    
    
    

Document Information

Published:
05/02/1997
Department:
Rural Utilities Service
Entry Type:
Rule
Action:
Final rule.
Document Number:
97-11316
Pages:
23958-24008 (51 pages)
PDF File:
97-11316.pdf
CFR: (11)
7 CFR 1755.406
7 CFR 1755.407
7 CFR 1755.97
7 CFR 1755.98
7 CFR 1755.400
More ...