2016-19227. Energy Conservation Program: Test Procedures for Central Air Conditioners and Heat Pumps; Correction
-
Start Preamble
Start Printed Page 55111
AGENCY:
Office of Energy Efficiency and Renewable Energy, Department of Energy.
ACTION:
Final rule; technical correction.
SUMMARY:
On June 8, 2016, the U.S. Department of Energy (DOE) published a final rule in the Federal Register that amended the test procedures for central air conditioners and heat pumps. This final rule corrects multiple editorial errors in that final rule.
DATES:
Effective Date: August 18, 2016.
Start Further InfoFOR FURTHER INFORMATION CONTACT:
Ms. Ashley Armstrong, U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, Building Technologies Office, EE-5B, 1000 Independence Avenue SW., Washington, DC 20585-0121. Telephone: (202) 586-6590. Email: Ashley.Armstrong@ee.doe.gov.
Ms. Johanna Jochum, U.S. Department of Energy, Office of the General Counsel, GC-33, 1000 Independence Avenue SW., Washington, DC 20585-0121. Telephone: (202) 287-6307. Email: Johanna.Jochum@hq.doe.gov.
End Further Info End Preamble Start Supplemental InformationSUPPLEMENTARY INFORMATION:
I. Background
On June 8, 2016, DOE's Office of Energy Efficiency and Renewable Energy published a test procedure final rule in the Federal Register titled, “Test Procedures for Central Air Conditioners and Heat Pumps” (“June 2016 final rule”). 81 FR 36992. Since the publication of that final rule, it has come to DOE's attention that, due to a technical oversight, certain portions of the regulatory text adopted in the June 2016 final rule for 10 CFR part 429 and appendix M to subpart B of 10 CFR part 430 (“appendix M”) contained editorial errors.
As part of that final rule, DOE amended 10 CFR 429.16, which addresses certification of central air conditioners and heat pumps, and 10 CFR 429.70, which addresses alternate efficiency determination methods. This correction addresses editorial errors in § 429.16(a)(1), (d)(1), (d)(2), and (e)(4). Specifically, at § 429.16(a)(1), DOE included a cross reference to paragraph (c)(2) that should have referred to paragraph (b)(2)(i). In § 429.16(d)(1) and (2), DOE mistakenly transposed the words “less” and “greater.” At § 429.16(e)(4), DOE erroneously referred to cubic feet per minute (cfm) instead of cubic feet per minute of standard air (scfm). At § 429.16(e)(4)(viii), DOE failed to remove regulatory text associated with changes to the test procedure for variable speed heat pumps not adopted in the June 2016 final rule that had been proposed on November 9, 2015 in a supplementary notice of proposed rulemaking (“November 2015 SNOPR”). 80 FR 69278. In order to remedy these errors, DOE is issuing this final rule correction to revise the text in these sections.
In addition, the June 2016 final rule revised appendix M to subpart B of 10 CFR part 430 (“appendix M”), which specifies the “Uniform Test Method for the Measurement the Energy Consumption of Central Air Conditioners and Heat Pumps.” This correction also addresses several editorial errors in appendix M.
In section 3.11.1 of appendix M, “If using the outdoor air enthalpy method as the secondary test method,” DOE erroneously numbered two subsections with the number “3.11.1.1.” The second of these two is renumbered to “3.11.1.2.”
In section 4.1 of appendix M, “Seasonal Energy Efficiency Ratio (SEER) Calculations,” DOE erroneously numbered subsection 4.1.3 as “4.1.2.3,” which propagated errors in numbering from that point through the end of section 4.1 and created erroneous cross-references to these sections. Section 4.1.2.3 is renumbered as section “4.1.3,” and the following section numbers through the end of section 4.1 are renumbered accordingly. Additionally, cross-references to the renumbered sections are revised.
Sections 2.11 and 3.19 of appendix M contain errors in the tolerance allowed between temperature measurements. The preamble to the June 2016 final rule states that the maximum allowable temperature difference is 2.0 °F and that it applies to the average measurements for the test period. 81 FR 36991, 37028 (June 8, 2016). In section 2.11, DOE erroneously referred to “maximum difference between readings” rather than adding the clarification discussed in the preamble that “readings” referred to the average temperatures measured during the test period. In section 3.1.9, DOE similarly failed to include the clarifying information on the tolerance and erroneously provided a tolerance of 1.5 °F rather than 2.0 °F. DOE is correcting section 2.11 accordingly and correcting 3.1.9 to refer directly to section 2.11 rather than correcting the provided tolerance.
Tables 8, 9, 15, 16, and 17 of appendix M contained various errors in testing tolerances for external resistance to airflow, airflow nozzle pressure difference, and electric voltage. In the preamble of the June 2016 Final Rule, DOE explained its intention to maintain the external resistance to airflow tolerance at 0.05 inches of water, to maintain the airflow nozzle pressure difference tolerance at 2.0%, and to maintain the electric voltage tolerance at 2.0%. 81 FR 36991, 37036 (June 8, 2016). However, this was not reflected in tables 8, 9, 15, 16 and 17 of appendix M, and the tables are revised to reflect these corrections.
In section 3.13.1.d of appendix M, P2x was erroneously printed instead of Px in two instances. This section provides instructions for measurement of the indoor unit low voltage power Px, which is later subtracted from the measurement of heating season total off mode power (P2x) for coil-only split systems and for blower coil split systems for which a furnace or a modular blower is the designated air mover. Instances of P2x in section 3.13.1.d of appendix M are revised to Px.
Finally, many of the instructions in the final rule that indicate that a default cyclic degradation coefficient is to be used if the tests to determine this value are not conducted, but erroneously did Start Printed Page 55112not specify that the default value is to be used if the value determined using the test exceeded the default value. 81 FR 36991, 37033 (June 8, 2016). DOE intended that the default value is to be used if the value determined using the test exceeds the default value for the cyclic degradation coefficient, and is correcting this omission in this final rule correction.
II. Need for Correction
As published, the adopted test procedure text may potentially result in confusion regarding how to correctly conduct DOE's central air conditioners and heat pumps test procedure.
Because this final rule would simply correct errors in the regulatory text without making substantive changes to the test procedures, the changes addressed in this document are technical in nature. Accordingly, DOE finds that there is good cause under 5 U.S.C. 553(b)(B) to not issue a separate notice to solicit public comment on the changes contained in this document. Issuing a separate notice to solicit public comment would be impracticable, unnecessary, and contrary to the public interest.
III. Procedural Requirements
DOE has concluded that the determinations made pursuant to the various procedural requirements applicable to the June 8, 2016 test procedure final rule remain unchanged for this final rule technical correction. These determinations are set forth in the June 8, 2016 final rule. 81 FR 36992.
Start List of SubjectsList of Subjects
10 CFR Part 429
- Administrative practice and procedure
- Confidential business information
- Energy conservation
- Reporting and recordkeeping requirements
10 CFR Part 430
- Administrative practice and procedure
- Confidential business information
- Energy conservation
- Energy conservation test procedures
- Household appliances
- Imports
- Incorporation by reference
- Intergovernmental relations
- Small businesses
Issued in Washington, DC, on August 5, 2016.
Kathleen Hogan,
Deputy Assistant Secretary for Energy Efficiency, Energy Efficiency and Renewable Energy.
For the reasons stated in the preamble, DOE amends parts 429 and 430 of chapter II of title 10, Code of Federal Regulations to read as follows:
Start PartPART 429—CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
End Part Start Amendment Part1. The authority citation for part 429 continues to read as follows:
End Amendment Part[Amended]2. Section 429.16 is amended:
End Amendment Part Start Amendment Parta. In paragraph (a)(1), in the last row of the table, by removing “(c)(2)” and adding in its place “(b)(2)(i)”;
End Amendment Part Start Amendment Partb. In paragraph (d)(1) by removing “less” and adding in its place “greater”;
End Amendment Part Start Amendment Partc. In paragraph (d)(2) by removing “greater” and adding in its place “less”;
End Amendment Part Start Amendment Partd. In paragraph (e)(4) by:
End Amendment Part Start Amendment Parti. Adding “of standard air” after “(in cubic feet per minute”;
End Amendment Part Start Amendment Partii. Removing the two instances of “(cfm)” and adding in its place “(scfm)”; and
End Amendment Part Start Amendment Partiii. Removing paragraph (viii).
End Amendment Part Start PartPART 430—ENERGY CONSERVATION PROGRAM FOR CONSUMER PRODUCTS
End Part Start Amendment Part3. The authority citation for part 430 continues to read as follows:
End Amendment Part Start Amendment Part4. Appendix M to subpart B of part 430 is amended by:
End Amendment Part Start Amendment Parta. In section 2.11.b(2), first paragraph, last sentence, removing “readings” and adding in its place “average temperatures measured during the test period”;
End Amendment Part Start Amendment Partb. Revising section 3.1.9;
End Amendment Part Start Amendment Partc. Revising section 3.2.1, introductory text;
End Amendment Part Start Amendment Partd. In section 3.2.3.d., adding a sentence after the first sentence;
End Amendment Part Start Amendment Parte. In section 3.3, paragraph d., revising Table 8;
End Amendment Part Start Amendment Partf. In section 3.5, paragraph h., revising Table 9 and its footnotes;
End Amendment Part Start Amendment Partg. In section 3.5.3, adding a sentence after the second sentence;
End Amendment Part Start Amendment Parth. Revising section 3.6.3.b., introductory text;
End Amendment Part Start Amendment Parti. In section 3.7, paragraph a., revising Table 15;
End Amendment Part Start Amendment Partj. In section 3.8.a., removing the sixth sentence;
End Amendment Part Start Amendment Partk. In section 3.8.1, adding a sentence after the third sentence and revising Table 16;
End Amendment Part Start Amendment Partl. In section 3.9, paragraph f., revising Table 17;
End Amendment Part Start Amendment Partm. In section 3.11, redesignating the second section 3.11.1.1 (“Official Test”) as section 3.11.1.2;
End Amendment Part Start Amendment Partn. In section 3.13.1.d, removing the two instances of “ P2x” and adding in their places “Px”;
End Amendment Part Start Amendment Parto. In section 4.1.1.b, adding a second sentence;
End Amendment Part Start Amendment Partp. In section 4.1.2.1.c, adding a second sentence;
End Amendment Part Start Amendment Partq. Redesignating sections 4.1.4.1 and 4.1.4.2 as sections 4.1.5.1 and 4.1.5.2, respectively;
End Amendment Part Start Amendment Partr. Redesignating section 4.1.4 as section 4.1.5;
End Amendment Part Start Amendment Parts. Redesignating sections 4.1.3.1, 4.1.3.2, and 4.1.3.3 as sections 4.1.4.1, 4.1.4.2, and 4.1.4.3, respectively;
End Amendment Part Start Amendment Partt. Redesignating section 4.1.3 as section 4.1.4;
End Amendment Part Start Amendment Partu. Redesignating section 4.1.2.7 as section 4.1.3.4;
End Amendment Part Start Amendment Partv. Redesignating section 4.1.2.6 as section 4.1.3.3;
End Amendment Part Start Amendment Partw. Redesignating section 4.1.2.5 as section 4.1.3.2;
End Amendment Part Start Amendment Partx. Redesignating section 4.1.2.4 as section 4.1.3.1;
End Amendment Part Start Amendment Party. Redesignating section 4.1.2.3 as section 4.1.3;
End Amendment Part Start Amendment Partz. In newly redesignated section 4.1.3.1, revising the equation and related information immediately before Table 18;
End Amendment Part Start Amendment Partaa. In newly redesignated section 4.1.4.1, adding a sentence after the last sentence of the section;
End Amendment Part Start Amendment Partbb. In section 4.2.1, adding the sentence “Evaluate the heating mode cyclic degradation factor ĊDh as specified in section 3.8.1 of this appendix.”, after “Use Equation 4.2-2 to determine BL(Tj). Obtain fractional bin hours for the heating season, nj/N, from Table 19.”; and
End Amendment Part Start Amendment Partcc. In section 4.2.3.1, adding the sentence “Evaluate the heating mode cyclic degradation factor CDh as specified in section 3.8.1 of this appendix.”, after “δ′(Tj) = the low temperature cutoff factor, dimensionless.”;
End Amendment PartThe revisions and additions read as follows.
Appendix M to Subpart B of Part 430—Uniform Test Method for Measuring the Energy Consumption of Central Air Conditioners and Heat Pumps
* * * * *3.1.9 Requirement for the Air Temperature Distribution Entering the Outdoor Coil
Monitor the temperatures of the air entering the outdoor coil using air sampling devices and/or temperature sensor grids, maintaining the required tolerances, if applicable, as described in section 2.11 of this appendix.
* * * * *Start Printed Page 551133.2.1 Tests for a System Having a Single-Speed Compressor and Fixed Cooling Air Volume Rate
This set of tests is for single-speed-compressor units that do not have a cooling minimum air volume rate or a cooling intermediate air volume rate that is different than the cooling full load air volume rate. Conduct two steady-state wet coil tests, the A and B Tests. Use the two optional dry-coil tests, the steady-state C Test and the cyclic D Test, to determine the cooling mode cyclic degradation coefficient, CDc. If the two optional tests are conducted but yield a tested CDc that exceeds the default CDc or if the two optional tests are not conducted, assign CDc the default value of 0.25 (for outdoor units with no match) or 0.20 (for all other systems). Table 4 specifies test conditions for these four tests.
* * * * *3.2.3 Tests for a Unit Having a Two-Capacity Compressor (See Section 1.2 of This Appendix, Definitions)
* * * * *d. * * * If the two optional tests are conducted but yield a tested CDc (k = 2) that exceeds the default CDc (k = 2) or if the two optional tests are not conducted, assign CDc (k = 2) the default value. ***
* * * * *3.3. * * *
d. * * *
Table 8—Test Operating and Test Condition Tolerances for Section 3.3 Steady-State Wet Coil Cooling Mode Tests and Section 3.4 Dry Coil Cooling Mode Tests
Test operating tolerance 1 Test condition tolerance 1 Indoor dry-bulb, °F: Entering temperature 2.0 0.5 Leaving temperature 2.0 Indoor wet-bulb, °F: Entering temperature 1.0 2 0.3 Leaving temperature 2 1.0 Outdoor dry-bulb, °F: Entering temperature 2.0 0.5 Leaving temperature 3 2.0 Outdoor wet-bulb, °F: Entering temperature 1.0 4 0.3 Leaving temperature 3 1.0 External resistance to airflow, inches of water 0.05 5 0.02 Electrical voltage, % of rdg. 2.0 1.5 Nozzle pressure drop, % of rdg. 2.0 1 See section 1.2 of this appendix, Definitions. 2 Only applies during wet coil tests; does not apply during steady-state, dry coil cooling mode tests. 3 Only applies when using the outdoor air enthalpy method. 4 Only applies during wet coil cooling mode tests where the unit rejects condensate to the outdoor coil. 5 Only applies when testing non-ducted units. * * * * *3.5 * * *
h. * * *
Table 9—Test Operating and Test Condition Tolerances for Cyclic Dry Coil Cooling Mode Tests
Test operating tolerance 1 Test condition tolerance 1 Indoor entering dry-bulb temperature 2, °F 2.0 0.5 Indoor entering wet-bulb temperature, °F (3) Outdoor entering dry-bulb temperature 2, °F 2.0 0.5 External resistance to airflow 2, inches of water 0.05 Airflow nozzle pressure difference or velocity pressure 2, % of reading 2.0 4 2.0 Electrical voltage 5, % of rdg. 2.0 1.5 1 See section 1.2 of this appendix, Definitions. 2 Applies during the interval that air flows through the indoor (outdoor) coil except for the first 30 seconds after flow initiation. For units having a variable-speed indoor blower that ramps, the tolerances listed for the external resistance to airflow apply from 30 seconds after achieving full speed until ramp down begins. 3 Shall at no time exceed a wet-bulb temperature that results in condensate forming on the indoor coil. 4 The test condition shall be the average nozzle pressure difference or velocity pressure measured during the steady-state dry coil test. 5 Applies during the interval when at least one of the following—the compressor, the outdoor fan, or, if applicable, the indoor blower—are operating except for the first 30 seconds after compressor start-up. * * * * *3.5.3 Cooling-Mode Cyclic-Degradation Coefficient Calculation
* * * If the two optional tests are conducted but yield a tested CDc that exceeds the default CDc or if the two optional tests are not conducted, assign CDc the default value of 0.25 for variable-speed compressor systems and outdoor units with no match, and 0.20 for all other systems.* * *
* * * * *3.6.3 Tests for a Heat Pump Having a Two-Capacity Compressor (see Section 1.2 of This Appendix, Definitions), Including Two-Capacity, Northern Heat Pumps (see Section 1.2 of This Appendix, Definitions)
* * * * *b. Conduct the optional high temperature cyclic test (H1C1) to determine the heating mode cyclic-degradation coefficient, CDh. If Start Printed Page 55114this optional test is conducted but yields a tested CDh that exceeds the default CDh or if the optional test is not conducted, assign CDh the default value of 0.25. If a two-capacity heat pump locks out low capacity operation at lower outdoor temperatures, conduct the high temperature cyclic test (H1C2) to determine the high-capacity heating mode cyclic-degradation coefficient, CDh (k=2). If this optional test at high capacity is conducted but yields a tested CDh (k = 2) that exceeds the default CDh (k = 2) or if the optional test is not conducted, assign CDh the default value. The default CDh (k=2) is the same value as determined or assigned for the low-capacity cyclic-degradation coefficient, CDh [or equivalently, CDh (k=1)]. Table 12 specifies test conditions for these nine tests.
* * * * *3.7 * * *
a. * * *
Table 15—Test Operating and Test Condition Tolerances for Section 3.7 and Section 3.10 Steady-State Heating Mode Tests
Test operating tolerance 1 Test condition tolerance 1 Indoor dry-bulb, °F: Entering temperature 2.0 0.5 Leaving temperature 2.0 Indoor wet-bulb, °F: Entering temperature 1.0 Leaving temperature 1.0 Outdoor dry-bulb, °F: Entering temperature 2.0 0.5 Leaving temperature 2 2.0 Outdoor wet-bulb, °F: Entering temperature 1.0 0.3 Leaving temperature 2 1.0 External resistance to airflow, inches of water 0.05 3 0.02 Electrical voltage, % of rdg 2.0 1.5 Nozzle pressure drop, % of rdg 2.0 1 See section 1.2 of this appendix, Definitions. 2 Only applies when the Outdoor Air Enthalpy Method is used. 3 Only applies when testing non-ducted units. * * * * *3.8.1 * * *
* * * If the optional cyclic test is conducted but yields a tested CDh that exceeds the default CDh or if the optional test is not conducted, assign CDh the default value of 0.25.* * *
* * * * *Table 16—Test Operating and Test Condition Tolerances for Cyclic Heating Mode Tests
Test operating tolerance 1 Test condition tolerance 1 Indoor entering dry-bulb temperature,2 °F 2.0 0.5 Indoor entering wet-bulb temperature,2 °F 1.0 Outdoor entering dry-bulb temperature,2 °F 2.0 0.5 Outdoor entering wet-bulb temperature,2 °F 2.0 1.0 External resistance to air-flow,2 inches of water 0.05 Airflow nozzle pressure difference or velocity pressure,2 % of reading 2.0 3 2.0 Electrical voltage,4 % of rdg 2.0 1.5 1 See section 1.2 of this appendix, Definitions. 2 Applies during the interval that air flows through the indoor (outdoor) coil except for the first 30 seconds after flow initiation. For units having a variable-speed indoor blower that ramps, the tolerances listed for the external resistance to airflow shall apply from 30 seconds after achieving full speed until ramp down begins. 3 The test condition shall be the average nozzle pressure difference or velocity pressure measured during the steady-state test conducted at the same test conditions. 4 Applies during the interval that at least one of the following—the compressor, the outdoor fan, or, if applicable, the indoor blower—are operating, except for the first 30 seconds after compressor start-up. * * * * *3.9 * * *
f. * * *
Table 17—Test Operating and Test Condition Tolerances for Frost Accumulation Heating Mode Tests
Test operating tolerance 1 Test condition tolerance 1 Sub-interval H 2 Sub-interval D 3 Sub-interval H 2 Indoor entering dry-bulb temperature, °F 2.0 4 4.0 0.5 Indoor entering wet-bulb temperature, °F 1.0 Outdoor entering dry-bulb temperature, °F 2.0 10.0 1.0 Start Printed Page 55115 Outdoor entering wet-bulb temperature, °F 1.5 0.5 External resistance to airflow, inches of water 0.05 5 0.02 Electrical voltage, % of rdg 2.0 1.5 1 See section 1.2 of this appendix, Definitions. 2 Applies when the heat pump is in the heating mode, except for the first 10 minutes after termination of a defrost cycle. 3 Applies during a defrost cycle and during the first 10 minutes after the termination of a defrost cycle when the heat pump is operating in the heating mode. 4 For heat pumps that turn off the indoor blower during the defrost cycle, the noted tolerance only applies during the 10 minute interval that follows defrost termination. 5 Only applies when testing non-ducted heat pumps. * * * * *4.1.1 * * *
b. * * * Evaluate the cooling mode cyclic degradation factor CDc as specified in section 3.5.3 of this appendix.
* * * * *4.1.2.1 * * *
c. * * * Evaluate the cooling mode cyclic degradation factor CDc as specified in section 3.5.3 of this appendix.
* * * * *4.1.3.1 * * *
nj/N = fractional bin hours for the cooling season; the ratio of the number of hours during the cooling season when the outdoor temperature fell within the range represented by bin temperature Tj to the total number of hours in the cooling season, dimensionless.
Obtain the fractional bin hours for the cooling season, nj/N, from Table 18. Use Equations 4.1.3-1 and 4.1.3-2, respectively, to evaluate Qck=1 (Tj) and Ėck=1 (Tj). Evaluate the cooling mode cyclic degradation factor CDc as specified in section 3.5.3 of this appendix.
* * * * *4.1.4.1 * * *
* * * Evaluate the cooling mode cyclic degradation factor CDc as specified in section 3.5.3 of this appendix.
* * * * *Appendix M to Subpart B of Part 430—[Amended]
Start Amendment Part5. In the table below, for each section of appendix M to subpart B of part 430 indicated in the left column, remove the language indicated in the middle column from wherever it appears in that section, and add the language indicated in the right column.
End Amendment PartSections Remove Add 3.2.2.1, 3.2.3.a A default value of CDc may be used in lieu of conducting the cyclic test. The default value of CDc is 0.20 If the two optional tests are conducted but yield a tested CDc that exceeds the default CDc or if the two optional tests are not conducted, assign CDc the default value of 0.20. 3.2.4.a A default value for CDc may be used in lieu of conducting the cyclic test. The default value of CDc is 0.25 If the two optional tests are conducted but yield a tested CDc that exceeds the default CDc or if the two optional tests are not conducted, assign CDc the default value of 0.25. 3.6.1 A default value for CDh may be used in lieu of conducting the cyclic test. The default value of CDh is 0.25 If this optional test is conducted but yields a tested CDh that exceeds the default CDh or if the optional test is not conducted, assign CDh the default value of 0.25. 3.6.2, 3.6.4.a A default value for CDh may be used in lieu of conducting the cyclic. The default value of CDh is 0.25 If this optional test is conducted but yields a tested CDh that exceeds the default CDh or if the optional test is not conducted, assign CDh the default value of 0.25. Appendix M to Subpart B of Part 430—[Amended]
Start Amendment Part6. For each newly redesignated section of appendix M to subpart B of part 430 in the first column, remove the cross reference sections in the middle column, and add in their places, the cross reference sections in the right column.
End Amendment PartEnd Supplemental InformationSection Remove Add 4.1.3 4.1.2.4 4.1.3.1 4.1.2.5 4.1.3.2 4.1.2.6 4.1.3.3 4.1.2.7 4.1.3.4 4.1.4.3 4.1.2.7 4.1.3.4 [FR Doc. 2016-19227 Filed 8-17-16; 8:45 am]
BILLING CODE 6450-01-P
Document Information
- Published:
- 08/18/2016
- Department:
- Energy Department
- Entry Type:
- Rule
- Action:
- Final rule; technical correction.
- Document Number:
- 2016-19227
- Pages:
- 55111-55115 (5 pages)
- Docket Numbers:
- Docket No. EERE-2009-BT-TP-0004
- RINs:
- 1904-AB94: Test Procedures for Residential Central Air Conditioners and Heat Pumps
- RIN Links:
- https://www.federalregister.gov/regulations/1904-AB94/test-procedures-for-residential-central-air-conditioners-and-heat-pumps
- Topics:
- Administrative practice and procedure, Confidential business information, Energy conservation, Household appliances, Imports, Incorporation by reference, Intergovernmental relations, Reporting and recordkeeping requirements, Small businesses
- PDF File:
- 2016-19227.pdf
- Supporting Documents:
- » 2015-08 Report: Review of Test Procedure For Determining HSPF's of Residential Variable-Speed Heat Pumps (ORNL/TM-2015/387)
- » 2015-08-26 Working Group Transcript: Central Air Conditioner and Heat Pump ASRAC Working Group Meeting
- » 2015-07 Presentation: Review of Test Procedure for Determining HSPFs of Residential Variable-Speed Heat Pumps, July 2015
- » 2015-07 Report: An Analysis of Representative Heating Load Lines for Residential HSPF Ratings, July 2015 (ORNL/TM-2015/281)
- » 2011-12-21 Notification of re-opening of SNOPR public comment period
- » 2011-10-03 Pre-publication of Federal Register Notice: Energy Conservation Program for Consumer Products: Test Procedures for Residential Central Air Conditioners and Heat Pumps; Supplemental notice of proposed rulemaking.
- » 2011-08-16 AHRI CAC Off-Mode Test Data
- » 2010-06-11 Public Meeting Attendee List
- » 2010-06-11 Transcript of Proceedings
- » 2010-06-11 Public Meeting Presentation Slides
- CFR: (1)
- 10 CFR 429.16