Start Preamble
AGENCY:
Office of Energy Efficiency and Renewable Energy, Department of Energy.
ACTION:
Final rule; technical amendments.
SUMMARY:
On May 1, 2023, the U.S. Department of Energy (“DOE”) published a final rule adopting procedures for fans and blowers (hereafter the “May 2023 Final Rule”). This document corrects editorial and typographical errors in the May 2023 Final Rule. Neither the errors nor the corrections in this document affect the Start Printed Page 53372 substance of the rulemaking or any conclusions reached in support of the final rule.
DATES:
Effective August 8, 2023.
Start Further InfoFOR FURTHER INFORMATION CONTACT:
Mr. Jeremy Dommu, U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, Building Technologies Office, EE–5B, 1000 Independence Avenue SW, Washington, DC 20585–0121. Telephone: (202) 586–9879. Email: ApplianceStandardsQuestions@ee.doe.gov.
Ms. Amelia Whiting, U.S. Department of Energy, Office of the General Counsel, GC–33, 1000 Independence Avenue SW, Washington, DC 20585–0121. Telephone: (202) 586–2588. Email: amelia.whiting@hq.doe.gov.
End Further Info End Preamble Start Supplemental InformationSUPPLEMENTARY INFORMATION:
I. Background
The May 2023 final rule established: (1) test procedures for fans and blowers and incorporated the relevant industry test standards for measuring the fan electrical power and determining the fan energy index (“FEI”) of fans and blowers other than air-circulating fans; (2) test procedure for air circulating fans measuring the fan airflow in cubic feet per minute per watt of electric power input (“CFM/Watt”); (3) supporting definitions; (4) requirements for alternative efficiency determination methods; and (5) sampling requirements. 88 FR 27312 (May 1, 2023).
Since the publication of the May 2023 Final Rule, DOE identified several typographical and editorial errors that could create confusion when conducting the DOE test procedure.
In the May 2023 Final Rule, in § 431.172, DOE introduced almost all definitions using “means the” or “means a” to describe each defined term. 88 FR 27312, 27389–27390. However, the definition of “air circulating fan discharge area” in § 431.172 of the regulatory text used a colon “:” rather than “means the” to introduce the definition. DOE replaces the colon “:” by “means the” to add consistency with how other definitions are presented. DOE notes that the meaning of the definition for “air circulating fan discharge area” is unchanged with this correction.
In the May 2023 Final Rule, DOE incorporated by reference AMCA 214–21, including the definitions of “fan static pressure” and “fan total pressure” in sections 3.41 and 3.43 of AMCA 214–21. 88 FR 27312, 27392. However, in the definition of “fan static air power” in § 431.172 of the regulatory text, the terms “static pressure” and “total pressure” are used without referencing the term “fan”. DOE is concerned that this may cause confusion as DOE incorporated the definitions of “fan static pressure” and “fan total pressure”,[1] but did not define the terms “static pressure” and “total pressure”. In addition, the terms “fan static pressure” and “fan total pressure” are used throughout the preamble of the May 2023 Final Rule and elsewhere in the regulatory text. 88 FR 27312, 27319, 27344, 27353, 27371, 27389, 27390, 27392. Consistent with the definition of “fan static pressure” and “fan total pressure” in sections 3.41 and 3.43 of AMCA 214–21, as incorporated by reference, and consistent with the terminology used throughout the preamble of the May 2023 Final Rule and elsewhere in the regulatory text, DOE replaces “using static pressure instead of total pressure” with “using fan static pressure instead of fan total pressure” in the definition of “fan static air power” in § 431.172. The meaning of the definition is unchanged by this correction.
DOE identified a missing hyphen in § 431.173, where the text reads as “ANSI/AMCA Standard 21016 (“AMCA 210–16”), rather than ANSI/AMCA Standard 210–16 (“AMCA 210–16”). 88 FR 27312, 27390. The reference should match the description in the preamble, which includes the hyphen. DOE corrects this to add the hyphen between 210 and 16.
Additionally, in the May 2023 Final Rule, the test procedure established for fans and blowers other than air circulating fans specifies that the applicable rating metric of FEI must be calculated using the electrical input power required to operate a fan in kilowatts (kW), abbreviated as “FEP”. 88 FR 27312, 27365. The May 2023 Final Rule generally uses the term “fan electrical input power” to designate the FEP throughout the preamble. 88 FR 27312, 27312, 27319, 27363, 27365, 27371. The preamble of the May 2023 Final Rule also uses the term “fan electrical power” to designate the FEP in one instance. 88 FR 27312, 27355. Further, in a number of places in the regulatory text, the term “fan electrical input power” and “fan electrical power” are used to describe the electrical input power to the fan in kilowatts (kW), abbreviated as “FEP”. 88 FR 27312, 27387, 27388, 27391, 27392, 27393. The May 2023 Final Rule also incorporates by reference AMCA 241–21 as the industry standards used to determine and define the FEP. In AMCA 214–21, the term “fan electrical power” is used to designate the FEP and defined in section 3 “Definitions” of AMCA 214–21, incorporated by reference. DOE believes that the use of “fan electrical input power” and “fan electrical power” to both designate the FEP may create confusion because only “fan electrical power” is the defined term. As such, DOE is correcting the regulatory text to only use “fan electrical power”, consistent with the definition in section 3 of AMCA 214–22, incorporated by reference, and replaces all instances of “fan electrical input power” with “fan electrical power”.
The preamble of the May 2023 Final Rule states that DOE is adopting the validation classes (1) through (9) and lists them as follows: (1) centrifugal housed; (2) radial housed; (3) centrifugal inline; (4) centrifugal unhoused; (5) centrifugal PRV exhaust; (6) centrifugal power roof ventilator (“PRV”) supply; (7) axial inline; (8) axial panel; (9) axial PRV. 88 FR 27312, 27373. The categories of PRVs are correctly listed in the preamble of the May 2023 Final Rule in footnote 20 where DOE specifies that PRVs include: Centrifugal PRV exhaust fans; Centrifugal PRV supply fans; and Axial PRVs, as defined in AMCA 214–21. 88 FR 27312, 27318. However, in the regulatory text, in § 429.70(n), DOE lists the following validation classes: centrifugal housed fan; radial housed fan; centrifugal inline fan; centrifugal unhoused fan; centrifugal power roof ventilator exhaust fan; centrifugal power roof ventilator supply fan; axial inline fan; axial panel fan; axial centrifugal power roof ventilator fan.” 88 FR 27312, 27388. DOE included the term “axial centrifugal power roof ventilator fan” as one of the validation classes instead of the correct term “axial power roof ventilator”. Similarly, the same error is included in § 431.174(a)(1), where DOE also used the term “axial centrifugal power roof ventilator fan” instead of “axial power roof ventilator” when listing the categories of fans in scope. 88 FR 27312, 27391. Therefore, DOE corrects this error and replaces the term “axial centrifugal power roof ventilator fan” by “axial power roof ventilator”.
In the May 2023 Final Rule, DOE established the metric for fans other than air circulating fans as the FEI, which is the fan energy index and represents the ratio of the electrical power of a reference fan to the electrical input power of the actual fan for which the FEI is calculated, both established at the same duty point. 88 FR 27312, Start Printed Page 53373 27349, 27365. However, in the regulatory text in § 429.69(a)(1)(iii), DOE wrote “any represented value of fan electrical input power (“FEI”), or other measure of energy consumption of a basic model for which consumers would favor higher values shall be less than or equal to the tested value” and incorrectly described the FEI as the “fan electrical input power” [2] rather than the “fan energy index”. 88 FR 27312, 27387. In § 429.69(a)(1)(v), the FEI is correctly described: “any represented value of the fan energy index (“FEI”), or other measure of energy consumption of a basic model for which consumers would favor higher values”. 88 FR 27312, 27388. DOE corrects this error and replaces “fan electrical input power (“FEI”)” by “fan energy index (“FEI”)” in § 429.69(a)(1)(iii).
In the test procedure NOPR published on July 25, 2022, DOE proposed to incorporate by reference AMCA 214–21 for air circulating fans, which relies on the FEP and FEI metrics (“wire-to-air metrics”) for air circulating fans. 87 FR 44194, 44236–44237. In the May 2023 Final Rule, DOE established the metric for air circulating fans in terms of efficacy in cubic feet per minute per watt (“CFM/W”) for air circulating fans at maximum speed. 88 FR 27312, 27371. This is also reflected in the regulatory text in section 2.2.1 of appendix B to subpart J of part 431 where DOE states that “The air circulating fan efficacy (Eƒƒcirc) in cubic feet per minute (“CFM”) per watt (“W”) (“CFM/W”) at maximum speed must be determined in accordance with the applicable sections of AMCA 230–23 as listed in section 2.2.2 of this appendix”. 88 FR 27312, 27393. However, in the May 2023 Final Rule, in the regulatory text in § 431.174, the text was not updated to reflect the adopted metric and incorrectly references the FEI and FEP metrics as proposed in the July 2022 NOPR, as follows: “Determine the FEI and the fan electrical input power (“FEP”) or the weighted-average FEI and weighted-average FEP as applicable, using the test procedure set forth in appendix B of this subpart”. 88 FR 27312, 27391. DOE corrects this error such that the text reflects the correct efficacy metric in CFM/W adopted for air circulating fans in the May 2023 Final Rule, such that it reads: “Determine the air circulating fan efficacy in cubic feet per minute per watt at maximum speed using the test procedure set forth in appendix B of this subpart.”
In the May 2023 Final Rule, DOE stated that, although it incorporated by reference AMCA 214–21, it does not include section 6.5 of AMCA 214.21 in its test procedure. 88 FR 27312, 27350. Similarly, in the regulatory text, when listing the applicable section of AMCA 214–21 in section 0 of appendix A to subpart J of part 431, DOE did not list section 6.5 of AMCA 214–21. 88 FR 27312, 27392. DOE also did not list section 6.5 of AMCA 214–21 as an applicable section in Table 1 appendix A to subpart J of part 431. Id. However, in the regulatory text, in section 2.2.1 of appendix A to subpart J of part 431, DOE mistakenly listed section 6.5 in the following statement “fan shaft power for fans tested in accordance with sections 6.3, 6.4 or 6.5 of AMCA 214–21”. 88 FR 27312, 27392. DOE corrects this error to be consistent with the discussion of the preamble and other sections of the regulatory text in the May 2023 Final Rule that excluded section 6.5 of AMCA 214–21.
In the May 2023 Final Rule, DOE adopted provisions to replace the motor efficiency values in Annex A of AMCA 214–21 with the values in Table 5 of 10 CFR 431.25. DOE stated that while the values are currently identical, referencing the CFR would ensure that the values of polyphase regulated motor efficiencies remain up to date with any potential future updates established by DOE. 88 FR 27312, 27349. In the regulatory text in § 429.69, to reflect this intent, DOE also states: “Manufacturers must update represented values to account for any change in the applicable motor standards in Table 5 of part 431 of this chapter”. In the regulatory text, DOE also included this provision in section 2.1 of appendix A to subpart J of part 431 as follows: “Where AMCA 214–21 refers to Annex A, “Polyphase Regulated Motor Efficiencies (Normative),” of AMCA 214–21, Table 5 of § 431.25 must be used instead.” However, because any potential future updates to electric motor energy conservation updates could appear in tables other than Table 5 of 10 CFR 431.25, DOE makes the following correction to reflect the intent of the preamble which is to remain up to date with any potential future updates established by DOE: “Polyphase Regulated Motor Efficiencies (Normative),” of AMCA 214–21, Table 5 of § 431.25 or the currently applicable standards in § 431.25 must be used instead.”
In the May 2023 Final Rule, DOE established stability criteria for testing both air circulating fans and fan and blowers other than air circulating fans. As part of the stability requirements for fans and blowers other than air circulating fans, DOE stated that it was adopting provisions to require that the stability will be evaluated and confirmed over at least three 60-second data collection intervals, and that the fan input power shall be monitored at least every 5 seconds over the 60-second data collection intervals. 88 FR 27312, 27360. In addition, DOE specified that the average fan speed from one data collection interval to the next must be within ±1 percent or 1 rpm, whichever is greater; and the average input power by reaction dynamometer, torque meter or calibrated motor must be within ±4 percent, or the average input power by electrical meter must be within ±2 percent of the mean or 1 watt, whichever is greater. Id. However, in the May 2023 Final Rule, DOE included incorrect regulatory text for the stability requirement for input power in section 2.4(b)(2) of appendix A to subpart J of part 431, specifying that “the average input power from the last 60-second interval varies by less than the absolute value of 1 percent, whichever is greater, compared to the average input power measured during the previous 60-second test interval.” 88 FR 27312, 27393. DOE is correcting this error in section 2.4(b)(2) of appendix A to subpart J of part 431 to remove this language and replace it with the appropriate stability requirement that “the average input power from the last 60-second interval by reaction dynamometer, torque meter or calibrated motor must be ±4 percent, or the average input power by electrical meter must be ±2 percent of the mean or 1 watt, whichever is greater, compared to the average input power measured during the previous 60-second test interval.”
In addition, for the stability conditions for fans and blowers other than air circulating fans in section 2.4(b) of appendix A to subpart J of part 431, DOE identified that the units for recording input power are listed as “pound-force, pound-force-in, or watts.” 88 FR 27312, 27393. but the units should be “horsepower or watts.” The pound-force and pound-force-in were listed incorrectly and the horsepower or watts are the correct units, consistent with AMCA 214–21, incorporated by reference. Therefore, DOE is correcting this error and replacing the units for input power in section 2.4(b) in appendix A to subpart J of part 431with “horsepower or watts.”
DOE identified that in the description of the stability conditions for air circulating fans in section 2.5(b)(3) of appendix B to subpart J of part 431, DOE defines the stable load differential as Start Printed Page 53374 “varies by less than the absolute value of 1 percent, whichever is greater.” The term “whichever is greater” is unnecessary as there is not a second criteria. In the May 2023 Final Rule, DOE stated that the average load differential from one data collection interval to the next must be within ±1 percent. 88 FR 27312, 27362. DOE corrects this error by removing the text “whichever is greater” from section 2.5(b)(3) of appendix B to subpart J of part 431.
DOE identified inconsistencies in the rounding requirements for FEP for fans and blowers other than air circulating fans. Section 2.6 of appendix A to subpart J of part 431 specifies that FEP must be rounded to three significant figures, but § 429.69(a)(1)(ii) and (iv) specifies that any represented value of FEP, fan shaft input power, or other measure of energy consumption of a basic model for which consumers would favor a lower value must be rounded to the nearest hundredth. 88 FR 27312, 27387–27388, 27393. In the May 2023 Final Rule, DOE noted that it was adopting requirements that FEP (in kilowatts) shall be rounded to three significant figures. 88 FR 27312, 27364. DOE acknowledges that § 429.69(a)(1)(ii) and (iv) contains the incorrect rounding requirements and DOE is revising these sections to specify that FEP be rounded to three significant figures. Fan shaft input power and other measures of energy consumption of a basic model for which consumers would favor a lower value must still be rounded to the nearest hundredth.
Also, as part of the stability condition requirements for both air circulating fans and fans and blowers other than air circulating fans, in the May 2023 Final Rule, DOE adopted provisions in section 2.4(b)(3) of appendix A to subpart J of part 431 and section 2.5(b)(4) of appendix B to subpart J of part 431 that slope of the fan speed, input power, and load differential [3] measurements from one data collection interval to the next shall not be trending positive or negative. 88 FR 27312, 27393, 27394. Specifically, DOE adopted requirements that if the slope of 3 or more successive data collection intervals are all positive or all negative, additional data collection intervals must be run until a negative or positive slope, respectively, is achieved. Id. DOE notes that the requirements may not be explicit as to whether a linear trendline should be applied to the data. DOE assumed that a linear trendline would be used and notes that the requirement to calculate the “slope” for each sampling interval implies a linear fit trendline, however, DOE is correcting the requirements in section 2.4(b)(3) of appendix A to subpart J of part 431 and section 2.5(b)(4) of appendix B to subpart J of part 431 to explicitly state that a linear fit trendline shall be applied when evaluating the slopes for each data collection interval.
In the May 2023 Final Rule, DOE incorporated by reference AMCA 230–23 and adopted by reference the equations for calculating ambient air density, as defined in Equations 8.5 and section 8.6 of AMCA 230–23. 88 FR 27312, 27393. However, DOE identified a typographical error in Equations 8.5 and section 8.6 of AMCA 230–23. The equations are given as:
II. Need for Correction
As published, the regulatory text in the May 2023 Final Rule may result in confusion due to the errors discussed in section I of this document. Because this final rule would simply correct errors in the text without making substantive changes in the May 2023 Final Rule, the changes addressed in this document are technical in nature.
III. Procedural Issues and Regulatory Review
DOE has concluded that the determinations made pursuant to the various procedural requirements applicable to the May 2023 Final Rule remain unchanged for this final rule technical correction. These determinations are set forth in the May 2023 Final Rule. 88 FR 27312, 27383–27387.
Pursuant to the Administrative Procedure Act, 5 U.S.C. 553(b), DOE finds that there is good cause to not issue a separate notice to solicit public Start Printed Page 53375 comment on the changes contained in this document. Neither the errors nor the corrections in this document affect the substance of the May 2023 Final Rule or any of the conclusions reached in support of the final rule. For these reasons, this rule is not subject to the 30-day delay in effective date requirement of 5 U.S.C. 553(d) otherwise applicable to rules that make substantive changes.
Start List of SubjectsList of Subjects
10 CFR Part 429
- Administrative practice and procedure
- Confidential business information
- Energy conservation
- Household appliances
- Imports
- Intergovernmental relations
- Reporting and recordkeeping requirements
- Small businesses
10 CFR Part 431
- Administrative practice and procedure
- Confidential business information
- Energy conservation
- Household appliances
- Imports
- Incorporation by reference
- Intergovernmental relations
- Laboratories
- Reporting and recordkeeping requirements
- Small businesses
Signing Authority
This document of the Department of Energy was signed on July 19, 2023, by Francisco Alejandro Moreno Acting Assistant Secretary for Energy Efficiency and Renewable Energy, pursuant to delegated authority from the Secretary of Energy. That document with the original signature and date is maintained by DOE. For administrative purposes only, and in compliance with requirements of the Office of the Federal Register, the undersigned DOE Federal Register Liaison Officer has been authorized to sign and submit the document in electronic format for publication, as an official document of the Department of Energy. This administrative process in no way alters the legal effect of this document upon publication in the Federal Register .
Start SignatureSigned in Washington, DC, on July 20, 2023.
Treena V. Garrett,
Federal Register Liaison Officer, U.S. Department of Energy.
For the reasons stated in the preamble, DOE corrects parts 429 and 431 of chapter II, subchapter D, of title 10 of the Code of Federal Regulations by making the following correcting amendments:
Start PartPART 429—CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
End Part Start Amendment Part1. The authority citation for part 429 continues to read as follows:
End Amendment Part[Amended]2. Amend § 429.69 by:
End Amendment Part Start Amendment Parta. In paragraph (a)(1)(ii), removing the words “fan electrical input power (“FEP”)” and adding in its place, the words “fan electrical power (“FEP”).”
End Amendment Part Start Amendment Partb. In paragraphs (a)(1)(ii) and (a)(1)(iv)(B), removing the text “Represented values must be rounded to the nearest hundredth” and adding in its place, the text “Represented values other than FEP must be rounded to the nearest hundredth. FEP must be rounded to three significant figures.”
End Amendment Part Start Amendment Partc. In paragraph (a)(1)(iii), removing the words “fan electrical input power (“FEI”)” and adding in its place, the words “fan energy index (“FEI”).”
End Amendment Part[Amended]3. Amend § 429.70 in paragraph (n)(2)(i) by removing the words “axial centrifugal power roof ventilator fan” and adding in its place, the words “axial power roof ventilator.”
End Amendment Part Start PartPART 431—ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND INDUSTRIAL EQUIPMENT
End Part Start Amendment Part4. The authority citation for part 431 continues to read as follows:
End Amendment Part Start Amendment Part5. Amend § 431.172 by revising the definitions for “Air circulating fan discharge area” and “Fan static air power” to read as follows:
End Amendment PartDefinitions.* * * * *Air circulating fan discharge area means the area of a circle having a diameter equal to the blade tip diameter.
* * * * *Fan static air power means the static power delivered to air by the fan or blower; it is proportional to the product of the fan airflow rate, the fan static pressure and the compressibility coefficient and is calculated in accordance with section 7.8.1 of AMCA 210–16 (incorporated by reference, see § 431.173), using fan static pressure instead of fan total pressure.
* * * * *6. Amend § 431.173 by revising paragraph (b)(1) to read as follows:
End Amendment PartMaterials incorporated by reference.* * * * *(b) * * *
(1) ANSI/AMCA Standard 210–16 (“AMCA 210–16”), Laboratory Methods of Testing Fans for Certified Aerodynamic Performance Rating, ANSI-approved August 26, 2016; IBR approved for § 431.172; appendix A to this subpart. (Co-published as ASHRAE 51–16).
* * * * *7. Amend § 431.174 by:
End Amendment Part Start Amendment Parta. In paragraph (a)(1), removing the words “axial centrifugal power roof ventilator” and adding in its place, the words “axial power roof ventilator”;
End Amendment Part Start Amendment Partb. In paragraph (a)(4)(i)(B) and paragraph (c), removing the words “fan electrical input power” and adding in its place, the words “fan electrical power”; and
End Amendment Part Start Amendment Partc. Revising paragraph (d).
End Amendment PartThe revision read as follows:
Test Procedure for fans or blowers.* * * * *(d) Testing and calculations for air circulating fan. Determine the air circulating fan efficacy in cubic feet per minute per watt at maximum speed using the test procedure set forth in appendix B to this subpart.
8. Amend appendix A to subpart J of part 431 by revising sections 2.1., 2.2.1. and 2.4(b), (b)(2), and (3) to read as follows:
End Amendment PartAppendix A to Subpart J of Part 431—Uniform Test Method for the Measurement of Energy Consumption of Fans and Blowers Other Than Air Circulating Fans
* * * * *2.1. General.
This section describes the test procedure for fans and blowers other than air circulating fans. In cases where there is a conflict, the provisions in this appendix take precedence over AMCA 214–21. Where AMCA 214–21 refers to Annex A, “Polyphase Regulated Motor Efficiencies (Normative),” of AMCA 214–21, Table 5 of § 431.25 or the currently applicable standards in § 431.25 must be used instead.
2.2 Testing
2.2.1. General.
The fan electrical power (FEPact) in kilowatts must be determined at every duty point specified by the manufacturer in accordance with one of the test methods listed in table 1, and the following sections of AMCA 214–21: Section 2, “References (Normative)”; Section 7, “Testing,” including the provisions of AMCA 210–16 and ISO 5801:2017 as referenced by Section 7 and Start Printed Page 53376 implicated by sections 2.2.2 and 2.2.3 of this appendix; Section 8.1, “Laboratory Measurement Only” (as applicable); and Annex J, “Other data and calculations to be retained.”
Table 1 to Appendix A to Subpart J of Part 431
Driver Motor controller present? Transmission configuration? Test method Applicable section(s) of AMCA 214–21 Electric motor Yes or No Any Wire-to-air 6.1 “Wire-to-Air Testing at the Required Duty Point”. Electric motor Yes or No Any Calculation based on Wire-to-air testing 6.2 “Calculated Ratings Based on Wire to Air Testing” (references Section 8.2.3, “Calculation to other speeds and densities for wire-to-air testing,” and Annex G, “Wire-to-Air Measurement—Calculation to Other Speeds and Densities (Normative)”). Regulated polyphase motor No Direct drive, V-belt drive, flexible coupling or synchronous belt drive Shaft-to-air 6.4 “Fans with Polyphase Regulated Motors,” (references Annex D, “Motor Performance Constants (Normative)”) *. None or non-electric No None Shaft-to-air Section 6.3, “Bare Shaft Fans”. Regulated polyphase motor No Direct drive, V-belt drive, flexible coupling or synchronous belt drive Calculation based on Shaft-to-air testing Section 8.2.1, “Fan laws and other calculation methods for shaft-to-air testing”(references Annex D, “Motor Performance Constants (Normative),” Annex E, “Calculation Methods for Fans Tested Shaft-to-Air,” and Annex K, “Proportionality and Dimensional Requirements (Normative)”). None or non-electric No None Calculation based on Shaft-to-air testing Section 8.2.1, “Fan laws and other calculation methods for shaft-to-air testing” (references Annex E, “Calculation Methods for Fans Tested Shaft-to-Air,” and Annex K, “Proportionality and Dimensional Requirements (Normative)”). * Excluding Section 6.4.1.4, “Requirements for the VFD, if included” and Section 6.4.2.4, “Combined motor-VFD efficiency.” Testing must be performed in accordance with the required test configuration listed in Table 7.1 of AMCA 214–21. The following values must be determined in accordance with this appendix at each duty point specified by the manufacturer: fan airflow in cubic feet per minute; fan air density; fan total pressure in inches of water gauge for fans using a total pressure basis FEI in accordance with Table 7.1 of AMCA 214–21; fan static pressure in inches of water gauge for fans using a static pressure basis FEI in accordance with Table 7.1 of AMCA 214–21; fan speed in revolutions per minute; and fan shaft input power in horsepower for fans tested in accordance with sections 6.3 or 6.4 of AMCA 214–21.
In addition, if applying the equations in Section E.2 of Annex E of AMCA 214–21 for compressible flows, the compressibility coefficients must be included in the equations as applicable.
All measurements must be recorded at the resolution of the test instrumentation and calculations must be rounded to the number of significant digits present at the resolution of the test instrumentation.
In cases where there is a conflict, the provisions in AMCA 214–21 take precedence over AMCA 210–16 and ISO 5801:2017. In addition, the provisions in this appendix apply.
* * * * *2.4. Stability Conditions.
* * * * *(b) After the fan has been run-in, record the fan speed in rpm and the input power (in horsepower or watts) at least every 5 seconds for at least three 60-second intervals. Readings shall be made simultaneously. Repeat these measurements over 60-second intervals until:
* * * * *(2) The average input power from the last 60-second interval by reaction dynamometer, torque meter or calibrated motor must be ±4 percent, or the average input power by electrical meter must be ±2 percent of the mean or 1 watt, whichever is greater, compared to the average input power measured during the previous 60-second test interval; and
(3) The slopes of a linear fit trendline calculated from the individual data collected for fan speed and input power during at least three 60-second sampling intervals include both positive and negative values ( e.g., two positive and one negative slope value or one positive and two negative slope values). If three positive or three negative slopes are determined in succession, additional sampling intervals are required until slopes from three successive sampling intervals include both positive and negative values.
* * * * *Start Amendment Part9. Amend appendix B to subpart J of part 431 by:
End Amendment Part Start Amendment Parta. Revising sections 0.1;
End Amendment Part Start Amendment Partb. In section 2.2.1., remove the text “section 2.2.2 of this appendix” and add, in its place, the text “section 0.1 of this appendix”;
End Amendment Part Start Amendment Partc. Removing section 2.2.2.;
End Amendment Part Start Amendment Partd. Revising sections 2.5(b)(3) and (4); and
End Amendment Part Start Amendment Parte. Adding section 2.6.
End Amendment PartThe revisions and addition read as follows:
Start AppendixAppendix B to Subpart J of Part 431—Uniform Test Method for the Measurement of Energy Consumption of Air Circulating Fans
* * * * *0.1 AMCA 230–23:
(a) Section 4, “Definitions/Units of Measurement/Symbols,”;
(b) Section 5, “Instruments and Methods of Measurement,”;
(c) Section 6, “Equipment and Setup,”;
(d) Section 7, “Observations and Conduct of Test,”;
(e) Section 8, “Calculations,” excluding equations 8.5 and 8.6; and
(f) Section 9, “Report and Results of Test,”.
* * * * *2.5. Stability Conditions.
* * * * *(b) * * *
(3) The average load differential of the last 120-second interval varies by less than the absolute value of 1 percent compared to the average load differential during the previous 120-second test interval; and Start Printed Page 53377
(4) The slopes of a linear fit trendline calculated from the individual data collected for fan speed, input power, and load differential during at least three 120-second intervals include both positive and negative values (e.g., two positive and one negative slope value or one positive and two negative slope values). If three positive or three negative slopes are determined in succession, additional sampling intervals are required until slopes from three successive 120-second intervals include both positive and negative values.
2.6. Calculation of Ambient Air Density.
For any references to ambient air density, ρ0, in AMCA 230–23, calculate ρ0, expressed in kg/m3 when using SI units or lbm/ft3 when using I–P units, as follows:
End Appendixwhere pb is the measured barometric pressure of the air, Td0 is the measured dry-bulb temperature of the air, pp is the partial vapor pressure, R is the gas constant, which are all determined according to section 8.2 of AMCA 230–23.
End Supplemental InformationFootnotes
1. As noted previously, DOE incorporated by reference AMCA 214–21, including the definitions of “fan static pressure” and “fan total pressure” in sections 3.41 and 3.43 of AMCA 214–21. 88 FR 27312, 27392.
Back to Citation2. As noted previously, the term “fan electrical input power” is equivalent to “fan electrical power”.
Back to Citation3. Load differential is applicable to only air circulating fans.
Back to Citation[FR Doc. 2023–15712 Filed 8–7–23; 8:45 am]
BILLING CODE 6450–01–P
Document Information
- Effective Date:
- 8/8/2023
- Published:
- 08/08/2023
- Department:
- Energy Department
- Entry Type:
- Rule
- Action:
- Final rule; technical amendments.
- Document Number:
- 2023-15712
- Dates:
- Effective August 8, 2023.
- Pages:
- 53371-53377 (7 pages)
- Docket Numbers:
- EERE-2021-BT-TP-0021
- RINs:
- 1904-AF17: Test Procedure for Fans and Blowers
- RIN Links:
- https://www.federalregister.gov/regulations/1904-AF17/test-procedure-for-fans-and-blowers
- Topics:
- Administrative practice and procedure, Confidential business information, Energy conservation, Household appliances, Imports, Incorporation by reference, Intergovernmental relations, Laboratories, Reporting and recordkeeping requirements, Small businesses
- PDF File:
- 2023-15712.pdf
- Supporting Documents:
- » 2022-09-21 DOE response to the Air Movement and Control Association International (AMCA) and Air Conditioning, Heating, and Refrigeration Institute (AHRI) request for a comment period extension (xref EERE-2021-BT-TP-0021-0019)
- » 2022-09-21 DOE response to the Association of Home Appliance Manufacturers (AHAM) request for a comment period extension (xref EERE-2021-BT-TP-0021-0020)
- » 2022-09-22 DOE response to the California Investor-Owned Utilities (CA IOUs) request for a comment period extension (xref EERE-2021-BT-TP-0021-0021)
- » 2022-09-22 DOE response to the Northwest Energy Efficiency Alliance (NEEA) request for a comment period extension (xref EERE-2021-BT-TP-0021-0022)
- » 2022-09-22 DOE response to the Johnson Controls (JCI) request for a comment period extension (xref EERE-2021-BT-TP-0021-0023)
- » 2022-08-02 Transcript of Proceedings In the Matter of: Appliance Standards Fans and Blowers Test Procedure Notice of Proposed Rulemaking, Docket No.: EERE-2021-BT-TP-0021
- » 2022-08-02 Public Meeting Registration List (registration-20220802143112)
- » 2022-08-02 Meeting Presentation: Fans and Blowers Test Procedure NOPR: Public Meeting - August 2, 2022
- CFR: (5)
- 10 CFR 429.69
- 10 CFR 429.70
- 10 CFR 431.172
- 10 CFR 431.173
- 10 CFR 431.174