C1-2019-26354. Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies  

  • Start Preamble

    Correction

    In rule document 2019-2635 beginning on page 1447 in the issue of Friday, January 10, 2020, make the following correction:

    [Corrected]

    On page 1503, in § 430.32(z)(3) the table should appear as follows:

    Battery charger product classRated output powerMinimum efficiency
    10a (VFD UPSs)0 W < P rated ≤ 300 W−1.20E-06 * P2 rated + 7.17E-04 * P rated + 0.862.
    300 W < P rated ≤ 700 W−7.85E-08 * P2 rated + 1.01E-04 * P rated + 0.946.
    P rated > 700 W−7.23E-09 * P2 rated + 7.52E-06 * P rated + 0.977.
    10b (VI UPSs)0 W < P rated ≤ 300 W−1.20E-06 * P2 rated + 7.19E-04 * P rated + 0.863.
    300 W < P rated ≤ 700 W−7.67E-08 * P2 rated + 1.05E-04 * P rated + 0.947.
    P rated > 700 W−4.62E-09 * P2 rated + 8.54E-06 * P rated + 0.979.
    10c (VFI UPSs)0 W < P rated ≤ 300 W−3.13E-06 * P2 rated + 1.96E-03 * P rated + 0.543.
    300 W < P rated ≤ 700 W−2.60E-07 * P2 rated + 3.65E-04 * P rated + 0.764.
    P rated > 700 W−1.70E-08 * P2 rated + 3.85E-05 * P rated + 0.876.
    End Preamble

    [FR Doc. C1-2019-26354 Filed 1-17-20; 8:45 am]