E6-16998. Energy Conservation Program: Test Procedures for Distribution Transformers; Correction  

  • Start Preamble

    AGENCY:

    Office of Energy Efficiency and Renewable Energy, Department of Energy.

    ACTION:

    Final rule; technical corrections.

    SUMMARY:

    The Department of Energy (DOE or the Department) published a final rule on April 27, 2006, amending Part 431 to prescribe test procedures and other provisions for distribution transformers, pursuant to sections 323(b)(10) and 346(a) of the Energy Policy and Conservation Act, as amended. (42 U.S.C. 6293(b)(10) and 6317(a)) This document corrects three typographical errors in the final rule.

    DATES:

    This correction is effective October 16, 2006.

    Start Further Info

    FOR FURTHER INFORMATION CONTACT:

    Antonio Bouza, U.S. Department of Energy, Energy Efficiency and Renewable Energy, Building Technologies Program, EE-2J, 1000 Independence Avenue, SW., Washington, DC 20585-0121, (202) 586-4563, e-mail: antonio.bouza@ee.doe.gov.

    Francine Pinto, Esq., U.S. Department of Energy, Office of General Counsel, GC-72, 1000 Independence Avenue, SW., Washington, DC 20585-0121, (202) 586-9507, e-mail: Francine.Pinto@hq.doe.gov.

    End Further Info End Preamble Start Supplemental Information

    SUPPLEMENTARY INFORMATION:

    The final rule that is the subject of this correction document established (1) Test procedures for measuring the energy efficiency of distribution transformers, (2) definitions to delineate the products covered by the test procedures, (3) provisions manufacturers must use to implement the test procedures, (4) calculation methods for determining the efficiency of distribution transformers, and (5) enforcement provisions for this equipment. 71 FR 24971 (April 27, 2006).

    Need for Corrections

    As published in the final rule, the definition for the term “excitation current” which can also be referred to as “no-load current” contains a typographical error that may prove to be misleading, and needs to be corrected. In the final rule, the conjunction “or” appearing between the terms “excitation current” and “no-load current” was italicized, such that the two terms excitation current and no-load current appeared as one continuous phrase (i.e., excitation current or no-load current). The Department is concerned that the italicization of the word “or” may lead to confusion about the defined term. This technical correction document removes the italicization of the word “or.” The remainder of the definition (i.e., “means the current that flows in any winding used to excite the transformer when all other windings are open-circuited”) was correct in the final rule and is not amended by this technical correction.

    In a comment submitted after the publication of the final rule, NEMA brought to the Department's attention two typographical errors that have an impact on the calculation of distribution transformer efficiency and must be corrected. (NEMA, No. 61 at p. 1) In the final rule notice, Equation 5-1 was given as:

    And an explanation of one of the terms in equation 5-1, Pos, was given as follows:

    Pos is the specified energy efficiency load level, where, Pos = Por L2, and

    NEMA determined that there are typographical errors in both equation 5-1 and the explanation of the term Pos. The Department carefully reviewed this comment, and agrees with NEMA's determination. In equation 5-1, the quantity contained in the square brackets should be squared (i.e., raised to the second power). In the explanation of the term Pos, the variable represented by the letter “L” should not be squared. These errors were present in the Department's previous supplemental notice of proposed rulemaking for this test procedure (69 FR 45532), but were not identified at that time.

    Today's technical correction document amends equation 5-1, raising the contents of the square brackets to the second power, so the corrected equation reads as follows:

    Similarly, this technical correction document amends the explanation of the term Pos to remove the square from the variable L, so the corrected equation reads as follows:

    Pos is the specified energy efficiency load level, where Pos = Por L, and

    Start List of Subjects

    List of Subjects in 10 CFR Part 431

    • Administrative practice and procedure
    • Distribution transformers
    • Energy conservation
    End List of Subjects Start Amendment Part

    Accordingly, 10 CFR part 431 is amended by making the following technical corrections:

    End Amendment Part Start Part

    PART 431—ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND INDUSTRIAL EQUIPMENT

    End Part Start Amendment Part

    1. The authority citation for part 431 continues to read as follows:

    End Amendment Part Start Authority

    Authority: 42 U.S.C. 6291-6317.

    End Authority Start Amendment Part

    2. In § 431.192, revise the definition of “excitation current” to read as follows:

    End Amendment Part
    Definitions.
    * * * * *

    Excitation current or no-load current means the current that flows in any winding used to excite the transformer when all other windings are open-circuited.

    * * * * *
    Start Amendment Part

    3. In section 5.1 of Appendix A to Subpart K of Part 431, revise equation 5-1 and the explanation for the term P os to read as follows:

    End Amendment Part Start Appendix

    Appendix A to Subpart K of Part 431—Uniform Test Method for Measuring the Energy Consumption of Distribution Transformers

    * * * * *

    5.1 Output Loading Level Adjustment.

    * * * * *

    Where:

    * * * * *

    Pos is the specified energy efficiency load level, where Pos = Por L, and

    * * * * *
    End Appendix Start Signature
    Start Printed Page 60663

    Issued in Washington, DC, on October 2, 2006.

    Alexander A. Karsner,

    Assistant Secretary, Energy Efficiency and Renewable Energy.

    End Signature End Supplemental Information

    [FR Doc. E6-16998 Filed 10-13-06; 8:45 am]

    BILLING CODE 6450-01-P

Document Information

Comments Received:
0 Comments
Effective Date:
10/16/2006
Published:
10/16/2006
Department:
Energy Efficiency and Renewable Energy Office
Entry Type:
Rule
Action:
Final rule; technical corrections.
Document Number:
E6-16998
Dates:
This correction is effective October 16, 2006.
Pages:
60662-60663 (2 pages)
Docket Numbers:
Docket No. EE-TP-98-550
RINs:
1904-AA85: Test Procedures for Electric Distribution Transformers
RIN Links:
https://www.federalregister.gov/regulations/1904-AA85/test-procedures-for-electric-distribution-transformers
Topics:
Administrative practice and procedure, Energy conservation
PDF File:
e6-16998.pdf
CFR: (1)
10 CFR 431.192