96-25314. National Institute for Occupational Safety and Health; Draft Document ``Engineering Control Guidelines for Hot Mix Asphalt Pavers''  

  • [Federal Register Volume 61, Number 193 (Thursday, October 3, 1996)]
    [Notices]
    [Pages 51708-51712]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 96-25314]
    
    
    -----------------------------------------------------------------------
    
    
    DEPARTMENT OF HEALTH AND HUMAN SERVICES
    
    National Institute for Occupational Safety and Health; Draft 
    Document ``Engineering Control Guidelines for Hot Mix Asphalt Pavers''
    
    AGENCY: National Institute for Occupational Safety and Health (NIOSH), 
    Centers for Disease Control
    
    [[Page 51709]]
    
    and Prevention (CDC), Department of Health and Human Services.
    
    ACTION: Request for comments.
    
    -----------------------------------------------------------------------
    
    SUMMARY: NIOSH is seeking public comments on the draft document 
    ``Engineering Control Guidelines for Hot Mix Asphalt Pavers'' provided 
    in this announcement.
    
    DATES: Written comments to this notice should be submitted to Diane 
    Manning, NIOSH Docket Office, 4676 Columbia Parkway, Mailstop C-34, 
    Cincinnati, Ohio 45226. Comments must be received on or before November 
    4, 1996.
        Comments may also be submitted by email to: [email protected] 
    NIOSDT1.em.cdc.gov. as WordPerfect 5.0, 5.1/5.2, 6.0/6.1, or ASCII 
    files.
    
    FOR FURTHER INFORMATION CONTACT: Technical information may be obtained 
    from Joann Wess or Ralph Zumwalde, NIOSH, CDC, 4676 Columbia Parkway, 
    M/S C-32, Cincinnati, Ohio 45226, telephone (513) 533-8319.
    
    SUPPLEMENTARY INFORMATION: The following is the complete text of the 
    draft document for public comment ``Engineering Control Guidelines for 
    Hot Mix Asphalt Pavers''.
    
    Background
    
        On July 8-9, 1996, NIOSH convened a public meeting in Cincinnati, 
    Ohio, to discuss the scientific and technical issues relevant to the 
    development of recommendations for controlling exposures to asphalt 
    fume during asphalt paving operations. Representatives from labor, 
    industry, and government knowledgeable of current control technologies 
    for asphalt exposure met to discuss the types of remedial action (e.g., 
    engineering controls, work practices) needed to reduce worker 
    exposures. Participants at this meeting included representatives from 
    the Asphalt Institute (AI), the Federal Highway Administration (FHWA), 
    the International Union of Operating Engineers, the Laborers' Health 
    and Safety Fund, the National Asphalt Pavement Association (NAPA), the 
    Occupational Safety and Health Administration (OSHA), manufacturers of 
    hot mix asphalt (HMA) pavers, and asphalt paving contractors.
        The participants provided detailed information on state-of-the-art 
    engineering controls currently in use and discussed a draft document on 
    guidelines for engineering controls in the asphalt paving industry that 
    was prepared jointly by labor and industry. The draft guidelines 
    provided in this announcement represent a recommendation of the 
    participants to minimize asphalt fume exposures by developing and 
    installing engineering controls on asphalt pavers and by providing 
    training for workers.
    
    Purpose
    
        The purpose of the document ``Engineering Control Guidelines for 
    Hot Mix Asphalt Pavers'' is to provide information on the use of 
    engineering controls for the reduction of worker exposure to asphalt 
    fumes during hot mix asphalt (HMA) paving operations. NIOSH is 
    soliciting public comments on the completeness and feasibility of the 
    recommendations.
    
    Document for Comment
    
    Engineering Control Guidelines for Hot Mix Asphalt Pavers
    
        On July 8-9, 1996, the National Institute for Occupational Safety 
    and Health (NIOSH) convened a public meeting in Cincinnati, Ohio, to 
    discuss recommendations for controlling exposures to asphalt fume 
    during asphalt paving operations. Participants at the meeting included 
    representatives from the Asphalt Institute (AI), the Federal Highway 
    Administration (FHWA), the International Union of Operating Engineers, 
    the Laborers' Health and Safety Fund, the National Asphalt Pavement 
    Association (NAPA), the Occupational Safety and Health Administration 
    (OSHA), manufacturers of hot mix asphalt (HMA) pavers, and asphalt 
    paving contractors. This meeting culminated in the development of these 
    guidelines that provide information about the use of engineering 
    controls (i.e., local exhaust ventilation systems) to reduce worker 
    exposures to asphalt fumes during HMA paving operations.
    1. New HMA Pavers
        a. Paver manufacturers should develop and install ventilation 
    systems with controlled indoor-capture efficiencies of at least 80% (as 
    determined by the tracer gas method described in Appendix A) on the 
    following equipment:
         All new self-propelled HMA pavers weighing 16,000 pounds 
    or more and manufactured after July 1, 1997.
         All new self-propelled HMA pavers weighing less than 
    16,000 pounds with slat conveyors or with augers detached from the 
    hoppers and manufactured after July 1, 1998.
        b. Paver manufacturers should test the ventilation systems for all 
    HMA paver models and certify that the systems meet the minimum capture 
    efficiency of 80% as specified in Section 1.a. To assure performance of 
    the ventilation systems, manufacturers should install an indicator 
    device on each HMA paver to monitor the system flow rate. Each HMA 
    paver manufacturer shall provide a plate attached to the paver that 
    shows:
          schematic of the ventilation system;
          acceptable operating range for the indicator device; and
          list of operator maintenance procedures.
    
        c. Manufacturers should develop and implement quality control plans 
    to ensure that ventilation systems on these models comply with the 
    minimum capture efficiency specified in Section 1.a.
    2. Existing HMA Pavers
        By July 1, 1998, paver manufacturers should make retrofit packages 
    available for all self-propelled HMA pavers weighing 16,000 pounds or 
    more and manufactured after July 1, 1987. These retrofit packages 
    should be installed by July 1, 1999. Retrofit packages for self-
    propelled pavers weighing less than 16,000 pounds with slat conveyors 
    or augers detached from the hopper should be available by July 1, 1999, 
    and should be installed by July 1, 2000. Manufacturers should test and 
    certify that all retrofit packages installed according to the 
    manufacturer's instructions meet the minimum capture efficiency of 80% 
    for a specific model or equivalent class design configuration (as 
    determined by the tracer gas method described in Appendix A). To assure 
    system performance, manufacturers should include in the retrofit 
    package an indicator device to monitor the system flow rate.
    3. Inspection and Maintenance
        Owners of HMA pavers with ventilation systems should inspect and 
    maintain the systems according to the manufacturer's recommendations. 
    Each manufacturer should provide an operator manual containing detailed 
    sketches and performance criteria for contractors to use in their 
    annual assessment of ventilation systems. Annual performance 
    inspections should be recorded in the operator's manual.
    4. Training Program
        The National Asphalt Pavement Association (NAPA), unions, and 
    equipment manufacturers should develop specific training criteria/
    materials (i.e., separate document) on the operation, maintenance, and 
    repair of HMA pavers.
    5. Glossary of Terms
        Asphalt Paver: A self-propelled construction machine (either 
    rubber-tired or crawler-mounted) specifically designed to receive, 
    convey, distribute,
    
    [[Page 51710]]
    
    profile, and compact paving material by the free-floating screed 
    method.
        Auger: A screw conveyor used to transversely distribute paving 
    material ahead of the screed.
        Automatic Feeder Control: A system for automatically controlling 
    the flow of paving material to the screed.
        Conveyor: A device for transferring paving material from the hopper 
    to the auger.
        Conveyor Flow Gate: A device for regulating the height of paving 
    material being transferred by the conveyor.
        Feeder System: The combined conveyor and auger components which 
    transfer paving material from the hopper and distribute it in front of 
    the screed.
        Hopper: That section of the paver which receives the paving 
    material from an external source.
        Material Feed Sensor: A device used to detect a quantity of paving 
    material in front of the screed.
        Operator: The person whose primary function is to control the 
    paver's speed and direction.
        Screed: The device which is towed behind the tractor to strike off, 
    compact, contour, and smooth the paving material.
        Screed Arm: The attachment by which the screed is connected to and 
    towed by the tractor.
        Screed End Plate: A vertically adjustable plate at the outboard end 
    of the screed, to retain the paving material and form the edge of the 
    mat.
        Screed Extension: A fixed or adjustable attachment to the screed 
    for paving at widths greater than the main screed.
        Tow Point: The point at which the screed arm is attached to the 
    tractor.
        Tractor: That portion of a paver which provides propulsion and may 
    also receive, convey, and distribute paving material.
        Tunnel: The passageway through which paving material moves from the 
    hopper to the auger/screed.
    
    Appendix A
    
    Laboratory/Factory Test Procedure
    
        Engineering controls (i.e., ventilation systems) for HMA pavers 
    will be evaluated in a laboratory setting (i.e., manufacturers' plant, 
    shop, or warehouse) in which ventilation control efficiency will be 
    measured using smoke and tracer gas tests. The smoke test will be used 
    as a qualitative test to visualize airflow patterns around the paver 
    and ventilation system, and to ensure appropriate testing conditions 
    for conducting the tracer gas tests. The tracer gas test will be used 
    to quantitatively measure the volumetric airflow rate and capture 
    efficiency of the ventilation system.
        Ventilation systems will be evaluated in a large bay area at the 
    manufacturing plant or testing shop. The paver will be parked with the 
    screed and rear half of the tractor positioned in the bay area 
    (referred to as the testing area) and with the front half of the 
    tractor and engine exhaust ducts positioned outside the building. An 
    overhead garage door or other barrier can be used to separate the two 
    areas. A garage door can be lowered to rest on top of the tractor, and 
    the remaining doorway openings around the tractor can be sealed to 
    isolate the paver's front and rear halves. The screed will rest on the 
    ground with edger plates extended one foot on each side of the screed. 
    The flow gates at the back of the hopper should be closed as far as 
    possible and the remaining tunnel opening should be blocked off. During 
    the performance evaluations the idle speed for the paver, which can 
    affect the exhaust rate of the ventilation system, will be set near the 
    typical revolutions per minute (rpm) that are maintained during normal 
    paving operations.
    Safety
        Following are safety precautions for each test:
    
         Handle smoke generating equipment that can be hot with 
    appropriate caution.
         Make sure that the smoke generators do not set off fire 
    sprinklers or create a false alarm.
         Avoid direct inhalation of smoke from the smoke generators 
    because the smoke may act as an irritant.
         Transport, handle, and store all compressed gas cylinders 
    in accordance with the safety recommendations of the Compressed Gas 
    Association.
         Store the compressed cylinder outdoors or in a well-
    ventilated area.
         Stand back and let the tank pressure come to equilibrium 
    with the ambient environment if a regulator malfunctions or some other 
    major accidental release occurs.
    Smoke Test
        A smoke generator is used to produce theatrical smoke as a 
    surrogate contaminant. The smoke is released through a perforated 
    distribution tube traversing the width of the auger area between the 
    tractor and the screed and supported above the ground under the augers. 
    The smoke test helps to identify failures in the integrity of the 
    barrier separating the front and rear portions of the paver. After 
    sealing leaks within this barrier, smoke is again released to verify 
    the integrity of the barrier system, to identify airflow patterns 
    within the test area, and to visually observe the ventilation system's 
    performance.
        The sequence of a typical smoke test is outlined below:
    
         Position paving equipment within door opening and lower 
    the overhead door.
         Seal the remaining door opening around the tractor.
         Place the smoke distribution tube directly underneath the 
    auger.
         Connect the smoke generator to the distribution tube (PVC 
    pipe, 2-inch diameter, 10 feet long, capped on one end, \1/4\-inch 
    diameter holes every 6 inches on-center).
         Activate video camera if a record is desired.
         Activate the ventilation system and the smoke generator.
         Inspect the separating barrier for integrity failures and 
    correct as required.
         Inspect the ventilation system for unintended leaks.
         De-activate the ventilation system for comparison 
    purposes.
         De-activate the smoke generator and wait for smoke levels 
    to subside.
         Disassemble test equipment.
    Tracer Gas
        The tracer gas test is designed to: (1) calculate the total 
    volumetric exhaust flow of the prototype design; and (2) evaluate the 
    effectiveness in capturing and controlling a surrogate contaminant 
    under the ``controlled'' indoor conditions. Sulfur hexafluoride 
    (SF6) will be used as the surrogate contaminant. A real-time 
    SF6 detector should be calibrated in the laboratory prior to the 
    test. There are several methods for calibrating the SF6 detector. 
    The least labor-intensive method requires the use of multiple 
    compressed gas cylinders with known concentrations of SF6. The 
    SF6 concentrations should include at least four concentrations 
    ranging from zero to 50 ppm SF6 in nitrogen. An industrial hygiene 
    sampling bag such as a 12-liter Milar bag can be filled from 
    each cylinder, then the bag can be hooked to the detector, and the 
    response of the detector can be recorded for each concentration.
        Another method for calibrating the SF6 detector requires the 
    use of two compressed gas cylinders, one with pure nitrogen and another 
    with 50 ppm (or higher concentration) SF6 in nitrogen. Four 
    different concentrations of SF6 are made by mixing different 
    volumes of fluid from the two cylinders into sampling bags. The bags 
    are mixed, hooked to the detector, and the response of the detector is 
    recorded for each concentration.
    
    [[Page 51711]]
    
        The sampling bags should be clearly marked with the appropriate 
    concentration of SF6 that each contains. Bags can be reused; 
    however, they should be emptied prior to reuse and they should only be 
    filled with approximately the same concentration of SF6. A bag 
    used to hold 50 ppm SF6 in a previous test should not be used to 
    hold the 2 ppm SF6 sample in the next test because of the 
    possibility of residual gas causing an incorrect calibration point.
        Using either calibration method or an equivalent method, a 
    calibration curve, not necessarily a straight line, can then be 
    calculated to fit the data and convert the detector's response to an 
    actual SF6 concentration.
        To increase the likelihood of independence for each SF6 
    concentration reading, program the SF6 detector to a minimum 
    sampling interval of 30 seconds. Larger intervals may be required based 
    on the model of SF6 detector and the experimental setup.
        100% Capture (to quantify exhaust volume): A known volumetric flow 
    rate (0.90 liters per minute) of SF6 is released into the 
    ventilation system. The release point must be upstream of the 
    ventilation system's fan and downstream of the ventilation system's 
    hood to ensure 100% capture of the released gas. The supply tank of 
    pure SF6 is connected to the release point via a pressure 
    regulator, flow controller, and \1/4\-inch tubing.
        A \1/4\-inch diameter hole is placed in the ventilation system's 
    exhaust duct half way between the fan and the outlet of the exhaust 
    dust. A 12-inch long and \1/4\-inch outside diameter stainless steel 
    tube (sampling probe) is inserted into this exhaust-duct hole 
    perpendicular to the exhaust air flow. The sampling probe should be 
    sealed at the end and have several \1/8\-inch diameter holes, one inch 
    on-center along one side. The number of holes depends on the diameter 
    of the exhaust duct. An 8-inch exhaust duct would require use of a 
    sampling probe with six \1/8\-inch holes. These holes should be 
    positioned perpendicular to the exhaust air flow and must all be inside 
    the duct when sampling. The tubing connecting the sampling probe to the 
    detector should be airtight to ensure that the sample is pulled from 
    within the exhaust duct and not from the surrounding area. The exhaust 
    volume is then calculated using the following equation:
    
    where
        Q(exh)=volume of air exhausted through the ventilation system (lpm 
    or cfm) (To convert from liters per minute (lpm) to cubic feet per 
    minute (cfm), divide lpm by 28.3.)
        Q(SF6)=volume of SF6 (lpm or cfm) introduced into the 
    system
        C*(SF6)=Concentration of SF6 (parts per million) detected 
    in exhaust and the * indicates 100% capture of the released SF6.
    
        If there is more than one ventilation system exhaust duct, then the 
    above procedure should be repeated for each. Sufficient time should be 
    allowed between tests for the background readings to drop to below 0.2 
    ppm SF6. Background readings must be subtracted from the detector 
    response before calculating the exhaust volume.
        To quantify capture efficiency, SF6 is released through a 
    distribution plenum located under the augers between the tractor and 
    the screed. A discharge hose feeds pure SF6 at a flow rate of 0.90 
    lpm from the pressure regulator, through a mass flow controller 
    (precision rotameter), and into the distribution plenum. Accuracy of 
    the flow controller will greatly affect the accuracy of the test and 
    should be #3% or better. The plenum is ten feet long and is designed to 
    release the SF6 evenly throughout its length. The same multi-port 
    sampling wand, sampling location, and detector, as used in the 100% 
    capture test, is also used in this test.
        At least five consecutive measurements will be taken and an average 
    value will be calculated. If the SF6 volumetric flow rate is the 
    same for both the 100% capture test and capture efficiency test, then 
    the capture efficiency is calculated using the following equation:
    
    where
        =capture efficiency
        C(SF6)=Concentration of SF6 (parts per million) detected 
    in exhaust
        C*(SF6)=Concentration of SF6 from 100% capture test
    
        If the SF6 volumetric flow rate is not the same for both the 
    100% capture test and the capture efficiency test, then the capture 
    efficiency is calculated using the following:
    
    where C(SF6) and Q(SF6) refer to the values obtained during 
    the capture efficiency test and Q(exh) was calculated from the 100% 
    capture test.
        A total of four pairs of the 100% capture tests and capture 
    efficiency tests will be performed with the ventilation system's 
    overall capture efficiency determined from the average of all four 
    trials.
        Between each test (after a pair of 100% capture test and capture 
    efficiency test), the paver should be shut down and background SF6 
    measurements should be monitored to determine if any SF6 had 
    accumulated in the test area. If SF6 has accumulated (>2.0 ppm), 
    the integrity of the barrier system should be checked and the test area 
    should be well ventilated before proceeding. Sufficient time should be 
    allowed between tests for the background readings to drop to below 0.2 
    ppm of SF6. Background readings must be subtracted from the 
    detector response before calculations are made.
        The sequence for a typical test run is outlined below:
         Position paving equipment and seal openings as outlined 
    above.
         Calibrate (outdoors) flow meters at approximately 0.9 lpm 
    of SF6.
         Drill an access hole in the ventilation system's exhaust 
    duct for insertion of the detector's sampling probe and position the 
    sampling probe into the exhaust duct.
         With the ventilation system activated, begin monitoring 
    for SF6 to determine background interference levels.
         While maintaining the SF6 tanks outdoors or in a 
    well-ventilated area, run the discharge tubing from the mass flow meter 
    to well within the exhaust hood to create 100% capture conditions.
         Initiate flow of SF6 through the flow meter and allow 
    it to reach steady-state (should take only a minute).
         Continue monitoring until 5 readings are recorded.
         Deactivate the flow of SF6.
         Remove the discharge tubing to an outdoor location.
         End the 100% capture test. (Leave the tractor engine 
    running.)
         Initiate monitoring to establish background interference 
    until levels drop to <0.2 ppm.=""> Locate an SF6 distribution plenum under the auger 
    area and connect the discharge tubing of the flow meter.
         Initiate SF6 flow through the mass flow meters and 
    monitor until approximate steady-state conditions appear (about one 
    minute) and take at least 5 readings.
         Discontinue SF6 flow and quickly remove the 
    distribution plenum and discharge tubing from the auger area and remove 
    to an outside location.
         Continue monitoring to determine the general area 
    concentration of SF6 which escaped into the test area.
         Discontinue monitoring when concentration decay is 
    complete.
         Turn off the ventilation system and paver engine; 
    calculate the capture efficiency.
         Repeat four times.
    
    Example Test Run and Calculations
    
        The paver was positioned and smoke was used to visually test the 
    system.
    
    [[Page 51712]]
    
    Smoke was seen coming in the top of the overhead door. The opening in 
    the overhead door was sealed and the smoke test revealed no other 
    problems.
        For simplicity of example, the SF6 detector was calibrated and 
    adjusted to read directly SF6 in ppms. The SF6 flow meter was 
    calibrated using a bubble meter.
    
    ------------------------------------------------------------------------
                                                                  Flow rate,
                             Trial No.                               lpm    
    ------------------------------------------------------------------------
    1..........................................................        0.903
    2..........................................................        0.908
    3..........................................................        0.899
    4..........................................................        0.900
    ------------------------------------------------------------------------
    
        The mean flow rate was ((0.903 + 0.908 + 0.899 + 0.900)/ 4)) 0.903 
    liters per minute (lpm).
        The sampling probe was placed in the exhaust duct of the 
    ventilation system and background samples were registered by the 
    detector. The tubing (pure SF6 outlet) from the flow meter was 
    placed through the hood and into the duct of the ventilation system 
    (upstream of the fan). Readings were as follows:
    
    ------------------------------------------------------------------------
                                                                  Detector  
                         Task                      Reading No.  reading, ppm
                                                                   of SF 6  
    ------------------------------------------------------------------------
    Background...................................            1        0.0051
                                                             2        0.0062
                                                             3        0.0048
                                                             4        0.0050
                                                             5        0.0066
                                                             6        0.0062
                                                             7        0.0058
    Start SF6....................................            8        6.3   
                                                             9       22.0   
                                                            10       21.8   
                                                            11       21.9   
                                                            12       21.7   
                                                            13       21.8   
    End..........................................           14       21.9   
    ------------------------------------------------------------------------
    
        At least five consecutive measurements are needed; in this case, 
    the last six data points were used. The eighth reading (6.3 ppm) does 
    not reflect steady-state and was not used in determining the average. 
    The mean concentration of SF6 is 21.85 ppm (the average of those 
    six points). The mean background value is 0.0057 ppm. These values were 
    used to calculate the volumetric flow rate from Equation 1.
    
    Q(exh)+0.903 / 28.3 / (21.85-0.0057) * 106 = 1460 cfm.
    
        The average background value, 0.0057 ppm, was subtracted from the 
    average 100% capture value, 21.85 ppm. In this case, the background 
    value was negligible.
        The same flow meter and SF6 flow rate were used for the 
    capture efficiency test. The tubing was removed from the ventilation 
    system hood and connected to the 10-foot distribution plenum. Readings 
    were as follows:
    
    ------------------------------------------------------------------------
                                                                  Detector  
                         Task                      Reading No.  reading, ppm
                                                                     SF6    
    ------------------------------------------------------------------------
    Background...................................            1         0.092
                                                             2         0.084
                                                             3         0.078
    Start SF 6...................................            4        28.1  
                                                             5        18.8  
                                                             6        19.6  
                                                             7        19.7  
                                                             8        20.9  
                                                             9        17.3  
                                                            10        19.4  
                                                            11        18.9  
                                                            12        19.6  
    ------------------------------------------------------------------------
    
        At least five consecutive measurements are needed; in this case, 
    the last eight will be used. The fourth reading (28.1 ppm) was high; in 
    this case it reflects the flow controller overshooting the set point 
    during the startup of SF6 flow, and this point is not used in 
    determining the average. The mean concentration of SF6 is 19.28 
    ppm; the average background concentration was 0.0847 ppm.
        Because we used the same SF6 flow rate in both the exhaust 
    volume test and the capture efficiency test, the calculations are 
    simplified. From Equation 2, the capture efficiency is (19.28-.0847) / 
    (21.85-0.0057)* 100 = 87.9%.
        This procedure was done four times with the following results:
    
    ------------------------------------------------------------------------
                                            100%      Capture      Capture  
                 Trial No.                capture,  efficiency,  efficiency,
                                          ppm SF 6    ppm SF 6        %     
    ------------------------------------------------------------------------
    1..................................      21.84       19.20         87.9 
    2..................................      21.67       19.95         92.1 
    3..................................      21.74       18.10         83.3 
    4..................................      21.93       19.01         86.7 
    ------------------------------------------------------------------------
    
    Statistics
    
        Calculate the overall average of the means:
    
    m = (87.9 + 92.1 + 83.3 + 86.7) / 4 = 87.5%
    
        Calculate the estimated standard deviation:
    
    s={((87.9-87.5)2 + (92.1-87.5)2 + (83.3-87.5)2 + (86.7-87.5)2) / 
    (4-1)}0.5
        ={ (0.16 + 21.16 + 17.64 + 0.64) / 3}0.5 = 3.63
    
        If the number of trials, n, is different from 4, then (n-1) is used 
    in the denominator of this calculation and the numerator is the sum of 
    all n squared differences, rather than just 4. Choose the number t 
    (from the Student's t-distribution table at the 95th percentile) from 
    the following table, based on the value of n:
    
    t: 6.31 (n=2) 2.92 (n=3) 2.35 (n=4)
        2.13 (n=5) 2.02 (n=6) 1.94 (n=7)
        1.90 (n=8) 1.86 (n=9) 1.83 (n=10)
    
        Calculate a test statistic (T):
    
    T=m-t*s / n0.5
    
        For this example: T = 87.5-2.35 * 3.63 / 40.5 = 83.2.
        If T > 80.0, then decide (with 95% confidence) that efficiency is 
    greater than 80%. In this example, we are 95% confident that the 
    efficiency is greater than 80%.
        If T  80.0, then the conclusion that the efficiency is 
    greater than 80% cannot be made from these data.
    
    Equipment
    
    Smoke Test
    Smoke generator
    2 inch x 10 foot Schedule-40 PVC perforated distribution pipe
    Tracer Gas Tests
    Compressed cylinder of 99.98% SF6 with regulator
    Flow controller such as a precision rotameter
    \1/8\-inch ID x 20-foot Teflon tubing and snap valves for SF6 
    distribution
    Primary Flow Calibrator
    \1/2\-inch ID x 10-foot Copper tubing with \1/32\-inch holes every 12 
    inches SF6 distribution plenum
    Gas monitor calibrated for SF6
    Calibration gases, nitrogen and at least one SF6 concentration in 
    nitrogen
    12-liter Mylar gas sampling bags
    Ventilation System Evaluation
    Air Velocity Meter
    Micro manometer w/Pitot Tube
    
        Dated: September 27, 1996.
    Linda Rosenstock,
    Director, National Institute for Occupational Safety and Health Centers 
    for Disease Control and Prevention (CDC).
    [FR Doc. 96-25314 Filed 10-2-96; 8:45 am]
    BILLING CODE 4163-19-P
    
    
    

Document Information

Published:
10/03/1996
Department:
Health and Human Services Department
Entry Type:
Notice
Action:
Request for comments.
Document Number:
96-25314
Dates:
Written comments to this notice should be submitted to Diane Manning, NIOSH Docket Office, 4676 Columbia Parkway, Mailstop C-34, Cincinnati, Ohio 45226. Comments must be received on or before November 4, 1996.
Pages:
51708-51712 (5 pages)
PDF File:
96-25314.pdf