95-28028. Nebraska Public Power District, Cooper Nuclear Station; Environmental Assessment and Finding of No Significant Impact  

  • [Federal Register Volume 60, Number 219 (Tuesday, November 14, 1995)]
    [Notices]
    [Pages 57250-57252]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 95-28028]
    
    
    
    =======================================================================
    -----------------------------------------------------------------------
    
    NUCLEAR REGULATORY COMMISSION
    
    [Docket No. 50-298]
    
    
    Nebraska Public Power District, Cooper Nuclear Station; 
    Environmental Assessment and Finding of No Significant Impact
    
        The U.S. Nuclear Regulatory Commission (the Commission) is 
    considering the issuance of an exemption from certain requirements of 
    its regulations to Facility Operating License Number DPR-46. This 
    license was issued to the Nebraska Public Power District (the licensee) 
    for operation of the Cooper Nuclear Station (CNS) located in Nemaha 
    County, Nebraska.
    
    Environmental Assessment
    
    Identification of the Proposed Action
    
        The licensee requested, in its application dated May 13, 1994, an 
    exemption from the pressure test requirements of Section III.D.2(b)(ii) 
    of Appendix J, ``Primary Reactor Containment Leakage Testing For Water-
    Cooled Power Reactors,'' to 10 CFR Part 50 (Appendix J to 10 CFR Part 
    50). The staff discussed the details of the proposed exemption with the 
    licensee in a telephone conference call on September 28, 1995. The 
    proposed exemption would allow the licensee to leak test the personnel 
    air lock at CNS at a test pressure less than Pa, (the calculated 
    peak containment internal pressure resulting from the containment 
    design basis accident), under certain conditions. The reduced pressure 
    test of the air lock would be conducted as the first of two tests 
    during a restart from refueling or cold shutdown, prior to entry into 
    an operational mode requiring containment leaktight integrity by the 
    CNS Technical Specifications (TSs). As stated in CNS TS 4.7.A.2.f.5, 
    for periodic leakage testing of the personnel air lock, Pa is 58 
    psig and the reduced test pressure is 3 psig.
        This leakage test is part of the Type B tests required by Appendix 
    J to 10 CFR Part 50 to verify containment integrity. Because an air 
    lock allows entry into the containment and is part of the containment 
    pressure boundary, excessive leakage through the air lock could 
    compromise containment integrity. The air lock consists of an inner and 
    outer door and the leakage test is performed by pressurizing the space 
    between the doors. 
    
    [[Page 57251]]
    
    
    The Need for the Proposed Action
    
        Section III.D.2 of Appendix J to 10 CFR Part 50 specifies the 
    required periodic retest schedule for Type B tests, including testing 
    of air locks. Pursuant to Section III.D.2(b)(ii), licensees are 
    required to leakage test air locks, opened during periods when 
    containment integrity is not required by the TSs, at the end of such 
    periods. This section applies to testing of air locks during restart 
    from refueling or cold shutdown because the CNS TSs do not require 
    containment integrity for either of these operational modes. This 
    section states that the air lock test shall be performed at a pressure 
    that is not less than Pa.
        The proposed exemption is concerned with Section III.D.2(b)(ii); 
    however, there are two other sections in Appendix J which have 
    requirements on testing air locks. Section III.D.2(b)(i) requires an 
    air lock test every 6 months at a test pressure of Pa and, as 
    relevant here, Section III.D.2(b)(iii) requires a test every 3 days 
    when the air lock is used during a period when containment integrity is 
    required by the TSs. The latter section requires the test pressure to 
    be Pa, or the test pressure specified in the TSs, which for CNS is 
    stipulated as 3 psig in TS 4.7.A.2.f.5.
        The licensee stated in its application that it currently tests the 
    personnel air lock twice during the restart of the plant for power 
    operation from refueling or cold shutdown: (1) Prior to the reactor 
    being taken critical, or the reactor water temperature being above 
    100 deg.C (212 deg.F), and (2) after the last entry into containment 
    for leak inspection during restart. The time between the two tests is 
    about 24 to 48 hours, and the second test is at low reactor power prior 
    to entry into the run mode, the full power mode of operation.
        The first test is in accordance with Section III.D.2(b)(ii) and is 
    performed at the conclusion of the period when containment integrity is 
    not required by the TSs. This test is conducted prior to entry into an 
    operational mode requiring containment integrity. The second test is in 
    accordance with Section III.D.2(b)(iii) and is performed at 3-day 
    intervals while the air lock is being used when containment integrity 
    is required. As stated above, in accordance with this section, the 
    second test could be conducted at a test pressure of 3 psig at CNS 
    because this pressure is stated in TS 4.7.A.2.f.5. However, because the 
    licensee also performs the second test to meet the 6-month interval 
    requirement in Section III.D.2(b)(i), the second test is conducted at 
    Pa. If this second test is not necessary to satisfy the 6-month 
    interval test requirement, there is no requirement that the licensee 
    conduct it at Pa.
        When no maintenance or repairs have been performed on the air lock 
    that could affect its sealing capability and the periodic 6-month test 
    at Pa has been performed successfully, opening of the air lock 
    during a plant shutdown or refueling outage is not a reason to expect 
    it to leak in excess of the requirements. When the air lock is tested 
    at a pressure less than Pa in preparation for restart from 
    refueling or cold shutdown, under such conditions, and the air lock has 
    been successfully tested at Pa within the previous six months, 
    containment integrity is assured. If, however, maintenance or repairs 
    have been performed on the air lock affecting its sealing capability 
    since the last 6-month test, the first test prior to entering a 
    condition which requires containment integrity must meet the test 
    pressure requirements of Section III.D.2(b)(ii) and be conducted at a 
    test pressure not less than Pa.
        In testing the air lock at reduced pressure, a strongback 
    (structural bracing) would not have to be installed on the inner air 
    lock door. During the test, the space between the inner and outer doors 
    is pressurized. The strongback is needed when the test pressure is 
    Pa because the pressure exerted on the inner door during the test 
    is in a direction opposite to the pressure on the inner door during an 
    accident, and Pa is sufficiently high to damage the inner door 
    during the test without the strongback. The reduced pressure test would 
    be conducted at 3 psig, and the strongback would not be needed to 
    protect the inner door during the test.
        Installing a strongback, performing the test, and removing the 
    strongback requires several hours during which access through the air 
    lock is prohibited. The strongback is attached to the door inside 
    containment where personnel would be exposed to radiation inside 
    containment. The reduced pressure test could be conducted without the 
    strongback and, thus, in a shorter time with less occupational exposure 
    to CNS personnel involved with the test. Because the second test is 
    conducted at Pa, not performing the first test at Pa will 
    reduce the number of such tests using strongbacks and, therefore, will 
    reduce the time involved in performing the tests and the magnitude of 
    occupational exposure at CNS.
        The licensee is, therefore, proposing to conduct the first test 
    during restart at a test pressure of 3 psig, which is less than 
    Pa, which is not presently allowed by Section III.D.2(b)(ii). The 
    air lock leakage measured for the reduced test pressure would be 
    extrapolated to a value consistent with Pa, then that value would 
    be compared to the acceptance criteria in Appendix J for Type B tests 
    to confirm that containment integrity is verified. If containment 
    integrity is verified, the measured air lock leakage is considered 
    acceptable.
    
    Environmental Impacts of the Proposed Action
    
        The Commission has completed its evaluation of the licensee's 
    request. The proposed exemption does not change the number of air lock 
    tests to verify containment integrity upon plant restart, the manner in 
    which the second test is conducted, the time when the tests would be 
    conducted, nor the acceptance criteria for the tests. Thus, the 
    assurance of containment integrity would be maintained at a level 
    consistent with current Appendix J requirements. The proposed exemption 
    would also not change other requirements in Appendix J for periodic 
    testing of the air lock at Pa, and would not change the existing 
    CNS safety limits, safety settings, power operations, or effluent 
    limits. The proposed exemption would effectively replace the test 
    pressure requirement in Section III.D.2(b)(ii) with that in Section 
    III.D.2(b)(iii), in that the latter section allows for reduced pressure 
    testing of air locks in accordance with plant TSs.
        The change will not increase the probability or consequences of 
    accidents, no changes are being made in the types of any effluents that 
    may be released offsite, and there is no significant increase in the 
    allowable individual or cumulative occupational radiation exposure. 
    Accordingly, the Commission concludes that there are no significant 
    radiological environmental impacts associated with the proposed action.
        With regard to potential nonradiological impacts, the proposed 
    action does involve features located entirely within the restricted 
    area as defined in 10 CFR Part 20. It does not affect nonradiological 
    plant effluents and has no other environmental impact. Accordingly, the 
    Commission concludes that there are no significant nonradiological 
    environmental impacts associated with the proposed action.
    
    Alternatives to the Proposed Action
    
        Since the Commission has concluded that there is no measurable 
    environmental impact associated with the proposed action, any 
    alternatives with equal or greater environmental impact need not be 
    evaluated. As an alternative to the proposed action, the staff 
    considered denial of the requested 
    
    [[Page 57252]]
    exemption. Denial of the application would result in no change in 
    current environmental impacts. The environmental impacts of the 
    proposed action and the alternative action are similar, but the 
    proposed action would reduce occupational exposure at CNS.
    
    Alternative Use of Resources
    
        This action does not involve the use of any resources not 
    previously considered in the Final Environmental Statement for the 
    Cooper Nuclear Station, dated February 1973.
    
    Agencies and Persons Consulted
    
        In accordance with its stated policy, on October 19, 1995, the 
    staff consulted with the Nebraska State official, Ms. Julia Schmidt, 
    Division of Radiological Health, Nebraska Department of Health, 
    regarding the environmental impact of the proposed action. The State 
    official had no comments.
    Finding of No Significant Impact
        Based upon the environmental assessment, the Commission concludes 
    that the proposed action will not have a significant effect on the 
    quality of the human environment. Accordingly, the Commission has 
    determined not to prepare an environmental impact statement for the 
    proposed action.
        For further details with respect to this action, see the licensee's 
    request for an exemption dated May 13, 1994, which is available for 
    public inspection at the Commission's Public Document Room, The Gelman 
    Building, 2120 L Street, NW, Washington, DC, and at the local public 
    document room located at the Auburn Public Library, 118 15th Street, 
    Auburn, Nebraska 68305.
    
        Dated at Rockville, Maryland, this 6th day of November 1995.
    
        For the Nuclear Regulatory Commission.
    James R. Hall,
    Senior Project Manager, Project Directorate IV-1, Division of Reactor 
    Projects III/IV, Office of Nuclear Reactor Regulation.
    [FR Doc. 95-28028 Filed 11-13-95; 8:45 am]
    BILLING CODE 7590-01-P
    
    

Document Information

Published:
11/14/1995
Department:
Nuclear Regulatory Commission
Entry Type:
Notice
Document Number:
95-28028
Pages:
57250-57252 (3 pages)
Docket Numbers:
Docket No. 50-298
PDF File:
95-28028.pdf