96-29459. All Nuclear Power Plants; Issuance of Director's Decision Under 10 CFR 2.206  

  • [Federal Register Volume 61, Number 223 (Monday, November 18, 1996)]
    [Notices]
    [Pages 58711-58715]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 96-29459]
    
    
    =======================================================================
    -----------------------------------------------------------------------
    
    
    NUCLEAR REGULATORY COMMISSION
    
    All Nuclear Power Plants; Issuance of Director's Decision Under 
    10 CFR 2.206
    
        Notice is hereby given that the Director, Office of Nuclear Reactor 
    Regulation, has taken action with regard to a Petition dated March 5, 
    1996, by Mr. C. Morris. The Petition pertains to all operating nuclear 
    power plants.
        In the Petition, the Petitioner requested that the operating 
    licenses of all nuclear power plants be suspended within 90 days and 
    remain suspended until such time as the licensees of those plants 
    discovered the reason for what the Petitioner asserts are repeated 
    errors in the undervoltage relay (UVR) setpoints (SPs) and electrical 
    distribution system (EDS) designs and provided convincing evidence that 
    these deficiencies had finally been corrected. Since the Petitioner had 
    requested action within 90 days, the request was treated as a request 
    for immediate relief. The Petitioner also requested that the 
    aforementioned evidence be reviewed by a competent third party, in 
    addition to the staff of the U.S. Nuclear Regulatory Commission (NRC), 
    and that if the NRC concludes that plants may safely operate with UVRs 
    that cannot be properly set for long periods, the NRC should reach 
    these conclusions by way of a public meeting.
        The Director of the Office of Nuclear Reactor Regulation has denied 
    the Petition. The reasons for this denial are explained in the 
    ``Director's Decision Under 10 CFR 2.206'' (DD-96-12), the complete 
    text of which follows this notice and is available for public 
    inspection at the Commission's Public Document Room, the Gelman 
    Building, 2120 L Street, NW., Washington, DC.
        A copy of the decision will be filed with the Secretary of the 
    Commission for the Commission's review in accordance with 10 CFR 
    2.206(c) of the Commission's regulations. As provided by this 
    regulation, the decision will constitute the final action of the 
    Commission 25 days after issuance unless the Commission, on its own 
    motion, institutes review of the decision in that time.
    
        Dated at Rockville, Maryland, this 26th day of September 1996.
    
    
    [[Page 58712]]
    
    
    For the Nuclear Regulatory Commission.
    William T. Russell,
    Director, Office of Nuclear Reactor Regulation.
    
    Director's Decision Under 10 CFR 2.206
    
    I. Introduction
    
        On March 5, 1996, Mr. Charles Morris (Petitioner) filed a Petition 
    with the Executive Director for Operations pursuant to Section 2.206 of 
    Title 10 of the Code of Federal Regulations (10 CFR 2.206). The 
    Petitioner requested that the operating licenses of all nuclear power 
    plants be suspended within 90 days and remain suspended until such time 
    as those plants have (1) discovered the reason for what the Petitioner 
    asserts are repeated errors in the undervoltage relay (UVR) setpoints 
    (SPs) and electrical distribution system (EDS) designs and (2) provided 
    convincing evidence that these deficiencies have finally been 
    corrected. Since the Petitioner had requested action within 90 days, 
    the request was treated as a request for immediate relief. The 
    Petitioner also requested that the aforementioned evidence by reviewed 
    by a competent third party, in addition to the Nuclear Regulatory 
    Commission (NRC) staff, and that if the NRC concludes that plants may 
    safely operate with UVRs that cannot be properly set for long periods 
    of time, the NRC should reach these conclusions by way of a public 
    meeting.
        On April 17, 1996, the Petitioner was informed that the request for 
    the suspension of all nuclear power plant licenses within 90 days for 
    the purposes of remedying repeated errors in UVR SPs and EDS designs 
    was denied because licensees have, to a large degree, already addressed 
    the issues which the Petitioner had raised. Also the Petitioner was 
    informed that the request was being evaluated pursuant to 10 CFR 2.206 
    of the NRC's regulations and that a decision, as provided by 10 CFR 
    2.206, would be made on the request within a reasonable time.
        On the basis of my review of the issues raised by the Petitioner as 
    discussed below, I have conclude that no substantial health and safety 
    issues have been raised that would require the initiation of the action 
    requested by the Petitioner.
    
    II. Discussion
    
        In his Petition, the Petitioner stated his concern that the 
    ``enduring and widespread nature of the electrical distribution system 
    (EDS) an undervoltage rely (UVR) setpoint (SP) errors (e.g., incorrect 
    UVR and thermal overload setpoints) was recognized by neither the 
    licensees nor the NRC staff,'' and was not included in NRC Information 
    Notice (IN) 93-99, ``Undervoltage Relay and Thermal Overload Setpoint 
    Problems.''
        IN 93-99 did, in fact, inform all holders of operating licenses or 
    contruction permits of the widespread nature of the setpoint errors by 
    listing approximately 40 licensees with incorrectly set UVRs or thermal 
    overload (TOL) protective devices. The identification of these problems 
    was not inadvertent, but was the result of concerted NRC staff 
    attention to these issues. As was indicated to the Petitioner in an 
    April 17, 1996, letter acknowledging receipt of his March 5, 1996, 10 
    CFR 2.206 Petition, the Petitioner himself recognized that Electrical 
    Distribution System Functional Inspections (EDSFIs) were highlighting 
    these issues and that licensees were conducting self-initiated design 
    basis reviews (possibly in anticipation of pending EDSFIs) to identify 
    problems and were undertaking corrective actions.
        In his March 5, 1996, Petition, the Petitioner listed seven 
    specific reasons that he believed caused repeated EDS and UVR 
    deficiencies. The following is a description of each concern 
    accompanied by the NRC staff's response:
        1. The Petitioner stated that NRC Branch Technical Position PSB-1, 
    ``Adequacy of Station Electric Distribution System Voltages,'' 
    contained in NUREG-0800, ``Standard Review Plan for the Review of 
    Safety Analysis Reports for Nuclear Power Plants,'' which requires a 
    degraded voltage relay with a long delay and a loss of power relay with 
    a short delay, is inadequate because it does not recognize the 
    complexity of the matter. Except for the arbitrary time delays 
    associated with the UVRs, no recognition has been made of voltage 
    dynamics and time dependence. Signal bandwidths, responses of tap 
    changing transformers, and UVR time delays have been overlooked and 
    should be considered.
    
    Response
    
        NRC Branch Technical Position PSB-1 does not recommend that 
    licensees arbitrarily select time delays for UVRs. On the contrary, 
    PSB-1 states that ``the selection of undervoltage and time delay 
    setpoints shall be determined from an analysis of the voltage 
    requirements of the Class 1E loads at all onsite system distributions 
    levels.'' Further, it states that ``Tap settings selected should be 
    based on an analysis of the voltage at the terminals of the Class 1E 
    loads. The analyses performed to determine minimum operating voltages 
    should typically consider maximum unit steady state and transient loads 
    * * *'' Additionally, ``the first time delay should be of a duration 
    that established the existence of a sustained degraded voltage 
    condition (i.e., something longer than a motor starting transient)'' 
    and ``the second time delay should be of a limited duration such that 
    the permanently connected Class 1E loads will not be damaged.''
        Therefore, the staff concludes the NRC Branch Technical Position 
    PSB-1 is adequate as it addresses those topics which the Petitioner 
    believes are neglected by the Branch Technical Position.
        2. The Petitioner asserted that UVR tolerances are statistical in 
    nature and not, as the staff and design engineers often regard 
    them,limits to the errors in the relay setpoints. This is a significant 
    problem which may not be solved if previous approaches are utilized and 
    decision analysis is not applied to study the consequences of 
    attempting to prevent the occasional loss of the most vulnerable safety 
    load at the expense of transferring a complete division to another 
    power source with attendant problems.
    
    Response
    
        Regulatory Guide 1.105, ``Instrument Setpoints for Safety-Related 
    Systems,'' states that ISA-S67.04-1982, ``Setpoints for Nuclear Safety-
    Related Instrumentation Used in Nuclear Power Plants,'' establishes NRC 
    staff guidance for ensuring that instrument setpoints in safety-related 
    systems are initially within and remain within the technical 
    specification limits. Section 4.3.1 of ISA-S67.04 states that 
    instrument accuracies (uncertainties, errors or tolerances) may be 
    combined in one of five ways: algebraically, square root of the sum of 
    the squares, statistically, probabilistically, or combinations of the 
    first four. Justification is to be provided for the method used.
        Regulatory Guide 1.105 expands upon this point:
    
        Paragraph 4.3 of the standard specifies the methods for 
    combining uncertainties is determining a trip setpoint and its 
    allowable values. Typically, the NRC staff has accepted 95% as a 
    probability limit for errors. That is, of the observed distribution 
    of values for a particular error component in the empirical data 
    base, 95% of the data points will be bounded by the value selected. 
    If the data base follows a normal distribution, this corresponds to 
    an error distribution approximately equal to a ``two sigma'' value.
    
        Although the use of ``two sigma'' values (value equal to twice the 
    standard deviation of the errors) does
    
    [[Page 58713]]
    
    not completely ensure that the measured parameter will not exceed the 
    safety analysis limit without accompanying protective action, the 
    probability of all the individual error occurring simultaneously at 
    this extreme, non-conservative, random values is very low. Therefore, 
    the regulatory guide and the industry standard together support a 
    credible, statistical approach for establishing setpoints that 
    considers such things as sample size of error values, random versus 
    non-random errors, and independence of errors.
        The preparatory training for EDSFI team members also did not 
    overlook the statistical nature of the UVR tolerances. In Section 4.8.2 
    of the EDSFI training textbook, a discussion of instrumentation 
    setpoint problems was provided with a sample application of ISA-S67.04 
    to degraded voltage relays. This methodology was also discussed in the 
    course itself. Using this knowledge EDFSIs were conducted and findings 
    were written covering improper degraded voltage relay setpoints. As a 
    result, licensees then followed this action with event notification and 
    other activities as described in Information Notice 93-99.
        Additionally, in response to a request from Region III pertaining 
    to an unanalyzed degraded voltage concern at Perry Nuclear Power Plant, 
    the Electrical Engineering Branch (EELB) of NRR in an April 13, 1992, 
    memo provided inspectors in NRC Regional Offices with guidance for 
    establishing an adequate setpoint for the degrade voltage relays by way 
    of reference to Section 4.8.2 of the EDSFI training course manual and 
    Regulatory Guide 1.105. Furthermore, the staff informed all holders of 
    operating licenses about a statistical approach for establishment of 
    UVR setpoints when 91-29, ``Deficiencies Identified during Electrical 
    Distribution Functional Inspections,'' made reference to ISA-S67-04-
    1982 for useful guidance in determination of setpoints.
        The staff therefore has regarded the UVR setpoint determinations as 
    statistical in nature.
        3. The Petitioner stated that although General Design Criterion 
    (GDC) 17, ``Electric power systems,'' requires all EDS to be testable, 
    only parts are tested because plants cannot conveniently be placed in a 
    condition where actual loads can be placed on the EDS and measured.
    
    Response
    
        The staff has already been aware that in certain situations it is 
    not practical nor safe to test each and every component in the exact 
    way it is used. General Design Criterion 18, ``Inspection and testing 
    of electrical power system,'' states that ``systems shall be designed 
    with a capability to test periodically * * * the operability of the 
    systems as a whole and, under conditions as close to design as 
    practical * * *.'' Regulatory Guide 1.118, ``Periodic Testing of 
    Electric Power and Protection Systems,'' Revision 2, endorses, IEEE Std 
    338-1977, ``Criteria for the Periodic Testing of Nuclear Power 
    Generating Station Safety Systems,'' which states that ``the test 
    program of each system shall be designed to provide for interference 
    with related operational channels, systems, or equipment.'' It further 
    states that `'wherever possible, tests shall be accomplished under 
    actual or simulated operating conditions, including sequence of 
    operations, for example, diesel load sequencing,'' but also
    
        Where it is not practicable to initiate the protective action, 
    the system shall be designed such that * * * Designs * * * shall be 
    justified on the basis that there is no practical system design that 
    would permit operation of the actuated equipment without adversely 
    affecting the safety or operability of the plant, and that the 
    probability of failure of actuated equipment not tested during plant 
    operation is acceptably low, and that the actuated equipment can be 
    routinely tested when the plant is shut down.
    
        It is the staff's goal to have all components of the EDS 
    periodically tested in a manner that is both reasonable and practical. 
    Various practical test methods such as the use of miniflow paths, 
    overlap testing, simulated loads, etc. have been found acceptable by 
    the staff.
        NRC Temporary Instruction 2515/107 (which provided guidance for 
    performing EDSFIs) required the EDSFI teams to ``verify that the 
    surveillance and test procedures are adequate to demonstrate the 
    functionality of the equipment or system being tested or the design 
    assumptions being verified.''
        Therefore, as shown above, testing of the EDS is evaluated in terms 
    of satisfying NRC requirements (GDC-17 and GDC-18) utilizing the 
    guidance provided by Regulatory Guide 1.118 for a reasonable and 
    practical approach (in lieu of testing each system as a whole), and 
    tests are properly implemented in the manner described above.
        4. The Petitioner pointed out that load nameplate ratings are used 
    in voltage analyses even when common knowledge shows that most loads 
    are operated at a fraction of their ratings. Furthermore, worst-case 
    ambient temperatures are used to select motor protection time delays 
    even though few loads, if any, see those conditions except during a 
    loss-of-coolant accident when the motor protection is bypassed. 
    Additionally, UVR output delays are treated as known quantities, when 
    the protection of loads by time delays and inverse time over current 
    relays is a crude mitigating approach. As a related matter, the 
    Petitioner objects to the inconsistent use of significant figures to 
    represent EDS and UVR SP parameters.
    
    Response
    
        The aforementioned temporary institution (TI) for the EDSFIs stated 
    that the inspectors should verify that values for mechanical loads used 
    for electrical calculations are based on actual system operating points 
    during both normal and accident conditions. The staff expects licenses 
    to perform accurate, conservative, and bounding calculations involving 
    worst-case estimates for parameters such as ambient temperatures and 
    loads. The licensees' analyses are reviewed by the staff utilizing 
    engineering judgment and applicable industry guidance to ensure that 
    reasonable, yet adequately safe solutions are provided.
        It is true that, occasionally, designs proposed by licensees do 
    involve basic approaches (such as inverse time delay relays) and that 
    some calculations performed by licensees involve the use of ultra-
    precise numerical values. What the staff does require is that the 
    designs utilized by licensees meet applicable NRC regulations and that 
    adequate protection of public health and safety is ensured.
        The staff, therefore, concludes that component characteristics are 
    treated and utilized properly in calculations that support EDS and UVR 
    designs.
        5. The Petitioner believed that when licensees have discovered that 
    UVR SPs are set too low, the typical response has been to raise the 
    setpoints. This, in turn, reduces the safety advantage of providing 
    UVRs for the EDS due to more frequent and unnecessary UVR actuations 
    accompanied by possible undesirable power systems transfers.
    
    Response
    
        In a letter dated August 8, 1979, addressed to all power reactor 
    licensees regarding the adequacy of station electric distribution 
    systems voltages, the staff stated that:
    
        Protection of safety loads from undervoltage conditions must be 
    deigned to provide the required protection without causing voltages 
    in excess of maximum voltage ratings of safety loads and without 
    causing spurious separations of safety buses from offsite power.
    Moreover,
    
    
    [[Page 58714]]
    
    
        Voltage-time settings for undervoltage relays shall be selected 
    so as to avoid spurious separation of safety buses from offsite 
    power during plant startup, normal operation and shutdown due to 
    startup and/or operation of electric loads.
    
    NRC Branch Technical Position PSB-1 states that:
    
        * * *imporper (sic) voltage protection logic can itself cause 
    adverse effects on the Class 1E systems and equipment such as * * * 
    spurious separation of Class 1E systems from offsite power due to 
    normal motor starting transients.
    
        Additionally, in IN 95-37, ``Inadequate Offsite Power System 
    Voltages during Design-Basis Events,`` the staff informed power reactor 
    licensees that although raising UVR setpoints ensures that adequate 
    voltages exist at equipment input terminals, the higher setpoints also 
    increase the potential for separation from the offsite power system 
    during design-basis events over the range of normally anticipated 
    offsite grid voltages.
        In a more specific example, a February 23, 1995, staff safety 
    evaluation of the degraded voltage design for the Edwin I. Hatch 
    Nuclear Plant, determined that combination of automatic and manual 
    actions was an acceptable alternative approach to meet the branch 
    technical position in lieu of raising the degraded voltage setpoints 
    which could lead to unwanted plant trips. That safety evaluation and 
    the above staff guidance provide evidence that the staff has considered 
    avoidance of spurious bus trips as one objective to be considered when 
    selecting an adequate setpoint of UVRs.
        The staff, therefore, has repeatedly and in detail both considered 
    the determental effects of raising the UVR setpoints and communicated 
    its concerns to licensees.
        6. The Petitioner stated that in IN 95-05, ``Undervoltage 
    Protection Relay Settings Out of Tolerance Due to Test Equipment 
    Harmonics,'' the staff discovered the peak reading voltmeters 
    calibrated for root-mean-square (RMS) are affected by the proportions 
    of harmonics in the AC bus voltages and in the calibrators used to set 
    the UVRs. Additionally, the harmonics affect the UVR responses by 
    changing their setpoints when the harmonic content of the bus voltage 
    changes.
    
    Response
    
        IN 95-05 discusses three occurrences, reported by licensees, where 
    harmonics in the output voltage of the power supplies used during 
    testing and calibration of UVRs resulted in the relay setpoints being 
    out of tolerance. The setpoint errors were also affected by the use of 
    digital voltmeters which do not respond to the harmonic content of the 
    test input voltage as do the UVRs. The purpose of the IN was to inform 
    all operating power plant licensees that harmonics in the voltage 
    inputs (test source voltage or normal bus voltage) to the UVRs impact 
    the actual operating points of those relays, as the Petitioner 
    believes, and to instruct the licensees to take appropriate action 
    (i.e., install filters, adjust setpoints, select proper test equipment, 
    etc.) to ensure that UVR setpoints are adequate.
        The staff, therefore, has addressed this concern and brought it to 
    the attention of licensees who are taking appropriate action as 
    discussed above.
        7. The Petitioner concluded that impedances and inrush currents to 
    motors and other loads are not known to the precision with which the 
    staff and the licensees' engineers have been trying to set UVRs. Both 
    groups must recognize that their task may be impossible and that their 
    attempts to do so have increased the risk of a nuclear accident.
    
    Response
    
        Branch Technical Position PSB-1 states that voltage analyses 
    (including effects of impedances and inrush currents) should be 
    performed with analytical techniques and assumptions verified by actual 
    measurement. It also states that, in general, test results should not 
    be more than 3% lower than the analytical results. This level of 
    precision has been determined to be acceptable based on engineering 
    judgment.
        Furthermore, as stated in the response to the Petitioner's fourth 
    concern, even though licensee propose solutions involving different 
    equipment and unique, precise calculations (which should be supported 
    by actual test data as mentioned above), staff reviews are conducted 
    utilizing both guidance from Branch Technical Position PSB-1 and 
    engineering judgment to ensure that all applicable regulations are met 
    and that adequate protection of public health and safety is ensured. 
    This approach provides reasonable assurance that the level of risk of a 
    nuclear accident is not increased and remains acceptable.
        Choosing a setpoint above an analytical limit based on minimum 
    voltage requirements and below nominal votage ranges while accounting 
    for instrumentation errors and analytical inaccuracies is often a 
    challenge which leads licensees to use more precise equipment and more 
    precise calculations. It is concerns such as these that have led the 
    staff to consider alternative approaches to its position on degraded 
    voltage protection on a plant-specific basis as noted above in the 
    staff's response to the Petitioner's fifth concern.
        Therefore, although the staff has concluded that the task is not 
    impossible, it has recognized alternative approaches that address 
    degraded voltage concerns without increasing the risk of an accident.
        To continue the discussion, identification of problems with UVRs 
    and EDSs was not inadvertent. The NRC staff had undertaken more global 
    measures to ensure that concerns such as those raised by the Petitioner 
    were addressed satisfactorily. Because previous NRC inspection teams 
    had observed that the required functional capabilities of certain 
    safety-related systems (including EDSs) were compromised due to a lack 
    of proper engineering support and the introduction of various design 
    deficiencies, EDFSIs were scheduled to be conducted for all operating 
    plants beginning with pilot inspections in 1989. NRC Temporary 
    Instruction (TI) 2515/107 was issued on October 19, 1990, to be made 
    part of the NRC Inspection Manual. That TI stated that calculations to 
    establish protective relay setpoints had not been initially performed 
    or were not updated to reflect setpoint changes and plant 
    modifications. These failures constituted some of the deficiencies that 
    had been encountered by previous inspection teams. The TI stated, with 
    regard to those concerns voiced by the Petitioner, that the forthcoming 
    inspections should verify:
         That ratings and setpoints have been correctly chosen and 
    controlled for protective and control relays and circuit breakers to 
    assure proper coordination, protection, required automatic action, and 
    annunciation.
         The adequacy of the load study, voltage profiles, voltage 
    drop calculations, motor starting study, load shedding, engineered 
    safety features (ESF) bus load sequencing and overload trip settings 
    for ESF loads including consideration of steady-state and accident-
    transient loads and consideration of acceleration of the loads during 
    degraded voltage conditions that may occur during various modes of 
    plant operation and accident mitigation scenarios.
         The adequacy of short circuit calculations, design of 
    protective relay logic and relay setting calculations, grounding 
    calculations and schemes, and protective device coordination studies.
         That setpoints for overcurrent protective relays are 
    correctly chosen (1) to assure proper breaker coordination
    
    [[Page 58715]]
    
    between different voltage levels; (2) to prevent exceeding the vendor-
    specified thermal limits on motors, containment electrical penetrations 
    and cable insulation systems; (3) to allow starting of electrical 
    equipment under degraded voltage conditions; and (4) to provide 
    adequate pre-trip alarms, when applicable.
         The adequacy of setpoints and time delays for other 
    protective relays for attributes such as undervoltage, underfrequency, 
    reverse power, ground faults, differential current, thermal overload 
    and phase synchronization to assure functionality of the EDS.
         That mechanical loads, such as pump horsepower, correspond 
    to actual system operating points during normal and accident conditions 
    and have been correctly translated to electrical loads and incorporated 
    in the electrical load list as appropriate.
         That surveillance and test procedures are adequate to 
    demonstrate the functionality of the equipment or system being tested 
    or the design assumptions being verified.
        NRC inspectors (including NRC contractors) assigned to the EDSFI 
    teams attended a week-long course (held in September and December 1990) 
    to enhance their knowledge of EDSs, the TI and related requirements. 
    Using the guidance provided by the TI and the EDSFI training course, 
    the EDSFI teams then conducted inspections of the EDSs through early 
    1994 at most operating nuclear power plants. As a result, numerous 
    deficiencies were identified and documented in plant-specific EDSFI 
    inspection reports, and corrective actions were taken. Those corrective 
    actions were subsequently evaluated, found acceptable by the staff and 
    documented in follow-up inspection reports. Many of these deficiencies 
    and corrective actions were listed in IN 93-99 and include incorrect 
    UVR relay and thermal overload setpoints caused by design errors, as 
    well as other points raised by the Petitioner.
        In summary, as stated in my April 17, 1996, letter, I believe the 
    NRC staff recognized the existence of repeated errors and widespread 
    EDS design deficiencies, including those associated with UVR SPs, took 
    appropriate actions (conducted EDSFIs, identified deficiencies, 
    required corrective actions) based on those observations, and made all 
    licenses aware of typical design deficiencies encountered during EDSFIs 
    and licensees' self-initiated efforts by issuing INs such as IN 91-29, 
    ``Deficiencies Identified During Electrical Distribution System 
    Functional Inspections,'' its supplements, and IN 93-99. Additionally, 
    the staff has continued to inform power reactor licensees of other 
    design deficiencies when they are encountered (e.g., IN 95-37 which 
    discusses UVR setpoints in relationship to inadequate offsite power 
    system voltages during design-basis events) and will continue to do so 
    in the future when necessary. Such action by the staff is appropriate 
    to address repeated errors in UVR setpoints and EDS designs and to 
    provide reasonable assurance of adequate protection of public health 
    and safety.
    
    III. Conclusion
    
        The institution of proceedings pursuant to 10 CFR 2.206 is 
    appropriate only if substantial health and safety issues have been 
    raised. See Consolidated Edison Co. of New York (Indian Point Units 1, 
    2, and 3) CLI-75-8, 2 NRC 173, 175 (1975) and Washington Public Power 
    Supply System (WPPSS Nuclear Project No. 2) DD-84-7, 19 NRC 899, 924 
    (1984). This is the standard that has been applied to the concerns 
    raised by the Petitioner to determine whether the action requested by 
    the Petitioner, or enforcement action, is warranted.
        On the basis of the preceding assessment, I have concluded that no 
    substantial health and safety issues have been raised by the Petitioner 
    that would warrant the action requested by the Petitioner. I further 
    conclude that the Petitioner's concerns have been adequately addressed 
    by the staff and that there is no need for a third party review. 
    Additionally, with regard to plants with UVRs that cannot be properly 
    set, the staff has shown in plant-specific evaluations, such as 
    described above, that other alternative designs are acceptable.
        The Petitioner's request for action pursuant to 10 CFR 2.206 is 
    denied. As provided for in 10 CFR 2.206(c), a copy of the decision will 
    be filed with the Secretary of the Commission for the Commission's 
    review. The decision will constitute the final action of the Commission 
    25 days after issuance unless the Commission, on its own motion, 
    institutes review of the decision in that time.
    
        Dated at Rockville, Maryland, this 26 day of September, 1996.
    
    For the Nuclear Regulatory Commission.
    William T. Russell,
    Director, Office of Nuclear Reactor Regulation.
    [FR Doc. 96-29459 Filed 11-15-96; 8:45 am]
    BILLING CODE 7590-01-M
    
    
    

Document Information

Published:
11/18/1996
Department:
Nuclear Regulatory Commission
Entry Type:
Notice
Document Number:
96-29459
Pages:
58711-58715 (5 pages)
PDF File:
96-29459.pdf