95-30048. Cleveland Electric Illuminating Company, Centerior Service Company, Duquesne Light Company, Ohio Edison Company, Pennsylvania Power Company, Toledo Edison Company (Perry Nuclear Power Plant, Unit 1); Exemption  

  • [Federal Register Volume 60, Number 237 (Monday, December 11, 1995)]
    [Notices]
    [Pages 63546-63548]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 95-30048]
    
    
    
    =======================================================================
    -----------------------------------------------------------------------
    
    NUCLEAR REGULATORY COMMISSION
    
    [Docket No. 50-440]
    
    
    Cleveland Electric Illuminating Company, Centerior Service 
    Company, Duquesne Light Company, Ohio Edison Company, Pennsylvania 
    Power Company, Toledo Edison Company (Perry Nuclear Power Plant, Unit 
    1); Exemption
    
    I
    
        Cleveland Electric Illuminating Company, (the licensee) is the 
    holder of Facility Operating License No. NPF-58, which authorizes 
    operation of the Perry Nuclear Power Plant, Unit 1 (PNPP). The 
    operating license provides, among other things, that the licensee is 
    subject to all rules, regulations, and orders of the Commission now and 
    hereafter in effect.
        The facility consists of a single boiling water reactor located at 
    the licensee's site in Lake County, Ohio.
    
    II
    
        Containment leak rate testing is necessary to demonstrate that the 
    measured leak rate is within the acceptance criteria cited in the 
    licensing design basis. Periodic testing of the overall containment 
    structure along with separate leak testing of the penetrations provides 
    assurance that post-accident radiological consequences will be within 
    the limits of 10 CFR Part 100. The Commission's requirements regarding 
    leak rate testing are found in Appendix J to 10 CFR Part 50.
        In its letter dated October 21, 1994, the licensee applied for 
    partial exemptions from the Commission's regulations. The subject 
    exemptions, which are from the requirements in Appendix J, Option A, to 
    10 CFR Part 50, include:
         Section III.A.5(b)(2) states that the measured leakage 
    from the containment integrated leak rate (Type A) test (Lam) shall be 
    less than 75% of the maximum allowable leakage rate (0.75 La).
         Sections III.B.3 and III.C.3 require that the combined 
    leakage of valves and penetrations subject to Type B and C local leak 
    rate testing be less than 0.6 times the maximum allowable leakage rate 
    (0.6 La).
         Section III.A.1(d) requires that all fluid systems that 
    would be open to containment following post-accident conditions, be 
    vented and drained prior to conducting the containment integrated leak 
    rate test.
         Section III.D.1(a) states that the third Type A test of 
    each 10-year interval be conducted when the plant is shut down for the 
    10-year plant inservice inspection.
         Section III.D.3 states that Type C tests shall be 
    performed during each reactor shutdown for refueling but in no case at 
    intervals greater than 2 years. Type C tests are tests intended to 
    measure containment isolation valve leakage rates.
    
    III
    
        Section III.A.5(b)(2) states that the measured leakage from the 
    containment integrated leak rate (Type A) test (Lam) shall be less 
    than 75% of the maximum allowable leakage rate (0.75 La). The 
    licensee proposes to exempt main steam line isolation valve leakage 
    from Type A test results and consider leakage from the main steam lines 
    separately. Sections III.B.3 and III.C.3 require that the combined 
    leakage of valves and penetrations subject to Type B and C local leak 
    rate testing be less than 0.6 
    
    [[Page 63547]]
    times the maximum allowable leakage rate (0.6 La). The licensee 
    proposes to exempt main steam line isolation valve leakage from the 
    combined leakage from Type B and C local leak rate testing and consider 
    leakage from the main steam lines separately. Section III.A.1(d) 
    requires that all fluid systems that would be open to containment 
    following post-accident conditions, be vented and drained prior to 
    conducting Type A tests. The licensee proposes that the piping between 
    the inboard and outboard main steam line isolation valves be flooded 
    with water when Type A tests are conducted.
        During the original staff review of the PNPP, the licensee proposed 
    separate treatment of measured leakage past the main steam isolation 
    valves. This approach is consistent with the staff's Standard Review 
    Plan (SRP) 15.6.5, Appendix D, ``Radiological Consequences of a Design 
    Basis Loss-of-Coolant Accident: Leakage from Main Steam Isolation Valve 
    Leakage Control System.'' In this SRP, the radiological consequences 
    associated with leakage from the main steam lines is calculated 
    separately and subsequently combined with the consequences from other 
    fission product release paths.
        As described in the Final Safety Analysis Report, the licensee 
    calculates off-site dose consequences by assuming separate 
    contributions from the containment integrated leak rate and the main 
    steam line isolation valve leak rate. These assumptions are supported 
    by the staff's Safety Evaluation Report (NUREG-0887) and the PNPP 
    Technical Specifications. Both the FSAR and Specification 3.6.1.2.a 
    state that the overall containment integrated leak rate shall be less 
    than 0.20 percent per day. NUREG-0887 lists this same value for the 
    containment integrated leak rate and a separate contribution from main 
    steam line leakage. Finally, Specification 3.6.1.2.b specifically 
    states that main steam line leakage will not be considered part of the 
    combined leak rate for penetrations and valves. Specification 3.6.1.2.c 
    limits the maximum allowable leakage from each main steam line to 25 
    standard cubic feet per hour.
        As described above, the licensee does not include leakage from the 
    main steam line isolation valves in either the Type A test results or 
    the combined Type B and C test results. Since the licensee measures 
    main steam line leakage separately from other Appendix J related 
    testing, the licensee does not want leakage from the main steam lines 
    to inadvertently influence the Type A test results. Therefore, in lieu 
    of venting and draining the piping between containment isolation valves 
    as required by Appendix J, the licensee proposes filling this section 
    of piping with water when Type A tests are performed. Filling these 
    sections of pipe with water would ensure that air would not pass 
    through these lines and thereby contribute to the Type A test results.
        The licensee has proposed alternative methods to the leak testing 
    requirements of Appendix J. While the licensee is treating main steam 
    line leakage separately from both Type A test results and the combined 
    Type B and C test results, the licensee still meets the intent of 
    Appendix J by demonstrating that the overall leakage is within design 
    limits. Therefore, the staff concludes that special circumstances are 
    present as required by 10 CFR 50.12(a)(2)(ii), in that application of 
    the regulation is not needed to meet the underlying purpose of the 
    rule. Furthermore, the staff finds that permitting the alternative 
    methods of leak testing will not present an undue risk to the public 
    health and safety.
        Section III.D.1(a) requires, in part, that ``* * * a set of three 
    Type A tests shall be performed, at approximately equal intervals 
    during each 10-year service period. The third test of each set shall be 
    conducted when the plant is shutdown for the 10-year plant inservice 
    inspections.'' The licensee proposes to perform the three Type A tests 
    at approximately equal intervals within each 10-year period, with the 
    third test of each set conducted as close as practical to the end of 
    the 10-year period. However, there would be no required connection 
    between the Appendix J 10-year interval and the inservice inspection 
    10-year interval.
        The 10-year plant inservice inspection (ISI) is the series of 
    inspections performed every 10-years in accordance with Section XI of 
    the ASME Boiler and Pressure Vessel Code and Addenda as required by 10 
    CFR 50.55a. The licensee performs the ISI volumetric, surface, and 
    visual examinations of components and system pressure tests in 
    accordance with 10 CFR 50.55a(g)(4) throughout the 10-year inspection 
    interval. The major portion of this effort is presently being performed 
    during the refueling outages. As a result, there is no extended outage 
    in which the 10-year ISI examinations are performed.
        There is no benefit to be gained by the coupling requirement cited 
    above in that elements of the PNPP ISI program are conducted throughout 
    each 10-year cycle rather than during a refueling outage at the end of 
    the 10-year cycle. Consequently, the subject coupling requirement 
    offers no benefit either to safety or to the economical operation of 
    the facility.
        Moreover, each of these two surveillance tests (i.e., the Type A 
    tests and the 10-year ISI program) is independent of the other and 
    provides assurances of different plant characteristics. The Type A test 
    assures the required leak-tightness to demonstrate compliance with the 
    guidelines of 10 CFR Part 100. The 10-year ISI program provides 
    assurance of the integrity of the structures, systems and components as 
    well as verifying operational readiness of pumps and valves in 
    compliance with 10 CFR 50.55a. There is no safety-related concern 
    necessitating their coupling in the same refueling outage. Accordingly, 
    the staff finds that application of the regulation is not necessary to 
    achieve the underlying purpose of the rule.
        On this basis, the staff finds that the licensee has demonstrated 
    that there are special circumstances present as required by 10 CFR 
    50.12(a)(2)(ii). Further, the staff also finds that the uncoupling of 
    the Type A tests from the 10-year ISI program will not present an undue 
    risk to the public health and safety.
        Section III.D.3 of Appendix J states that Type C tests shall be 
    performed during each reactor shutdown for refueling but in no case at 
    intervals greater than 2 years. The licensee requested relief from the 
    requirement to perform Type C tests during each reactor shutdown for 
    refueling. The licensee proposes to perform the required Type C tests 
    while the plant is at power.
        Section II.D.3 of Appendix J requires that ``Type C tests shall be 
    performed during each reactor shutdown for refueling but in no case at 
    intervals greater than 2 years.'' Paragraph III.D.2 discusses the 
    scheduling of Type B tests and contains the same wording but also 
    includes an additional provision that allows Type B tests to be 
    performed at ``other convenient intervals'' in lieu of during reactor 
    shutdown for refueling. The licensee has requested that this same 
    flexibility be applied to Type C local leak rate testing.
        The underlying purpose of the rule is to ensure that adequate 
    testing is done to demonstrate containment integrity. From the 
    standpoint of testing adequacy, when the testing is performed is not 
    significant because the conditions of testing are the same regardless 
    of when it is performed. As indicated by the licensee, the BWR/6 Mark 
    III containment/suppression pool design is such that Type C local leak 
    rate testing can be performed during power operation on certain 
    systems. In addition, the Drywell and Containment Purge System 
    containment isolation 
    
    [[Page 63548]]
    valves have surveillance requirements imposed on them to demonstrate 
    leak tightness during power operation. These surveillance tests are the 
    same exact leak rate tests as the Type C local leak rate tests 
    performed during refueling outages.
        Taking credit for testing performed during power operation provides 
    the same degree of assurance of containment integrity as taking credit 
    for testing performed during shutdown. In addition, testing while at 
    power may be preferable when considering ALARA and operability 
    requirements. Therefore, the special circumstances of 10 CFR 
    50.12(a)(2)(ii) are present in that application of the regulation in 
    this particular circumstance is not necessary to achieve the underlying 
    purpose of the rule.
    
    IV
    
        The Commission has determined that pursuant to 10 CFR 50.12(a)(1) 
    that this exemption is authorized by law, will not present an undue 
    risk to the public health and safety, and is consistent with the common 
    defense and security. The Commission further determines that special 
    circumstances, as provided in 10 CFR 50.12(a)(2)(ii), are present 
    justifying the exemption; namely, that application of the regulation in 
    this particular circumstance is not necessary to achieve the underlying 
    purpose of the rule.
        Pursuant to 10 CFR 51.32, the Commission has determined that the 
    granting of this Exemption will not have a significant impact on the 
    quality of the human environment (60 FR 51821). This exemption is 
    effective upon issuance.
    
        Dated at Rockville, Maryland, this 4th day of December 1995.
    
        For the Nuclear Regulatory Commission
    Jack W. Roe,
    Director, Division of Reactor Projects III/IV,Office of Nuclear Reactor 
    Regulation
    [FR Doc. 95-30048 Filed 12-8-95; 8:45 am]
    BILLING CODE 7590-01-P
    
    

Document Information

Published:
12/11/1995
Department:
Nuclear Regulatory Commission
Entry Type:
Notice
Document Number:
95-30048
Pages:
63546-63548 (3 pages)
Docket Numbers:
Docket No. 50-440
PDF File:
95-30048.pdf