98-32207. RUS Standard for Service Installations at Customer Access Locations  

  • [Federal Register Volume 63, Number 244 (Monday, December 21, 1998)]
    [Proposed Rules]
    [Pages 70456-70523]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 98-32207]
    
    
    
    [[Page 70455]]
    
    _______________________________________________________________________
    
    Part II
    
    
    
    
    
    Department of Agriculture
    
    
    
    
    
    _______________________________________________________________________
    
    
    
    Rural Utilities Service
    
    
    
    _______________________________________________________________________
    
    
    
    7 CFR Part 1755
    
    
    
    RUS Standard for Service Installations at Customer Access Locations; 
    Proposed Rule
    
    Federal Register / Vol. 63, No. 244, Monday, December 21, 1998 / 
    Proposed Rules
    
    [[Page 70456]]
    
    
    
    DEPARTMENT OF AGRICULTURE
    
    Rural Utilities Service
    
    7 CFR Part 1755
    
    
    RUS Standard for Service Installations at Customer Access 
    Locations
    
    AGENCY: Rural Utilities Service, USDA.
    
    ACTION: Proposed rule.
    
    -----------------------------------------------------------------------
    
    SUMMARY: The Rural Utilities Service (RUS) proposes to amend its 
    regulations on Telecommunications Standards and Specifications for 
    Materials, Equipment and Construction, by rescinding RUS Bulletin 345-
    52, RUS Standard for Service Entrance and Station Protector 
    Installations, PC-5A, and codifying the revised standard in the Code of 
    Federal Regulations as RUS Standard for Service Installations at 
    Customer Access Locations. The revised standard will update the 
    installation methods used for installing aerial and buried service 
    drops, network interface devices, fused primary station protectors, and 
    protected building entrance terminals at customer access locations as a 
    result of technological advancements made in installation practices and 
    materials over the past 17 years.
    
    DATES: Comments concerning this proposed rule must be received by RUS 
    or be postmarked no later February 19, 1999.
    
    ADDRESSES: Comments should be mailed to the Orren E. Cameron III, 
    Director, Telecommunications Standards Division, Rural Utilities 
    Service, U.S. Department of Agriculture, 1400 Independence Avenue, SW., 
    STOP 1598, Washington, DC 20250-1598. RUS requests an original and 
    three copies of all comments (7 CFR part 1700). All comments received 
    will be made available for public inspection at room 2835, South 
    Building, U.S. Department of Agriculture, 1400 Independence Avenue, 
    SW., STOP 1598 Washington, DC 20250-1598 between 8 a.m. and 4 p.m. (7 
    CFR 1.27(b)).
    
    FOR FURTHER INFORMATION CONTACT: Charlie I. Harper, Jr., Chief, Outside 
    Plant Branch, Telecommunications Standards Division, Rural Utilities 
    Service, U.S. Department of Agriculture, 1400 Independence Avenue, SW., 
    STOP 1598, Washington, DC 20250-1598, telephone (202) 720-0667.
    
    SUPPLEMENTARY INFORMATION:
    
    Executive Order 12866
    
        This proposed rule is exempt from the Office of Management and 
    Budget (OMB) review for purposes of Executive Order 12866 and, 
    therefore has not been reviewed by OMB.
    
    Executive Order 12988
    
        This proposed rule has been reviewed under Executive Order 12988, 
    Civil Justice Reform. RUS has determined that this proposed rule meets 
    the applicable standards provided in section 3 of that Executive Order. 
    In addition, all State and local laws and regulations that are in 
    conflict with this rule will be preempted, no retroactive effort will 
    be given to this rule, and, in accordance with section 212(c) of the 
    Department of Agriculture Reorganization Act of 1994 (7 U.S.C. 
    6912(c)), administrative appeal procedures must be exhausted before an 
    action against the Department or its agencies may be initiated.
    
    Regulatory Flexibility Act Certification
    
        The Administrator RUS has determined that this proposed rule will 
    not have a significant impact on a substantial number of small 
    entities, as defined by the Regulatory Flexibility Act (5 U.S.C. 601 et 
    seq.). This proposed rule involves standards and specifications, which 
    may increase the direct-short term costs to the RUS borrower. However, 
    the long-term direct economic costs are reduced through greater 
    durability and lower maintenance cost over time. Small entities are not 
    subjected to any requirement which are not applied equally to large 
    entities.
    
    Information Collection and Recordkeeping Requirements
    
        This proposed rule contains no information collection or 
    recordkeeping requirements under the Paperwork Reduction Act of 1995 
    (44 U.S.C. Chapter 35, as amended).
    
    National Environmental Policy Act Certification
    
        The Administrator of RUS has determined that this proposed rule 
    will not significantly affect the quality of the human environment as 
    defined by the National Environmental Policy Act of 1969 (42 U.S.C. 
    4321 et seq.). Therefore, this action does not require an environmental 
    impact statement or assessment.
    
    Catalog of Federal Domestic Assistance
    
        The program described by this proposed rule is listed in the 
    Catalog of Federal Domestic Assistance programs under No. 10.851, Rural 
    Telephone Loans and Loan Guarantees, and No. 10.852, Rural Telephone 
    Bank Loans. This catalog is available on a subscription basis from the 
    Superintendent of Documents, the United States Government Printing 
    Office, Washington, DC 20402.
    
    Executive Order 12372
    
        This proposed rule is excluded from the scope of Executive Order 
    12372, Intergovernmental Consultation, which may require consultation 
    with State and local officials. A Notice of Final rule titled 
    Department Programs and Activities Excluded from Executive Order 12372 
    (50 FR 47034) exempts RUS and RTB loans and loan guarantees, and RTB 
    bank loans, to governmental and nongovernmental entities from coverage 
    under this Order.
    
    Unfunded Mandates
    
        This proposed rule contains no Federal mandates (under the 
    regulatory provision of Title II of the Unfunded Mandates Reform Act) 
    for State, local, and tribal governments or the private sector. Thus 
    this proposed rule is not subject to the requirements of section 202 
    and 205 of the Unfunded Mandates Reform Act.
    
    Background
    
        RUS issues publications titled ``Bulletin'' which serve to guide 
    borrowers regarding already codified policy, procedures, and 
    requirements needed to manage loans, loan guarantee programs, and the 
    security instruments which provide for and secure RUS financing. RUS 
    issues standards and specifications for the construction of 
    telecommunications facilities financed with RUS loan funds. RUS is 
    proposing to rescind Bulletin 345-52, RUS Standard for Service Entrance 
    and Station Protector Installations, PC-5A, and to codify the revised 
    standard at 7 CFR 1755.500 through 7 CFR 1755.510, RUS Standard for 
    Service Installations at Customer Access Locations.
        RUS Bulletin 345-52 is used by borrowers and contractors as an 
    outside plant construction standard for the installation of aerial and 
    buried service drops and primary station protectors at customer 
    residences. Because of technological advancements and national code 
    changes made in customer drop and protector installation methods and 
    materials over the past 17 years, the installation methods and 
    materials specified in the current standard have become outdated. To 
    allow borrowers and contractors to observe current codes and take 
    advantage of these improved installation methods and materials which 
    will reduce installation costs, the current standard will be revised to 
    update the customer access location installation methods and materials 
    to reflect these improved methods and materials.
        This action will allow borrowers and contractors an economical and 
    efficient
    
    [[Page 70457]]
    
    means of reducing their construction costs through the use of improved 
    customer access location installation methods and materials.
        While this proposed rule proposes to codify the full text of this 
    contract, RUS is considering a new procedure under which we will no 
    longer publish the full text of construction contracts such as this in 
    the CFR. Consequently, it is contemplated that at the final rule stage, 
    the full text of this contract will not appear in codified text.
    
    List of Subjects in 7 CFR Part 1755
    
        Incorporation by reference, Loan programs--communications, 
    Reporting and recordkeeping requirements, Rural areas, Telephone.
        For reasons set out in the preamble, RUS proposes to amend Chapter 
    XVII of title 7 of the Code of Federal Regulations as follows:
    
    PART 1755--TELECOMMUNICATIONS STANDARDS AND SPECIFICATIONS FOR 
    MATERIALS, EQUIPMENT AND CONSTRUCTION
    
        1. The authority citation for part 1755 continues to read as 
    follows:
    
        Authority: 7 U.S.C. 901 et seq., 1921 et seq., 6941 et seq.
    
    
    Sec. 1755.97  [Amended]
    
        2. Section 1755.97 is amended by removing the entry RUS Bulletin 
    345-52 from the table.
        3. Section 1755.98 is amended by adding the entry 1755.500 through 
    1755.510 to the table in numerical order to read as follows:
    
    
    Sec. 1755.98  List of telephone standards and specifications included 
    in other 7 CFR parts.
    
    * * * * *
    
    ----------------------------------------------------------------------------------------------------------------
                  Section                         Issue date                               Title
    ----------------------------------------------------------------------------------------------------------------
     
    *                  *                  *                  *                  *                  *
                                                            *
    1755.500 through 1755.510..........  [Effective date of final     RUS Standard for Service Installations at
                                          rule].                       Customer Access Locations.
     
    *                  *                  *                  *                  *                  *
                                                            *
    ----------------------------------------------------------------------------------------------------------------
    
        4. Sections 1755.500 through 1755.510 are added to read as follows:
    
    
    Sec. 1755.500  RUS standard for service installations at customers 
    access locations.
    
        (a) Sections 1755.501 through 1755.510 cover service installations 
    at permanent or mobile home customer access locations. Sections 
    1755.501 through 1755.510 do not cover service installations at 
    customer access locations associated with boat yards or marinas.
        (b) Service installations for customer access locations in boat 
    yards or marinas shall be performed in accordance with Article 800, 
    Communications Circuits, of the American National Standards Institute/
    National Fire Protection Association (ANSI/NFPA) 70-1996, National 
    Electrical Code (NEC). The National Electrical 
    Code and NEC are registered trademarks of the 
    National Fire Protection Association, Inc., Quincy, MA 02269. The ANSI/
    NFPA 70-1996, NEC is incorporated by reference in 
    accordance with 5 U.S.C. 552(a) and 1 CFR part 51. Copies are available 
    from NFPA, 1 Batterymarch Park, P. O. Box 9101, Quincy, Massachusetts 
    02269-9101, telephone number 1 (800) 344-3555. Copies of ANSI/NFPA 70-
    1996, NEC, are available for inspection during normal 
    business hours at Rural Utilities Service (RUS), room 2845, U.S. 
    Department of Agriculture, 1400 Independence Avenue, SW., STOP 1598, 
    Washington, DC 20250-1598 or at the Office of the Federal Register, 800 
    North Capitol Street, NW., suite 700, Washington, DC.
    
    
    Sec. 1755.501  Definitions.
    
        (a) For the purpose of this section and Secs. 1755.502 through 
    1755.510, the following terms shall have the following meanings:
        American National Standards Institute (ANSI). A private sector 
    standards coordinating body which serves as the United States source 
    and information center for all American National Standards.
        Ampacity. As defined in the ANSI/NFPA 70-1996, NEC: The 
    current in amperes that a conductor can carry continuously under the 
    conditions of use without exceeding its temperature rating. (Reprinted 
    with permission from NFPA 70-1996, the National Electrical 
    Code, Copyright 1995, National Fire 
    Protection Association, Quincy, MA 02269. This reprinted material is 
    not the complete and official position of the National Fire Protection 
    Association, on the referenced subject which is represented only by the 
    standard in its entirety.). The National Electrical Code 
    and NEC are registered trademarks of the National Fire 
    Protection Association, Inc., Quincy, MA 02269. The ANSI/NFPA 70-1996, 
    NEC, is incorporated by reference in accordance with 5 
    U.S.C. 552(a) and 1 CFR part 51. Copies are available from NFPA, 1 
    Batterymarch Park, P. O. Box 9101, Quincy, Massachusetts 02269-9101, 
    telephone number 1 (800) 344-3555. Copies of ANSI/NFPA 70-1996, 
    NEC, are available for inspection during normal business 
    hours at RUS, room 2845, U.S. Department of Agriculture, 1400 
    Independence Avenue, SW., STOP 1598, Washington, DC 20250-1598 or at 
    the Office of the Federal Register, 800 North Capitol Street, NW., 
    suite 700, Washington, DC.
        Bonding. The permanent joining of metallic parts to form an 
    electrically conductive path that will ensure electrical continuity and 
    the capacity to conduct safely any current likely to be imposed.
        Bonding harness wire. A reliable electrical conductor purposefully 
    connected between metal parts which are required to be electrically 
    connected (bonded) to one another to ensure the metal parts are at 
    similar electrical potential.
        Building entrance terminal (BET). A BET is comprised of a housing 
    suitable for indoor and outdoor installation which contains quick-
    connect or binding post terminals for terminating both 
    telecommunications service cable conductors and inside wiring cable 
    conductors. The BET also includes primary station protectors and a 
    means of terminating the metallic shields of service entrance cables.
        Demarcation point (DP). As defined in the Federal Communications 
    Commission (FCC) rules in 47 CFR Part 68: The point of demarcation or 
    interconnection between telecommunications company communications 
    facilities and terminal equipment, protective apparatus, or wiring at a 
    subscriber's premises. Carrier-installed facilities at, or 
    constituting, the demarcation point shall consist of wire or a jack 
    conforming to subpart F of 47 CFR part 68. ``Premises'' as used herein 
    generally
    
    [[Page 70458]]
    
    means a dwelling unit, other building or a legal unit of real property 
    such as a lot on which a dwelling unit is located, as determined by the 
    telecommunications company's reasonable and nondiscriminatory standard 
    operating practices. The ``minimum point of entry'' as used herein 
    shall be either the closest practicable point to where the wiring 
    crosses a property line or the closest practicable point to where the 
    wiring enters a multiunit building or buildings. The telecommunications 
    company's reasonable and nondiscriminatory standard operating practices 
    shall determine which shall apply. The telecommunications company is 
    not precluded from establishing reasonable clarifications of multiunit 
    premises for determining which shall apply. Multiunit premises include, 
    but are not limited to, residential, commercial, shopping center, and 
    campus situations.
        (1) Single unit installations. For single unit installations 
    existing as of August 13, 1990, and installations installed after that 
    date, the demarcation point shall be a point within 12 inches (in.) 
    [305 millimeters (mm)] of the primary protector, where there is no 
    protector, within 12 in. (305 mm) of where the telecommunications wire 
    enters the customer's premises.
        (2) Multiunit installations. (i) In multiunit premises existing as 
    of August 13, 1990, the demarcation point shall be determined in 
    accordance with the local carrier's reasonable and nondiscriminatory 
    standard operating practices. Provided, however, that where there are 
    multiple demarcation points within the multiunit premises, a 
    demarcation point for a customer shall not be further inside the 
    customer's premises than a point 12 in. (305 mm) from where the wiring 
    enters the customer's premises.
        (ii) In multiunit premises in which wiring is installed after 
    August 13, 1990, including additions, modifications, and rearrangements 
    of wiring existing prior to that date, the telecommunications company 
    may establish a reasonable and nondiscriminatory practice of placing 
    the demarcation point at the minimum point of entry. If the 
    telecommunications company does not elect to establish a practice of 
    placing the demarcation point at the minimum point of entry, the 
    multiunit premises owner shall determine the location of the 
    demarcation point or points. The multiunit premises owner shall 
    determine whether there shall be a single demarcation point for all 
    customers or separate such locations for each customer. Provided, 
    however, that where there are multiple demarcation points within the 
    multiunit premises, a demarcation point for a customer shall not be 
    further inside the customer's premises than a point 12 in. (305 mm) 
    from where the wiring enters the customer's premises.
        Fuse link. As defined in the ANSI/NFPA 70-1996, NEC: A 
    fine gauge section of wire or cable that serves as a fuse (that is, 
    open-circuits to interrupt the current should it become excessive) that 
    coordinates with the telecommunications cable and wire plant, and 
    protective devices. (Reprinted with permission from NFPA 70-1996, the 
    National Electrical Code, Copyright 1995, 
    National Fire Protection Association, Quincy, MA 02269. This reprinted 
    material is not the complete and official position of the National Fire 
    Protection Association, on the referenced subject which is represented 
    only by the standard in its entirety.)
        Grounding conductor. As defined in the ANSI/NFPA 70-1996, 
    NEC: A conductor used to connect equipment or the grounded 
    circuit of a wiring system to a grounding electrode or electrodes. 
    (Reprinted with permission from NFPA 70-1996, the National Electrical 
    Code, Copyright 1995, National Fire Protection 
    Association, Quincy, MA 02269. This reprinted material is not the 
    complete and official position of the National Fire Protection 
    Association, on the referenced subject which is represented only by the 
    standard in its entirety.)
        Listed. As defined in the ANSI/NFPA 70-1996, NEC: 
    Equipment or materials included in a list published by an organization 
    acceptable to the authority having jurisdiction and concerned with 
    product evaluation, that maintains periodic inspection of production of 
    listed equipment or materials, and whose listing states either that the 
    equipment or material meets appropriate designated standards or has 
    been tested and found suitable for use in a specified manner. 
    (Reprinted with permission from NFPA 70-1996, the National Electrical 
    Code, Copyright 1995, National Fire Protection 
    Association, Quincy, MA 02269. This reprinted material is not the 
    complete and official position of the National Fire Protection 
    Association, on the referenced subject which is represented only by the 
    standard in its entirety.)
        Manufactured home. As defined in the ANSI/NFPA 70-1996, 
    NEC: A factory-assembled structure or structures 
    transported in one or more sections, that is built on a permanent 
    chassis and designed to be used as a dwelling with a permanent 
    foundation acceptable to the authority having jurisdiction where 
    connected to the required utilities, and includes the plumbing, 
    heating, air conditioning, and electric systems contained therein. 
    Unless otherwise indicated, the term ``mobile home'' includes 
    manufactured homes. (Reprinted with permission from NFPA 70-1996, the 
    National Electrical Code, Copyright 1995, 
    National Fire Protection Association, Quincy, MA 02269. This reprinted 
    material is not the complete and official position of the National Fire 
    Protection Association, on the referenced subject which is represented 
    only by the standard in its entirety.)
        Mobile home. As defined in the ANSI/NFPA 70-1996, NEC: 
    A factory-assembled structure or structures transportable in one or 
    more sections, that is built on a permanent chassis and designed to be 
    used as a dwelling without a permanent foundation where connected to 
    the required utilities, and includes the plumbing, heating, air-
    conditioning, and electric systems contained therein. Unless otherwise 
    indicated, the term ``mobile home'' includes manufactured homes. 
    (Reprinted with permission from NFPA 70-1996, the National Electrical 
    Code, Copyright 1995, National Fire Protection 
    Association, Quincy, MA 02269. This reprinted material is not the 
    complete and official position of the National Fire Protection 
    Association, on the referenced subject which is represented only by the 
    standard in its entirety.)
        Motor home. As defined in the ANSI/NFPA 70-1996, NEC: A 
    vehicular unit designed to provide temporary living quarters for 
    recreational, camping, or travel use built on or permanently attached 
    to a self-propelled motor vehicle chassis or on a chassis cab or van 
    that is an integral part of the completed vehicle. (Reprinted with 
    permission from NFPA 70-1996, the National Electrical Code, 
    Copyright 1995, National Fire Protection Association, 
    Quincy, MA 02269. This reprinted material is not the complete and 
    official position of the National Fire Protection Association, on the 
    referenced subject which is represented only by the standard in its 
    entirety.)
        Network interface device (NID). A NID is comprised of a housing 
    suitable for outdoor installation which contains a compartment 
    accessible by only telecommunications employees which includes a 
    primary station protector and the means for terminating 
    telecommunications service wire conductors and metallic shields, and a 
    compartment accessible by customers which includes an RJ-11 plug and 
    jack
    
    [[Page 70459]]
    
    of the type specified in part 68 of FCC rules and regulations.
        Primary station protector. An assembly which complies with RUS 
    Bulletin 345-39, RUS Specification for Telephone Station Protectors. 
    Copies of RUS Bulletin 345-39 are available upon request from RUS, U.S. 
    Department of Agriculture (USDA), 1400 Independence Avenue, SW., STOP 
    1522, Washington, DC 20250-1522, FAX (202) 690-2268.
        Recreational vehicle. As defined in the ANSI/NFPA 70-1996, 
    NEC: A vehicular-type unit designed to provide temporary 
    living quarters for recreational, camping, or travel use, which either 
    has its own motive power or is mounted on or drawn by another vehicle. 
    The basic entities are: travel trailer, camping trailer, truck camper, 
    and motor home. (Reprinted with permission from NFPA 70-1996, the 
    National Electrical Code, Copyright 1995, 
    National Fire Protection Association, Quincy, MA 02269. This reprinted 
    material is not the complete and official position of the National Fire 
    Protection Association, on the referenced subject which is represented 
    only by the standard in its entirety.)
        RUS accepted (material and equipment). Equipment which RUS has 
    reviewed and determined that:
        (1) Final assembly or manufacture of the equipment is completed in 
    the United States, its territories and possessions, or in an eligible 
    country;
        (2) The cost of components within the material or equipment 
    manufactured in the United States, its territories and possessions, or 
    in an eligible country is more than 50 percent of the total cost of all 
    components used in the material or equipment; and
        (3) The material or equipment is suitable for use on systems of RUS 
    telecommunications borrowers.
        RUS technically accepted (material and equipment). Equipment which 
    RUS has reviewed and determined that:
        (1) Final assembly or manufacture of the equipment is not completed 
    in the United States, its territories and possessions, or in an 
    eligible country;
        (2) The cost of components within the material or equipment 
    manufactured in the United States, its territories and possessions, or 
    in an eligible country is 50 percent or less than the total cost of all 
    components used in the material or equipment; and
        (3) The material or equipment is suitable for use on systems of RUS 
    telecommunications borrowers.
        Travel trailer. As defined in the ANSI/NFPA 70-1996, 
    NEC: A vehicular unit mounted on wheels, designed to 
    provide temporary living quarters for recreational, camping, or travel 
    use, of such size and weight as to not require special highway movement 
    permits when towed by a motorized vehicle and of gross trailer area 
    less than 320 square feet (29.77 square meters). (Reprinted with 
    permission from NFPA 70-1996, the National Electrical Code, 
    Copyright 1995, National Fire Protection Association, 
    Quincy, MA 02269. This reprinted material is not the complete and 
    official position of the National Fire Protection Association, on the 
    referenced subject which is represented only by the standard in its 
    entirety.)
        Truck camper. As defined in the ANSI/NFPA 70-1996, NEC: 
    A portable unit constructed to provide temporary living quarters for 
    recreational, travel or camping use, consisting of a roof, floor, and 
    sides, designed to be loaded onto and unloaded from the bed of a pick-
    up truck. (Reprinted with permission from NFPA 70-1996, the National 
    Electrical Code, Copyright 1995, National Fire 
    Protection Association, Quincy, MA 02269. This reprinted material is 
    not the complete and official position of the National Fire Protection 
    Association, on the referenced subject which is represented only by the 
    standard in its entirety.)
    
    
    Sec. 1755.502  Scope.
    
        (a) Sections 1755.503 through 1755.510 cover approved methods of 
    making service installations at customer access locations in 
    telecommunications systems of RUS borrowers.
        (b) Requirements in Secs. 1755.503 through 1755.510 cover 
    facilities of the type described in the FCC rules in 47 CFR part 68 for 
    one and multi-party customer owned premises wiring.
    
    
    Sec. 1755.503  General.
    
        (a) For the purposes of this section and Secs. 1755.504 through 
    1755.510, a NID shall be as defined in Sec. 1755.501 and shall contain 
    both a fuseless primary station protector and a modular plug and jack 
    for each conductor pair, up to a maximum of eleven (11) pairs, and 
    shall be provided by the telecommunications company and used by 
    customers.
        (b) For the purposes of this section and Secs. 1755.504 through 
    1755.510, a BET shall be as defined in Sec. 1755.501 and shall contain 
    both primary station protectors and connector terminals for each 
    conductor pair, of twelve (12) or more pairs, and shall be provided by 
    the telecommunications company and used by customers. The primary 
    station protectors may be either fuseless or fused.
        (c) The requirements provided in this section and Secs. 1755.504 
    through 1755.510 have been designed to coordinate with the provisions 
    of the ANSI/NFPA 70-1996, NEC, and the American National 
    Standards Institute/Institute of Electrical and Electronics Engineers, 
    Inc. (ANSI/IEEE) C2-1997, National Electrical Safety Code (NESC). The 
    National Electrical Code and NEC are registered 
    trademarks of the National Fire Protection Association, Inc., Quincy, 
    MA 02269. The ANSI/NFPA 70-1996, NEC, and the ANSI/IEEE C2-
    1997, NESC, are incorporated by reference in accordance with 5 U.S.C. 
    552(a) and 1 CFR part 51. Copies of ANSI/NFPA 70-1996, NEC, 
    are available from NFPA, 1 Batterymarch Park, P. O. Box 9101, Quincy, 
    Massachusetts 02269--9101, telephone number 1 (800) 344-3555. Copies of 
    ANSI/IEEE C2--1997, NESC, are available from IEEE Service Center, 455 
    Hoes Lane, Piscataway, New Jersey 08854, telephone number 1 (800) 678-
    4333. Copies of the ANSI/NFPA 70-1996, NEC, and the ANSI/
    IEEE C2-1997, NESC, are available for inspection during normal business 
    hours at RUS, room 2845, U.S. Department of Agriculture, 1400 
    Independence Avenue, SW., STOP 1598, Washington, DC 20250-1598 or at 
    the Office of the Federal Register, 800 North Capitol Street, NW., 
    suite 700, Washington, DC. Most state and local authorities require 
    that utility construction comply with either the ANSI/NFPA 70-1996, 
    NEC, and ANSI/IEEE C2-1997, NESC, or some earlier editions 
    of the ANSI/NFPA 70, NEC, and ANSI/IEEE C2, NESC. Some 
    authorities have their own more stringent codes which may or may not be 
    embellishments of the ANSI/NFPA 70, NEC, and ANSI/IEEE C2, 
    NESC.
        (d) RUS borrowers shall make certain that all construction financed 
    with RUS loan funds comply with:
        (1) The provisions of this section and Secs. 1755.504 through 
    1755.510 and the ANSI/NFPA 70-1996, NEC, and ANSI/IEEE C2-
    1997, NESC codes, or any more stringent local codes; or
        (2) The provisions of this section and Secs. 1755.504 through 
    1755.510 with borrower added adjustments to bring construction into 
    compliance with any more stringent local codes.
        (e) This section and Secs. 1755.504 through 1755.510 are intended 
    primarily for the installer who will perform the work. It assumes that 
    decisions regarding the selection of grounding electrodes, locations, 
    and types of equipment have been made by the RUS borrower or the 
    engineer delegated by the RUS borrower.
        (f) Only a qualified installer shall be assigned to make 
    installations without advance planning and without direct
    
    [[Page 70460]]
    
    supervision. A qualified installer is one who has extensive 
    installation experience, complete knowledge and understanding of RUS 
    Bulletin 1751F-805, Electrical Protection At Customer Locations; RUS 
    Bulletin 345-154 (RUS Form 515g), Specifications and Drawings for 
    Service Entrance and Station Protector Installation, and applicable 
    portions of the ANSI/NFPA 70-1996, NEC, and ANSI/IEEE C2-
    1997, NESC. Copies of RUS Bulletins 1751F-805 and 345-154 are available 
    upon request from RUS/USDA, 1400 Independence Avenue, SW., STOP 1522, 
    Washington, DC 20250-1522, FAX (202) 690-2268.
        (g) This section and Secs. 1755.504 through 1755.509 contain 
    information which is normally not provided on the construction drawings 
    which are included in Sec. 1755.510.
        (h) All work shall be conducted in a careful and professional 
    manner. Service wire and cable shall not be trampled on, run over by 
    vehicles, pulled over or around abrasive objects or otherwise subjected 
    to abuse.
        (i) When situations not covered by this section and Secs. 1755.504 
    through 1755.510 arise, the RUS borrower or the engineer delegated by 
    the borrower, shall specify the installation procedure to be used. The 
    requirements of paragraph (j) of this section shall be complied with in 
    every installation.
        (j) NIDs, BETs, and fused primary station protectors shall be 
    installed and grounded to meet the requirements of the ANSI/NFPA 70-
    1996, NEC, or local laws or ordinances, whichever are more 
    stringent.
        (k) Battery polarity and conductor identification shall be 
    maintained throughout the system as indicated on construction drawings 
    815 and 815-1 contained in Sec. 1755.510. Color codes and other means 
    of conductor identification of buried and aerial service wires shall 
    conform to the requirements of this section and Secs. 1755.504 through 
    1755.510.
        (l) All materials for which RUS makes acceptance determinations, 
    such as service wires and cables, ground rods, ground rod clamps, etc., 
    used in service entrance installations shall be RUS accepted or RUS 
    technically accepted. Borrowers shall require contractors to obtain the 
    borrower's approval before RUS technically accepted materials are to be 
    used in service entrance installations. Borrower's shall also ensure 
    that the cost of the RUS technically accepted materials are at least 6 
    percent less than the cost of equivalent RUS accepted materials, as 
    specified in ``Buy American'' Requirement of the Rural Electrification 
    Act of 1938, as amended. Materials used in service entrance 
    installations which are of the type which RUS does not make acceptance 
    determinations shall be of a suitable quality for their intended 
    application as determined by the RUS borrower or the engineer delegated 
    by the RUS borrower.
        (m) On completion of an installation, borrowers shall require the 
    installer to make all applicable tests required by Secs. 1755.400 
    through 1755.407, RUS standard for acceptance tests and measurements of 
    telecommunications plant.
    
    
    Sec. 1755.504  Demarcation point.
    
        (a) The demarcation point (DP) provides the physical and electrical 
    interface between the telecommunications company's facilities and the 
    customer's premises wiring.
        (b) The FCC rules in 47 CFR part 68 require telecommunications 
    providers to establish a ``DP'' which marks a separation of the 
    provider's facilities from the customer's (owned) premises wiring and 
    equipment.
        (c) RUS borrowers shall observe the FCC DP requirement by 
    installing NIDs, BETs, or fused primary station protectors when 
    required by Section 800-30(a)(2) of the ANSI/NFPA 70-1996, 
    NEC, at all new or significantly modified customer access 
    locations which are financed with RUS loan funds. The National 
    Electrical Code and NEC are registered 
    trademarks of the National Fire Protection Association, Inc., Quincy, 
    MA 02269. The ANSI/NFPA 70-1996, NEC, is incorporated by 
    reference in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. Copies 
    are available from NFPA, 1 Batterymarch Park, P.O. Box 9101, Quincy, 
    Massachusetts 02269-9101, telephone number 1 (800) 344-3555. Copies of 
    ANSI/NFPA 70-1996, NEC, are available for inspection during 
    normal business hours at RUS, room 2845, U.S. Department of 
    Agriculture, 1400 Independence Avenue, SW., STOP 1598, Washington, DC 
    20250-1598 or at the Office of the Federal Register, 800 North Capitol 
    Street, NW., suite 700, Washington, DC.
        (d) For all customer access locations of less than 12 pairs, RUS 
    borrowers shall establish DPs by using either NIDs or fused primary 
    station protectors when required by Section 800-30(a)(2) of the ANSI/
    NFPA 70-1996, NEC. For customer access locations of 12 
    pairs or greater, RUS borrowers shall establish DPs using either NIDs, 
    BETs, or fused primary station protectors when required by Section 800-
    30(a)(2) of the ANSI/NFPA 70-1996, NEC.
    
    
    Sec. 1755.505  Buried services.
    
        (a) Buried services of two or three pairs shall consist of Service 
    Entrance, Buried (SEB) assembly units, in accordance with RUS Bulletin 
    345-154 (RUS Form 515g), Specifications and Drawings for Service 
    Entrance and Station Protector Installations. The wire used for buried 
    services shall conform to the requirements of Sec. 1755.860, RUS 
    specification for filled buried wires, and shall be RUS accepted or RUS 
    technically accepted. The conductor size for two and three pair buried 
    service wires shall be 22 American Wire Gauge (AWG). Copies of RUS 
    Bulletin 345-154 are available upon request from RUS/USDA, 1400 
    Independence Avenue, SW., STOP 1522, Washington, DC 20250-1522, FAX 
    (202) 690-2268.
        (b) Buried services of six or more pairs shall be RUS accepted or 
    RUS technically accepted 22 AWG filled buried cable conforming to the 
    requirements of Sec. 1755.390, RUS specification filled telephone 
    cables.
        (c) Buried service wire or cable shall be terminated in buried 
    plant housings using either splicing connectors or filled terminal 
    blocks in accordance with the applicable paragraphs of Sec. 1755.200, 
    RUS standard for splicing copper and fiber optic cables.
        (d) Buried service wire or cable shall be identified at buried 
    plant housings in accordance with construction drawing 958 contained in 
    Sec. 1755.510.
        (e) Buried service wire or cable shall be installed up to the 
    building in the same general manner as buried exchange cable but in 
    addition must meet the following requirements:
        (1) Light weight lawn plows or trenchers shall be used;
        (2) The shortest feasible route commensurate with the requirements 
    of Sec. 1755.508 (i), (j), and (k) and paragraph (f)(1) of this section 
    shall be followed;
        (3) Buried service wire or cable shall be plowed or trenched to a 
    depth of 24 in. (610 mm) or greater where practicable in soil, 36 in. 
    (914 mm) in ditches, or 3 in. (76 mm) in rock. Depths shall be measured 
    from the top of the wire or cable to the surface of the ground or rock;
        (4) In the case of a layer of soil over rock either the minimum 
    depth in rock measured to the surface of the rock, or the minimum depth 
    in soil measured to the surface of the soil may be used; and
        (5) Where adequate advance planning has been done, burial of 
    telecommunications services jointly with electric power services may be 
    feasible. If a decision has been reached by management to provide joint 
    occupancy services, the services may be installed using the 
    recommendations in
    
    [[Page 70461]]
    
    RUS Bulletin 305-1, ``Joint Use of Facilities for Telephone and 
    Electric Service.'' Copies of RUS Bulletin 305-1 are available upon 
    request from RUS/USDA, 1400 Independence Avenue, SW., STOP 1522, 
    Washington, DC 20250-1522, FAX (202) 690-2268.
        (f) Buried service wire or cable shall be installed on or in 
    buildings as follows:
        (1) Each buried service wire or cable shall contact the building as 
    close to the NID, BET, or fused primary station protector as 
    practicable. Service wire or cable runs on buildings shall normally 
    consist of a single vertical run held to the minimum practical length. 
    Horizontal and diagonal runs shall not be permitted.
        (2) Buried service wire or cable shall be located so as to avoid 
    damage from lawn mowers, animals, gardening operations, etc.
        (3) Buried service wire or cable shall be installed against a 
    foundation wall or pillar to provide adequate support and mechanical 
    protection.
        (4) Where it is likely that the service wire or cable shall be 
    subjected to mechanical damage, the wire or cable shall be enclosed in 
    a guard in accordance with assembly unit drawing BM83 contained in 
    Sec. 1755.510.
        (5) The first above-ground attachment for a buried service wire or 
    cable, unless it is enclosed in a guard, shall not be more than 4 in. 
    (100 mm) above final grade.
        (6) Uninsulated attachment devices may be used to attach buried 
    service wire and cable to masonry and other types of noncombustible 
    buildings and on any type of building if fuseless primary station 
    protectors incorporated in NIDs or BETs are used and installations 
    fully comply with Section 800-30(a)(1) of the ANSI/NFPA 70-1996, 
    NEC. The National Electrical Code and 
    NEC are registered trademarks of the National Fire 
    Protection Association, Inc., Quincy, MA 02269. The ANSI/NFPA 70-1996, 
    NEC, is incorporated by reference in accordance with 5 
    U.S.C. 552(a) and 1 CFR part 51. Copies are available from NFPA, 1 
    Batterymarch Park, P.O. Box 9101, Quincy, Massachusetts 02269-9101, 
    telephone number 1 (800) 344-3555. Copies of ANSI/NFPA 70-1996, 
    NEC, are available for inspection during normal business 
    hours at RUS, room 2845, U.S. Department of Agriculture, 1400 
    Independence Avenue, SW., STOP 1598, Washington, DC 20250-1598 or at 
    the Office of the Federal Register, 800 North Capitol Street, NW., 
    suite 700, Washington, DC.
        (7) Insulated attachments shall be used to separate service wires 
    or cables from woodwork where Section 800-30(a)(2) of the ANSI/NFPA 70-
    1996, NEC, requiring the use of fused primary station 
    protectors must be observed.
        (8) Minimum separation between buried service wire or cable and 
    other facilities shall be as listed in Table 1, as follows:
    
     Table 1.--Minimum Separation for Telecommunications Wires and Cables On
                                 or In Buildings
    ------------------------------------------------------------------------
                                               Minimum clearance in. [mm]1 2
         Foreign facility or obstruction       telecommunications company's
                                                      wires or cables
    ------------------------------------------------------------------------
    Electric supply wire including neutral
     and grounding conductors.
        Open................................  4 [102]
        In conduit..........................  2 [50.8]
    Radio and television antennas, lead-in    4 [102]
     and grounding conductors.
    Lightning rods and lightning conductors.  72 [1830] \3\
    All foreign grounding conductors except   2 [50.8]
     lightning rod ground conductors.
    Neon signs and associated wiring........  6 [150]
    Metallic objects--pipes (gas, cold        2 [50.8] \4\
     water, oil, sewer,) and structures.
    Wires or cables of another                2 [50.8]
     communications system.
    ------------------------------------------------------------------------
    Notes: \1\ If minimum separation cannot be obtained, nonshielded wire
      and cable facilities shall be protected with either porcelain tubes or
      flexible tubing as modified by Notes 3 and 4 of this table.
    \2\ Separation applies to crossings and parallel runs.
    \3\ If this separation cannot be obtained, bond the telecommunications
      grounding conductors or grounding electrode to the lightning rod
      grounding conductor or grounding electrode with at least a Number
      (No.) 6 AWG copper, insulated, ground wire. With this provision a
      minimum separation of 4 in. (100 mm) is acceptable but this provision
      must not be utilized if the separation cited in this table can be
      maintained.
    \4\ Increase to a minimum of 3 in. (75 mm) separation from steam or hot
      water pipes, heating ducts, and other heat sources.
    
        (9) Wire and cable attachments to buildings for outside mounted 
    NIDs, BETs, or fused primary station protectors shall be in accordance 
    with construction drawing 962 contained in Sec. 1755.510.
        (10) Appropriate devices for attaching service wire or cable on or 
    in buildings vary with the type of building construction and the wire 
    or cable size. Figures 1 and 2 illustrate various types of anchoring 
    devices and their applications. The size and type of fastening device 
    for the wire or cable size and type of surface shall be in accordance 
    with the manufacturer's recommendation; Figures 1 and 2 are as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70462]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.000
    
    
    
    [[Page 70463]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.001
    
    
    
        (11) Experience indicates that there are strenuous objections from 
    many owners of buildings covered with aluminum or vinyl siding to the 
    drilling of holes in the siding for the attachment of wires or cables, 
    and NIDs, BETs, or fused primary station protectors. It is, therefore, 
    important to obtain permission from the owner before drilling holes in 
    such siding.
        (12) If the NID, BET, or fused primary station protector must be 
    mounted
    
    [[Page 70464]]
    
    inside (not recommended by RUS), the service entrance into the building 
    shall be installed in accordance with Section 800-12(c) of the ANSI/
    NFPA 70-1996, NEC. After pulling-in the wire or cable, the 
    free space around the cable or wire shall be carefully sealed both 
    outside and inside with a duct sealer that has RUS acceptance or RUS 
    technical acceptance.
        (13) If the customer requests an all buried installation for an 
    alarm system or objects to above-ground facilities because of 
    appearance and one-party service is involved, the entrance hole shall 
    be made below grade as shown in sketch C of construction drawing 510-2 
    contained in Sec. 1755.510. Care shall be exercised to prevent damage 
    to the building foundation. The hole shall be sealed as specified in 
    paragraph (f)(12) of this section. The installation shall comply with 
    all the requirements of Section 800-12(c) of the ANSI/NFPA 70-1996, 
    NEC.
        (g) When the NID, BET, or fused primary station protector is to be 
    installed inside the building, the installation shall comply with 
    Section 800-12(c) of the ANSI/NFPA 70-1996, NEC, and the 
    outside plant wire or cable shall preferably be installed in a rigid 
    metal or intermediate metal conduit that is grounded to an electrode in 
    accordance with Section 800-40(b) of the ANSI/NFPA 70-1996, 
    NEC, as shown in sketch A of Figure 3 in paragraph (h)(2) 
    of this section. The shield of the outside plant wire or cable shall be 
    bonded to the grounding terminal of the NID, BET, or fused primary 
    station protector which in turn shall be connected to the closest, 
    existing, and accessible grounding electrode, of the electrodes cited 
    in Section 800-40 of the ANSI/NFPA 70-1996, NEC.
        (h) An inside NID, BET, or fused primary station protector 
    installation may also be made without use of a rigid metal or 
    intermediate metal conduit provided that the ingress of the outside 
    plant wire or cable complies with Section 800-12(c) of the ANSI/NFPA 
    70-1996, NEC, and provided either of the following are 
    observed:
        (1) The NID, BET, or fused primary station protector is located as 
    close as practicable to the point where the outside plant wire or cable 
    emerges through an exterior wall. The length of outside plant wire or 
    cable exposed within the building shall be as short as practicable but 
    in no case shall it be longer than 50 feet (ft) [15.2 meters (m)] in 
    accordance with the allowable exception No. 3 of Section 800-50 of the 
    ANSI/NFPA 70-1996, NEC. See sketch B of Figure 3 in 
    paragraph (h)(2) of this section. The shield of the outside plant wire 
    or cable shall be bonded to the grounding terminal of the NID, BET, or 
    fused primary station protector which in turn shall be connected to the 
    closest, existing and accessible grounding electrode, of the electrodes 
    cited in Section 800-40 of the ANSI/NFPA 70-1996, NEC (Fine 
    print Note No. 2 of ANSI/NFPA 70-1996, NEC, Section 800-50, 
    warns that the full 50 ft (15.2 m) may not be authorized for outside 
    unlisted cable (not in a metal or intermediate metal conduit) within a 
    building if it is practicable to place the NID, BET, or fused primary 
    station protector closer than 50 ft (15.2 m) to the cable entrance 
    point, e.g., if there is an acceptable and accessible grounding 
    electrode of the type cited in Section 800-40 of the ANSI/NFPA 70-1996, 
    NEC, anywhere along the proposed routing of the outside 
    cable within the building); or
        (2) Where the NID, BET, or fused primary station protector must be 
    located within the building remote from the entrance point and the 
    entrance point of the outside plant wire or cable cannot be designed to 
    be closer to the NID, BET, or fused primary station protector location, 
    the outside plant wire or cable shall be spliced, as close as 
    practicable to the point where the outside plant wire or cable emerges 
    through an outside wall, to an inside wiring cable that is ``Listed'' 
    as being suitable for the purpose in accordance with Part E of Article 
    800 of the ANSI/NFPA 70-1996, NEC. The length of outside 
    plant wire or cable exposed within the building shall be as short as 
    practicable but in no case shall it be longer than 50 ft (15.2 m) in 
    accordance with the allowable exception No. 3 of Section 800-50 of the 
    ANSI/NFPA 70-1996, NEC. See sketch C of Figure 3. The 
    shield of the outside plant wire or cable shall be bonded to the 
    grounding terminal of the NID, BET, or fused primary station protector 
    which in turn shall be connected to the closest, existing, and 
    accessible grounding electrode, of the electrodes cited in Section 800-
    40 of the ANSI/NFPA 70-1996, NEC (Fine print Note No. 2 of 
    the ANSI/NFPA 70-1996, NEC, Section 800-50, warns that the 
    full 50 ft (15.2 m) may not be authorized for outside unlisted cable 
    (not in a metal or intermediate metal conduit) if it is practicable to 
    place the NID, BET, or fused primary station protector closer than 50 
    ft (15.2 m) to the cable entrance point, e.g., if there is an 
    acceptable and accessible grounding electrode of the type cited in 
    Section 800-40 of the ANSI/NFPA 70-1996, NEC, anywhere 
    along the proposed routing of the outside cable within the building). 
    Figure 3 is as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70465]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.002
    
    
    
    [[Page 70466]]
    
        (i) The polarity of buried wire or cable ``tip'' and ``ring'' 
    conductors shall be maintained by making the connections in accordance 
    with Table 2, as follows:
    
                                            Table 2.--Color Codes for Tip and Ring Connections of Inside Wiring Cable
    --------------------------------------------------------------------------------------------------------------------------------------------------------
                                                                     Tip                                                      Ring
                    Pair                 -------------------------------------------------------------------------------------------------------------------
                                              Color of insulation            Color of marking           Color of insulation            Color of marking
    --------------------------------------------------------------------------------------------------------------------------------------------------------
     1..................................  White......................  Blue.......................  Blue.......................  White
     2..................................  White......................  Orange.....................  Orange.....................  White
     3..................................  White......................  Green......................  Green......................  White
     4..................................  White......................  Brown......................  Brown......................  White
     5..................................  White......................  Slate......................  Slate......................  White
     6..................................  Red........................  Blue.......................  Blue.......................  Red
     7..................................  Red........................  Orange.....................  Orange.....................  Red
     8..................................  Red........................  Green......................  Green......................  Red
     9..................................  Red........................  Brown......................  Brown......................  Red
    10..................................  Red........................  Slate......................  Slate......................  Red
    11..................................  Black......................  Blue.......................  Blue.......................  Black
    12..................................  Black......................  Orange.....................  Orange.....................  Black
    13..................................  Black......................  Green......................  Green......................  Black
    14..................................  Black......................  Brown......................  Brown......................  Black
    15..................................  Black......................  Slate......................  Slate......................  Black
    16..................................  Yellow.....................  Blue.......................  Blue.......................  Yellow
    17..................................  Yellow.....................  Orange.....................  Orange.....................  Yellow
    18..................................  Yellow.....................  Green......................  Green......................  Yellow
    19..................................  Yellow.....................  Brown......................  Brown......................  Yellow
    20..................................  Yellow.....................  Slate......................  Slate......................  Yellow
    21..................................  Violet.....................  Blue.......................  Blue.......................  Violet
    22..................................  Violet.....................  Orange.....................  Orange.....................  Violet
    23..................................  Violet.....................  Green......................  Green......................  Violet
    24..................................  Violet.....................  Brown......................  Brown......................  Violet
    25..................................  Violet.....................  Slate......................  Slate......................  Violet
    --------------------------------------------------------------------------------------------------------------------------------------------------------
    
    Sec. 1755.506  Aerial wire services.
    
        (a) Aerial services of one through six pairs shall consist of 
    Service Entrance, Aerial (SEA) assembly units, in accordance with RUS 
    Bulletin 345-154 (RUS Form 515g), Specifications and Drawings for 
    Service Entrance and Station Protector Installations. The wire used for 
    aerial services shall conform to the requirements of Secs. 1755.700 
    through 7 CFR 1755.704, RUS specification for aerial service wires, and 
    shall be RUS accepted or RUS technically accepted. Copies of RUS 
    Bulletin 345-154 are available upon request from RUS/USDA, 1400 
    Independence Avenue, SW., STOP 1522, Washington, DC 20250-1522, FAX 
    (202) 690-2268.
        (b) If aerial wire services are to be connected to aerial cable 
    pairs, the NIDs or fused primary station protectors and grounds shall 
    be installed and connected before the aerial service wires are attached 
    to the customer's structure.
        (c) Kinks or splices shall not be permitted in aerial service wire 
    spans.
        (d) Aerial service wires shall be run in accordance with the 
    construction drawings contained in Sec. 1755.510 and shall conform to 
    all clearance requirements of the ANSI/NFPA 70-1996, NEC, 
    and ANSI/IEEE C2-1997, NESC, or local laws or ordinances, whichever are 
    the most stringent. The National Electrical Code and 
    NEC are registered trademarks of the National Fire 
    Protection Association, Inc., Quincy, MA 02269. The ANSI/NFPA 70-1996, 
    NEC, and ANSI/IEEE C2-1997, NESC, are incorporated by 
    reference in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. Copies 
    of ANSI/NFPA 70-1996, NEC, are available from NFPA, 1 
    Batterymarch Park, P.O. Box 9101, Quincy, Massachusetts 02269-9101, 
    telephone number 1 (800) 344-3555. Copies of ANSI/IEEE C2-1997, NESC, 
    are available from IEEE Service Center, 455 Hoes Lane, Piscataway, New 
    Jersey 08854, telephone number 1 (800) 678--4333. Copies of ANSI/NFPA 
    70-1996, NEC, and ANSI/IEEE C2-1997, NESC, are available 
    for inspection during normal business hours at RUS, room 2845, U.S. 
    Department of Agriculture, 1400 Independence Avenue, SW., STOP 1598, 
    Washington, DC 20250-1598 or at the Office of the Federal Register, 800 
    North Capitol Street, NW., suite 700, Washington, DC.
        (e) Aerial service wire shall be installed using the maximum 
    practicable sag consistent with the required ground clearance and good 
    construction practices. In no event shall the minimum sags be less than 
    the values shown on construction drawing 505 contained in Sec. 1755.510 
    for various span lengths and loading areas provided. Span lengths shall 
    not exceed 250 ft (76 m).
        (f) To reduce vibration and galloping, aerial service wire shall be 
    twisted one complete turn for each 10 ft (3 m) of span length at the 
    time of installation.
        (g) The methods of attaching aerial service wires at poles shall be 
    as illustrated in construction drawings 503-2 and 504 contained in 
    Sec. 1755.510.
        (h) A horizontal climbing space of 24 in. (610 mm) shall be 
    provided on poles used jointly with power circuits that operate at 300 
    volts or less, provided the telecommunications conductors are 
    positioned below the power conductors; however, if the 
    telecommunications conductors are installed above power conductors that 
    operate at 300 volts or less (a practice which is highly discouraged 
    and not practicable), a horizontal climbing space of 30 in. (762 mm) 
    shall be provided as indicated on construction drawing 702 contained in 
    Sec. 1755.510. A climbing space of 30 in. (762 mm) shall be provided on 
    poles used jointly with power circuits that operate at voltages greater 
    than 300 volts but less than 15 kilovolts (kV) as indicated on 
    construction drawing 702 contained in Sec. 1755.510. On jointly used 
    poles with power conductors operating at voltages greater than 15 kV, 
    climbing space shall be provided in conformance
    
    [[Page 70467]]
    
    with the requirements of Rule 236 of the ANSI/IEEE C2-1997, NESC. 
    Climbing space shall be projected vertically 40 in. (1.02 m) above and 
    below the bounding telecommunications conductors on jointly used poles 
    with power conductors unless the telecommunications conductors are 
    installed above the power conductors (a practice which is highly 
    discouraged and not practicable) and the power conductors operate at 
    voltages greater than 8.7 kV line-to-ground or 15 kV line-to-line, in 
    which case the projected vertical space shall be increased to 60 in. 
    (1.5 m).
        (i) Not more than four aerial service wires shall be distributed 
    from any one in \7/16\ in. (10 mm) drive hook, or more than two aerial 
    service wires from any one \5/16\ in. (8 mm) drive hook. Aerial service 
    wires and drive hooks shall be arranged so that the load does not pull 
    the drive hook out of the pole. When more than one drive hook is 
    required, the drive hooks shall be staggered with a minimum separation 
    of 1 in. (25.4 mm) horizontally on centers and 1.5 in. (40 mm) 
    vertically on centers. If drive hooks are placed within 3 in. (76 mm) 
    of the top of the pole and on the opposite side of the pole's 
    circumference, a vertical separation of at least 3 in. (76 mm) shall be 
    provided. A drive hook shall not be placed on the top of a pole or stub 
    pole.
        (j) When connecting aerial service wires to cable pairs at 
    terminals, sufficient slack shall be provided so that each aerial 
    service wire shall reach any binding post position as shown on 
    construction drawing 312-1 contained in Sec. 1755.510.
        (k) Aerial service wire attachments on utility poles and the manner 
    of placing bridle rings and entering cable terminals shall be as shown 
    on construction drawing 503-2 contained in Sec. 1755.510.
        (l) Not more than two conductors shall be connected to any terminal 
    binding post. Where it is necessary to bridge more than two aerial 
    service wires at the same closure, the aerial service wires shall be 
    terminated in aerial service wire terminals connected in parallel with 
    a No. 20 AWG bridle wire which shall be terminated on the binding posts 
    of the filled terminal block.
        (m) Where aerial service wire is attached to aerial plastic cable, 
    it shall be brought directly into a ready-access closure and shall be 
    terminated on the binding posts of the filled terminal block as shown 
    on construction drawing 503-2 contained in Sec. 1755.510.
        (n) The conductor of copper coated steel reinforced aerial service 
    wires identified by tracer ridges shall be used as the ring (negative 
    battery) conductor of the pair, and shall normally be connected to the 
    right or lower binding post of a pair on filled terminal blocks and 
    NIDs or fused primary station protectors.
        (o)(1) The tip and ring conductors of nonmetallic reinforced aerial 
    service wires shall be identified in accordance with Table 3, as 
    follows:
    
         Table 3.--Nonmetallic Reinforced Aerial Service Wire Color Code
    ------------------------------------------------------------------------
                                                Conductor color
               Pair No           -------------------------------------------
                                           Tip                  Ring
    ------------------------------------------------------------------------
    1...........................  White/Blue or White.  Blue.
    2...........................  White/Orange or       Orange.
                                   White.
    3...........................  White/Green or White  Green.
    4...........................  White/Brown or White  Brown.
    5...........................  White/Slate or White  Slate.
    6...........................  Red/Blue or Red.....  Blue.
    ------------------------------------------------------------------------
    
        (2) The ring (negative battery) conductor of the pair shall 
    normally be connected to the right or lower binding post of a pair on 
    filled terminal blocks and NIDs or fused primary station protectors.
        (p) When it is necessary to avoid intervening obstacles between a 
    pole and a building, span clamp attachments shall be used to support 
    the aerial service wires at points between the poles that are 
    supporting the cable on the suspension strand as indicated by 
    construction drawings 501-1 and 501-2 contained in Sec. 1755.510.
        (q) Aerial service wire strung from pole to pole shall be placed 
    entirely below or entirely above any existing wire or cable. When 
    adequate ground clearance can be obtained, preference shall be given to 
    placing aerial service wire below wire and cable.
        (r) When more than one aerial service wire is installed from pole 
    to pole, the first aerial service wire shall be sagged in accordance 
    with construction drawing 505 contained in Sec. 1755.510. Succeeding 
    aerial service wires shall be sagged with 2 in. (50.8 mm) more sag for 
    each aerial service wire.
        (s) Aerial service wire spans from pole lines to buildings shall 
    follow the shortest feasible route commensurate with the requirements 
    of paragraph (t) of this section and shall be sagged in accordance with 
    construction drawing 505 contained in Sec. 1755.510. The route shall 
    avoid trees and other obstructions to the extent practicable. Where 
    trees cannot be avoided, tree trimming permission shall be obtained 
    from the owner or the owner's representative, and all limbs and foliage 
    within 2 ft (600 mm) of the finally sagged wire shall be removed. If 
    tree trimming permission cannot be obtained, the matter shall be 
    referred to the borrower for resolution before proceeding with the 
    installation.
        (t) Aerial service wires shall contact buildings as closely as 
    practicable at a point directly above the NID, or fused primary station 
    protector. Generally, horizontal drop wire runs on buildings shall not 
    exceed 20 ft (6 m). The warning given in Sec. 1755.505(f)(11) regarding 
    drilling holes in aluminum and vinyl siding applies also to attaching 
    aerial service wires.
        (u) The point of the first building attachment shall be located so 
    that the aerial service wire will be clear of roof drainage points.
        (v) Where practicable, aerial service wires shall pass under 
    electrical guys, power distribution secondaries and services, tree 
    limbs, etc.
        (w) Aerial service wire shall not pass in front of windows or 
    immediately above doors.
        (x) Aerial service wires shall be routed so as to have a minimum 
    clearance of 2 ft (600 mm) from any part of a short wave, ham radio, 
    etc. antenna mast and a television antenna mast in its normal vertical 
    position and of the possible region through which it sweeps when being 
    lowered to a horizontal position.
        (y) Aerial service wires shall be installed such that all 
    clearances and separations comply with either Section 237 of the ANSI/
    IEEE C2-1997, NESC, or ANSI/NFPA 70-1996, NEC, or local
    
    [[Page 70468]]
    
    laws or ordinances, whichever is the most stringent.
        (z) Aerial service wire attachments to buildings shall be as 
    follows:
        (1) First attachments on buildings shall be made in accordance with 
    construction drawings 506, 507, or 508-1 contained in Sec. 1755.510, as 
    applicable;
        (2) Intermediate attachments on buildings shall be made in 
    accordance with construction drawings 510 or 510-1 contained in 
    Sec. 1755.510; and
        (3) Uninsulated attachments shall be permitted to be used as 
    follows:
        (i) Wherever NIDS are used as permitted by Section 800-30(a)(1) of 
    the ANSI/NFPA 70-1996, NEC; and
        (ii) On masonry and other types of nonflammable buildings.
        (aa) Insulated attachments shall be used on wooden frame, metallic 
    siding and other types of combustible buildings where fused primary 
    station protectors are used, as required by Section 800-30(a)(2) of the 
    ANSI/NFPA 70-1996, NEC.
        (bb) Aerial service wire runs on buildings shall be attached 
    vertically and/or horizontally in a neat and most inconspicuous 
    possible manner. See construction drawing 513 contained in 
    Sec. 1755.510. Horizontal runs on buildings are undesirable and shall 
    be kept to a minimum. Diagonal runs shall not be made.
        (cc) Aerial service wire runs on buildings shall be located so as 
    not to be subjected to damage from passing vehicles, pedestrians, or 
    livestock.
        (dd) Minimum separation between aerial service wires and other 
    facilities on or in buildings shall be in accordance with 
    Sec. 1755.505(f)(8),
    Table 1.
        (ee) Appropriate devices for attaching aerial service wires to 
    buildings vary with the type of building construction and with the type 
    of customer access location equipment. Table 4 lists various types of 
    attachments and their application with respect to construction, 
    customer access location equipment, and proper mounting devices. 
    Construction drawings 506 through 513 contained in Sec. 1755.510 
    illustrate requirements with respect to various angles of service wire 
    contacts and uses of various attachments. Table 4 is as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70469]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.003
    
    
    
    [[Page 70470]]
    
        Notes: \1\ Screw dimensions are minimum. Where appropriate, 
    either or both dimensions shall be increased. All wood screws for 
    exterior use shall be stainless steel. All other exterior metal 
    devices shall be stainless steel, zinc coated steel, silicon bronze, 
    or corrosion resistant aluminum alloy.
        \2\ Toggle bolt dimensions are minimum. Where appropriate, 
    either or both dimensions shall be increased.
        \3\ All devices should be attached to studding.
        \4\ Screw-type devices shall be secured by means of expansion-
    type anchors. Equivalent manual or machine-driven devices may be 
    used. Where toggle bolts are specified equivalent devices may be 
    used.
        \5\ Pilot holes shall be provided for screws and bridle rings in 
    shingles and dropsiding.
        \6\ Attachment device not applicable.
        \7\ Attachment device applicable but no separate fastening 
    device required.
        \8\ To convert English units to Metric units use 1 in. = 25.4 
    mm.
    
        (ff) Fastener spacings for vertical and horizontal runs on frame or 
    masonry buildings shall not be more than 6 ft (2 m) apart. Fasteners 
    should be spaced close enough to prevent the aerial service wire from 
    ``slapping'' against the building during windy conditions.
        (gg) When it is necessary to pass behind or around obstructions 
    such as downspouts and vertical conduits, the aerial service wire shall 
    be supported firmly with attachment devices placed not more than 6 in. 
    (152 mm) from the obstruction as illustrated in Figures 4 and 5 of 
    paragraph (hh) of this section. Preferably, the aerial service wire 
    should be routed behind obstructions to minimize the possibility of 
    mechanical damage to the aerial service wire in the event repair work 
    to the obstruction is required.
        (hh) When passing around building projections of masonry or wood or 
    around corners, aerial service wires shall be installed as illustrated 
    in Figures 5 and 6. Figures 4, 5, and 6 are as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70471]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.004
    
    
    
    [[Page 70472]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.005
    
    
    
    [[Page 70473]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.006
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70474]]
    
        (ii) In areas where ice and snow conditions are severe, aerial 
    service wires shall be located so that ice and snow falling from the 
    roof will not strike the wires. However, where aerial service wires 
    must pass under the sloping part of the roof, first attachments shall 
    be made as close as practicable to the eaves.
        (jj) If two aerial service wire spans are required to the same 
    building, the first attachment shall be such that both aerial service 
    wires can be attached at the same attachment device. Refer to 
    construction drawing 508-1 contained in Sec. 1755.510. Where more than 
    two aerial service wires are required, additional attachment devices in 
    the same general location on the building shall be used.
        (kk) When two or more aerial service wire runs are required on the 
    same building they shall share the same type of attachment devices.
        (ll) Aerial service wire entrances to buildings shall conform to 
    sketch B of construction drawing 510-2 contained in Sec. 1755.510, 
    unless the entrance is made through a conduit.
        (mm) When the aerial service wire approaches the entrance hole from 
    above, a 1.5 in. (40 mm) minimum drip loop shall be formed in 
    accordance with sketch B of construction drawing 510-2 contained in 
    Sec. 1755.510.
        (nn) If an entrance conduit which slopes upward from outside to 
    inside is available and suitably located, it shall be used for the 
    aerial service wire entrance.
    
    
    Sec. 1755.507  Aerial cable services.
    
        (a) Where more than six pairs are needed initially, and where an 
    aerial service is necessary, the service shall consist of 22 AWG filled 
    aerial cable of a pair size adequate for the ultimate anticipated 
    service needs of the building. The cable shall comply with the 
    requirements of Sec. 1755.390, RUS Specification for Filled Telephone 
    Cables, and shall be RUS accepted or RUS technically accepted.
        (b) Aerial cable services shall be constructed in accordance with 
    specific installation specifications prepared by the RUS borrower or 
    the engineer delegated by the borrower.
        (c) Unless otherwise specified in the installation specifications, 
    aerial cable service installations shall meet the following 
    requirements:
        (1) Strand supported lashed construction shall be used.
        (2) Where practicable a \5/16\ in. (8 mm) utility grade strand and 
    automatic clamps shall be used in slack spans to avoid damage to the 
    building.
        (3) Construction on poles shall comply with applicable construction 
    drawings for regular line construction. Aerial service cable shall be 
    spliced to the main cable in accordance with Sec. 1755.200, RUS 
    standard for splicing copper and fiber optic cables.
        (4) Where practicable, aerial cable shall pass under electrical 
    guys, distribution secondaries, and services.
        (5) The suspension strand shall be attached to the building by wall 
    brackets as indicated in Figure 7 as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70475]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.007
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70476]]
    
        (i) If taut spans are necessary, appropriate size strand may be 
    used if the pull is in line with one wall of the building, or within 20 
    degrees of being in line as illustrated in sketch A of Figure 7. If the 
    angle of pull is greater than 20 degrees from the building, the wall 
    bracket shall be reinforced against pullout by an arrangement 
    equivalent to sketch B of Figure 7. Taut spans may be strung using the 
    recommendations in RUS Bulletin 1751F-630, Design of Aerial Plant. The 
    same tension as would be used in normal line construction so as not to 
    exceed 60 percent of the breaking strength of the strand under maximum 
    loading shall be used. Taut spans shall not exceed 100 ft (30.5 m) in 
    length and the cable weight shall not exceed 1 pound/foot (lb/ft) [1.5 
    kilogram/meter (kg/m)] except when equivalent combinations of greater 
    span lengths with cable weight less than 1 lb/ft (1.5 kg/m) are 
    permissible. Copies of RUS Bulletin 1751F-630 are available upon 
    request from RUS/USDA, 1400 Independence Avenue, SW., STOP 1522, 
    Washington, DC 20250-1522, FAX (202) 690-2268.
        (ii) When an attachment must be made to the face of a building wall 
    away from a corner, a ``U'' type wall bracket shall be used as 
    indicated in sketch C of Figure 7 of this paragraph (c)(5). Only slack 
    span construction with \5/16\ in. (8 mm) utility grade strand shall be 
    permitted in this situation. The bail of the automatic clamp shall be 
    protected by a wire rope thimble.
        (6) Aerial cable shall be located on the rear or side of the 
    building and shall be run only in a horizontal or a vertical direction. 
    The cable route shall be selected so as to avoid building projections 
    and obstructions to the extent practicable.
        (7) Cable attachment devices shall be located in solid masonry or 
    in studs of wood frame buildings. Sheet surface materials may be used 
    only where they are reinforced by substantial backing material which 
    the attachment services can penetrate.
        (8) The minimum separation on or in buildings between cable and 
    other facilities shall be as indicated in Sec. 1755.505(f)(8), Table 1.
        (9) On horizontal runs, place cable clamps so that the attachment 
    shall be made below the cable. On vertical runs place the cable clamps 
    so that the attachment shall be made on the same side as horizontal 
    runs. Cable clamps shall be placed on the inside of cable bends.
        (10) On horizontal runs, cable clamps shall be placed not more than 
    16 in. (400 mm) apart for cable diameters equal to or greater than 1 
    in. (25.4 mm) and 24 in. (600 mm) apart for cable diameters less than 1 
    in. (25.4 mm).
        (11) On vertical runs, cable clamps shall be approximately 24 in. 
    (600 mm) apart for all sizes of cable.
        (12) For the cable entrance, holes shall be bored slightly larger 
    in diameter than the cable and shall slope upward from outside to 
    inside. A duct sealer having RUS acceptance or RUS technical acceptance 
    shall be applied to both ends of the hole after the cable is pulled in.
        (13) Section 1755.505 (g) and (h) shall also apply to aerial cable 
    services.
    
    
    Sec. 1755.508  Customer access location protection.
    
        (a) All customer access locations shall be protected.
        (b) Customer access location protection shall consist of installing 
    the telecommunications facilities with proper clearances and insulation 
    from other facilities, providing primary voltage limiting protection, 
    fuse links, NIDs, BETs, or fused primary station protectors, if 
    required, and adequate bonding and grounding.
        (c) All NIDs shall be RUS accepted or RUS technically accepted or 
    the RUS borrower shall obtain RUS regional office approval on a case by 
    case basis as applicable.
        (d) All BETs shall be RUS accepted or RUS technically accepted.
        (e) All fused primary station protectors shall be RUS accepted or 
    RUS technically accepted.
        (f) NIDs, BETs, or fused primary station protectors shall be 
    mounted outside for all applications except for those described in 
    paragraphs (g) introductory text through (g)(3) of this section.
        (g) NIDs, BETs, or fused primary station protectors may be mounted 
    inside when:
        (1) Large buildings are to be served and the customer requests an 
    inside installation;
        (2) Buried alarm circuits are requested by the subscriber; or
        (3) The customer requests an all buried installation for appearance 
    or to prevent the drilling of holes in aluminum or vinyl siding.
        (h) Outside mounted NIDs, BETs, or fused primary station protectors 
    shall be easily accessible and shall be located between 3 to 5 ft (1 to 
    1.5 m) above final grade.
        (i) The locations of NIDs, BETs, or fused primary station 
    protectors shall be selected with emphasis on utilizing the shortest 
    primary station protector grounding conductor practicable and on 
    grounding of the telecommunications primary station protector to the 
    electric service grounding system established at the building served 
    utilizing electrodes (3) through (7) cited in Section 800-40(b)(1) of 
    the ANSI/NFPA 70-1996, NEC. The National Electrical 
    Code and NEC are registered trademarks of the 
    National Fire Protection Association, Inc., Quincy, MA 02269. The ANSI/
    NFPA 70-1996, NEC, is incorporated by reference in 
    accordance with 5 U.S.C. 552(a) and 1 CFR part 51. Copies are available 
    from NFPA, 1 Batterymarch Park, P.O. Box 9101, Quincy, Massachusetts 
    02269-9101, telephone number 1 (800) 344-3555. Copies of ANSI/NFPA 70-
    1996, NEC, are available for inspection during normal 
    business hours at RUS, room 2845, U.S. Department of Agriculture, 1400 
    Independence Avenue, SW., STOP 1598, Washington, DC 20250-1598 or at 
    the Office of the Federal Register, 800 North Capitol Street, NW., 
    suite 700, Washington, DC.
        (j) If access to the building electric service grounding system, as 
    referenced in paragraph (i) of this section, is not possible or is not 
    reasonable [telecommunications primary station protector grounding 
    conductor will be longer than 10 ft (3 m)], the NID, BET, or fused 
    primary station protector shall be located as close as practicable to 
    electrodes (1) or (2) cited in Section 800-40(b)(1) of the ANSI/NFPA 
    70-1996, NEC.
        (k) In addition, the NID, BET, or fused primary station protector 
    shall be located in, on, or immediately adjacent to the structure or 
    building to be served as close as practicable to the point at which the 
    telecommunications service wire attaches to the building, making sure 
    that the telecommunications primary station protector grounding 
    conductor is connected to the closest, existing, and accessible 
    electrode, of the electrodes cited in paragraphs (i) or (j) of this 
    section.
        (l) For the preferred customer access location installation, the 
    ANSI/NFPA 70-1996, NEC, permits the telecommunications 
    grounding conductor to be connected to the metallic conduit, service 
    equipment closure, or electric grounding conductor as shown in Figure 8 
    of paragraph (l)(2) of this section.
        (1) Connections to metallic conduits shall be made by ground straps 
    clamped over a portion of the conduit that has been cleaned by sanding 
    down to bare metal.
        (2) Connections to metallic service equipment closures shall be 
    made by attaching a connector which is listed for the purpose by some 
    organization acceptable to the local authority (State, county, etc.) 
    per Article 100 of the
    
    [[Page 70477]]
    
    ANSI/NFPA 70-1996, NEC, definition for ``Listed'' [for 
    example connectors listed for the purpose by Underwriters Laboratories 
    (UL)]. Figure 8 is as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70478]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.008
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70479]]
    
        (m) Where it is not possible to accomplish the objective of 
    paragraphs (i), (j), and (k) of this section, interior metallic pipes 
    may be used to the maximum practicable extent to gain access to the 
    electric service ground as shown in Figure 9. Note that the water pipe 
    in Figure 9 is electrically continuous between electric and 
    telecommunications bonds to the cold water pipe and it is used only as 
    a portion of a bonding conductor and, therefore, does not have to be 
    ``acceptable'' as a ground electrode but may be floating (isolated from 
    ground by a plastic pipe section). ANSI/NFPA 70-1996, NEC, 
    requires that metal piping be used as a bonding conductor in this 
    manner only when the connectors to the pipe are within 1.5 m (5 ft) of 
    where the pipe enters the premises. This is not the preferred 
    installation. The RUS preferred installation has the telecommunications 
    primary station protector grounded directly to an accessible location 
    near the power grounding system. See paragraph (l) of this section. 
    Figure 9 is as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70480]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.009
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70481]]
    
        (n) Where the telecommunications premises system at a customer's 
    access location is grounded to a separate electrode (of any type) this 
    telecommunications grounding electrode must be bonded to the electric 
    grounding system with a No. 6 AWG or larger copper insulated grounding 
    conductor. Bonding of separate electrodes is a requirement of the ANSI/
    NFPA 70-1996, NEC.
        (o) The NID, BET, or fused primary station protector pair size 
    shall be adequate for the number of lines anticipated within five 
    years.
        (p) When lightning damage is considered probable or customer access 
    locations are remote from the borrower's headquarters, use of maximum 
    duty gas tube primary station protectors incorporated in NIDs, BETs, or 
    fused primary station protectors shall be considered. (See RUS TE&CM 
    823, Electrical Protection by Use of Gas Tube Arresters). Copies of RUS 
    TE&CM 823 are available upon request from RUS/USDA, 1400 Independence 
    Avenue, SW., STOP 1522, Washington, DC 20250-1522, FAX (202) 690-2268.
        (q) NIDs or BETs incorporating fuseless station protectors shall 
    always be used in preference to fused station protectors or BETs 
    incorporating fused protectors, when in the judgment of the RUS 
    borrower or the engineer delegated by the RUS borrower, the 
    requirements of the ANSI/NFPA 70-1996, NEC, for fuseless 
    station protectors can be met.
        (r) A fuse link consisting of a copper conductor two gauges (AWG) 
    finer (numerically higher) conductivity than the aerial service wire 
    shall be provided between the cable and aerial service wire where NIDs 
    or BETs incorporating fuseless station protectors are used. Thus for a 
    22 AWG drop, a fuse link of No. 24 AWG or finer copper wire shall be 
    provided. If the cable circuit is No. 24 gauge or finer, the cable 
    conductors serve as the fuse link for the 22 AWG aerial service wire 
    and no separate fuse link is necessary. (Note: The fuse link or the 
    facilities serving as the fuse link must be located between the 
    telecommunications facilities that are exposed to possible power cross 
    and the customer drop where there is no exposure to possible power 
    cross.)
        (s) RUS's buried plant practices require buried main line plant to 
    be protected against power contacts to aerial plant extensions and 
    aerial inserts by No. 24 AWG fuse links at every buried-aerial 
    junction.
        (t) In aerial cable plant, fuse links are usually provided by 24 
    AWG leads on filled terminal blocks regardless of the gauge of the 
    cable conductors. This practice is acceptable if the ampacity of the 
    aerial service wire is sufficiently higher than the fuse link's 
    ampacity.
        (u) The grounding and bonding of each NID, BET, or fused primary 
    station protector shall be selected by consulting paragraphs (i) 
    through (n) of this section. The ``first choice'' assembly unit shall 
    be selected whenever the prevailing conditions make its use 
    practicable. The NID, BET, or fused primary station protector assembly 
    unit selected shall be installed in accordance with the appropriate 
    construction drawing specified in RUS Bulletin 345-154 (RUS Form 515g), 
    Specifications and Drawings for Service Entrance and Station Protector 
    Installation. Copies of RUS Bulletin 345-154 are available upon request 
    from RUS/USDA, 1400 Independence Avenue, SW., STOP 1522, Washington, DC 
    20250-1522, FAX (202) 690-2268.
        (v) The minimum size grounding conductor that can be used with a 
    single NID; a group of NIDS; a multipair NID; fused protector; or BET 
    shall be in accordance Table 5, as follows:
    
                              Table 5.--Grounding Conductor Size Versus Number of Circuits
    ----------------------------------------------------------------------------------------------------------------
                                                                         Number of circuits
         Minimum Grounding Conductor Size     ----------------------------------------------------------------------
                                                    Fuseless (carbon or gas tube)                   Fused
    ----------------------------------------------------------------------------------------------------------------
    #12 AWG, copper, insulated...............  1 to 2.................................  1 to 3.
    #10 AWG, copper, insulated...............  3 to 5.................................  4 to 7.
    #6 AWG, copper, insulated................  6 or more..............................  8 or more.
    ----------------------------------------------------------------------------------------------------------------
    
        (w) Grounding conductor runs between the NID, BET, or fused station 
    protector and the ground electrode shall conform to the following:
        (1) The shortest, most direct route practicable shall be used;
        (2) Sharp bends in the grounding conductor shall be avoided during 
    installation;
        (3) No splices shall be made in the grounding conductor;
        (4) Grounding conductors shall not be fished through walls, under 
    floors, or placed in bridle rings or any metal conduit unless the 
    grounding conductor is bonded to the conductor at both ends of the 
    metallic conduit;
        (5) Grounding conductor runs from an outside mounted NID, BET, or 
    fused station protector to an inside ground electrode shall use the 
    same entrance as the station wire; and
        (6) Grounding conductor runs from an outside mounted NID, BET, or 
    fused station protector to an outside ground electrode at the building 
    shall be attached to the exterior surface of the building or buried. If 
    buried, the grounding conductor shall be either plowed or trenched to a 
    minimum depth of 12 in. (300 mm). When trenched, the trenches shall be 
    as close to the side of the building as practicable, backfilled, and 
    tamped to restore the earth to its original condition.
        (x) Telecommunications grounding connectors shall be RUS accepted 
    or RUS technically accepted. Grounding and bonding conductors shall be 
    made of copper. Where the grounding and bonding conductors must be 
    connected to aluminum electric service grounding conductors, bimetal 
    grounding connectors shall be used.
        (y) Grounding conductor attachments shall conform to the following:
        (1) Galvanized nails or clamps, or nickel-copper alloy staples 
    shall be used for grounding conductor attachments in accordance with 
    Table 6 in paragraph (y)(3) of this section.
        (2) Grounding conductors, station or buried service wires in 
    parallel runs may share the same fastening device when the device is 
    specifically designed for two wires. See Table 6 in paragraph (y)(3) of 
    this section for station wire and grounding conductor fasteners; and
        (3) Grounding conductor fasteners shall be placed 12 to 18 in. (300 
    to 450 mm) apart on straight runs and 2 to 4 in. (50.8 to 100 mm) apart 
    at corners and at bends. Table 6 is as follows:
    BILLING CODE 3410-15-P
    
    
    [[Page 70482]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.010
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70483]]
    
        Notes: \1\ Screw dimensions are minimum. Where appropriate, 
    either or both dimensions shall be increased. All wood screws for 
    exterior use shall be stainless steel. All other exterior metal 
    devices shall be stainless steel, zinc coated steel, silicon bronze, 
    or corrosion resistant aluminum alloy.
        \2\ Toggle bolt dimensions are minimum. Where appropriate, 
    either or both dimensions shall be increased.
        \3\ Wall screw anchors may be used in wall board, plaster or 
    tile walls. Screws and nails in masonry shall be secured by means of 
    expansions type anchors. Equivalent manual or machine-driven devices 
    may be used. Where toggle bolts are specified, equivalent devices 
    may be used.
        \4\ Lead holes shall be drilled for screws, nails, and bridle 
    rings in shingles and drop siding.
        \5\ Sheet metal screws shall be used except where toggle bolts 
    are required. Where wood sheathing under sheet metal siding is 
    encountered, the sheet metal may be drilled or punched and a wood 
    screw used.
        \6\ Machine-driven staples of nickel-copper composition may be 
    used for exterior wiring.
        \7\ Galvanized clamps and wiring nails may be used for exterior 
    and interior wiring. Enameled clamps shall be used for interior 
    wiring only. Where toggle bolts or equivalent devices require holes 
    in the structure larger than the clamp being fastened, a suitable 
    washer of sufficient size to cover the hole must be used under the 
    clamp.
        \8\ Double clamp may be used where two #22 AWG station wires, 
    two #12 AWG grounding conductors, or one #22 AWG station wire and 
    one #12 grounding conductor parallels one another.
        \9\ For converting English units to Metric units use 1 in. = 
    25.4 mm.
    
        (z) Grounding conductors shall be separated from non-telephone 
    company wires in accordance with Section 800-12(b) of the ANSI/NFPA 70-
    1996, NEC.
        (aa) Grounding conductors run through metal conduits shall be 
    bonded to the conduit at each end. RUS accepted and RUS technically 
    accepted pipe type ground clamps and grounding connectors shall be used 
    for bonding.
        (bb) Where NID, BET, or fused station protector assembly units 
    require grounding conductor connections to pipe systems, the following 
    apply:
        (1) The connection shall be made to a cold water pipe of an 
    operating water system;
        (2) The connection point shall be preferably inside the building;
        (3) Allow a minimum of 6 in. (152 mm) between the last fastener and 
    the point where the grounding conductor first touches the water pipe;
        (4) Leave 2 in. (50.8 mm) of slack in the grounding conductor to 
    avoid breaking the conductor at the terminating point. Tape the 
    grounding conductor to the pipe where possible to avoid movement. In no 
    case, shall the grounding conductor be coiled or wrapped around the 
    pipe;
        (5) The pipe shall be cleaned with fine sand paper to make a good 
    electrical connection. Care should be taken to avoid damaging the pipe 
    while cleaning it;
        (6) Attach the pipe grounding conductor connector to the cleaned 
    area of pipe and tighten. Care shall be exercised to avoid deforming, 
    crushing, or otherwise damaging the pipe. A simple continuity check 
    with an ohmmeter between the connector and the pipe will indicate 
    whether or not a good electrical contact has been made. Set the 
    ohmmeter to ``R x 1'' scale to ensure that a low resistance contact is 
    made;
        (7) A warning tag shall be attached to the ground clamp with the 
    following or equivalent statement: ``Call the telecommunications 
    company if this connector or grounding conductor is loose or must be 
    removed''; and
        (8) When the water pipe is used, the ANSI/NFPA 70-1996, 
    NEC, requires that metal piping be used as a bonding 
    conductor in this manner only when the connections to the pipe are 
    within 5 ft (1.5 m) of where the pipe enters the premises.
        (cc) Bonding conductors shall consist of either copper or tinned 
    copper insulated wires of appropriate sizes.
        (1) Bonding conductors shall be run and attached in the same manner 
    as grounding conductors.
        (2) Attaching and terminating devices for bonding conductors shall 
    be adequate for the size of wire involved. The No. 6 AWG copper 
    insulated conductor or larger shall not be terminated by bending it 
    around a threaded stud.
        (dd) Where NID, BET, or fused station protector assembly units 
    require a driven ground rod the following shall apply to the ground rod 
    installation:
        (1) Locate the ground rod at least 1 ft (300 mm) from buildings, 
    poles, trees and other obstruction;
        (2) Ground rods shall not be installed within 6 ft (2 m) of 
    electric service ground rods (Note: This minimum separation is provided 
    to avoid mutual impedance effects of multiple grounding electrodes that 
    will deleteriously degrade the effective impedance-to-earth if 
    grounding electrodes are installed any closer than 6 ft (2 m) to one 
    another. This requirement is included for special cases where the 
    telecommunications company is not allowed, for some reason, to observe 
    the RUS preferred grounding method of attaching the primary protector 
    grounding conductor directly to an accessible point on the building 
    electric service grounding system. RUS believes that if the primary 
    protector location can be sited within 6 ft (2 m) of the electric 
    service ground rod then the electric service ground rod could be used 
    as the preferred telecommunications grounding electrode and a separate 
    telecommunications ground rod is unnecessary);
        (3) A hole, 15 in. (350 mm) deep and 6 in. (150 mm) in diameter, 
    shall be dug at the location where the ground rod is to be driven;
        (4) Where ``slip-on'' type ground rod clamps are used instead of 
    ``clamp-around'' type clamps, the ground rod clamps shall be placed 
    onto the rod prior to driving the rod into the ground (Note there 
    should be one clamp for the NID, BET, or fused station protector 
    grounding conductor and one clamp for the conductor required to bond 
    the telecommunications ground rod to the electric grounding system). 
    However, the clamp shall not be tightened until the rod is completely 
    driven. The end of the rod shall be placed in the bottom of the hole 
    and the rod shall be aligned vertically adjacent to one wall of the 
    hole prior to driving. The rod shall be driven until its tip is 12 in. 
    (300 mm) below final grade. The grounding conductor shall then be 
    attached, the clamp shall be tightened, and hole backfilled. Clamps 
    employed in this manner shall be suitable for direct burial and shall 
    be RUS accepted or RUS technically accepted; and
        (5) Where rods are manually driven, a large number of blows from a 
    light hammer (4 lbs [1.8 kg]) shall be used instead of heavy 
    sledgehammer type blows. This should keep the rod from bending.
        (ee) Terminations on fuseless primary station protectors 
    incorporated in NIDs and on fused primary station protectors shall be 
    as shown in Figures 10, 11, 12, 13, 14, and 15 of paragraph (ee)(1) of 
    this section. The inner jackets of buried service wires and outer 
    jackets of cables used as service drops shall be extended into the NID 
    or the fused primary station protector. A 10 in. (250 mm) length of 
    each spare wire shall be left in NIDs or fused primary station 
    protectors. The spare wires shall be coiled up neatly and stored in the 
    NID
    
    [[Page 70484]]
    
    or fused primary station protector housing.
        (1) The shields of buried service wires may be connected to the 
    ground binding post using RUS accepted or RUS technically accepted 
    buried service shield bond connectors as shown in Figure 10 for NIDs 
    and Figure 11 for fused primary station protectors. RUS accepted or RUS 
    technically accepted buried service wire harness wires designed for 
    customer access location installations may also be used for terminating 
    buried service wire shields to the ground binding post of the NID as 
    shown in Figure 12 and Figure 13 for fused primary station protectors. 
    Figures 10 through 13 are as follows:
    
    BILLING CODE 3410-15-P
          
    
    [[Page 70485]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.011
    
    
    
    [[Page 70486]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.012
    
    
    
    [[Page 70487]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.013
    
    
    
    [[Page 70488]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.014
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70489]]
    
        (2) On buried service drops and aerial service drops of more than 6 
    pairs using RUS accepted or RUS technically accepted cables, the 
    shields shall be terminated with a RUS accepted or RUS technically 
    accepted cable shield bonding connector and extended to the ground 
    binding post of the NID, BET, or fused primary station protector with a 
    RUS accepted or RUS technically accepted bonding harness wire. The 
    installation of the shield bond connector and bonding harness wire 
    shall be in accordance with the manufacturer's instructions.
        (3) The shield and other conductors at the fuseless primary station 
    protector incorporated in the NID shall be terminated as shown on 
    Figure 14 in paragraph (ee)(4) of this section. The pronged or cupped 
    washer shall be placed above the shield. The grounding conductor shall 
    be placed around the post on top of the pronged or cupped washer. A 
    flat washer shall be placed above the grounding conductor.
        (4) The station wire signaling ground conductor, if required, shall 
    be placed above the first flat washer and beneath the second flat 
    washer as indicated in Figure 14 as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70490]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.015
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70491]]
    
        (5) The shield and other conductors at the fused primary station 
    protector shall be terminated as shown on Figure 15 in paragraph 
    (ee)(6) of this section. The pronged or cupped washer shall be placed 
    above the shield. The grounding conductor shall be placed around the 
    post on top of the pronged or cupped washer. A flat washer shall be 
    placed above the grounding conductor.
        (6) The station wire signaling ground conductor, if required, shall 
    be placed above the first flat washer and beneath the second flat 
    washer as indicated in Figure 15 as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70492]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.016
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70493]]
    
        (7) Indoor NIDs or BETs that are equipped with ``Quick Connect'' 
    type terminals shall not have more than one wire connected per clip. 
    No. 19 AWG copper and No. 18 AWG copper covered-steel reinforced aerial 
    service wire conductors shall not be connected to quick connect 
    terminals. Nonmetallic reinforced aerial service wire using No. 22 AWG 
    copper conductors may be connected to the quick connect terminals.
        (8) Tip and ring connections and other connections in multipair 
    NIDs or BETs shall be as indicated in Figure 16 as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70494]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.017
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70495]]
    
        (ff) System polarity and conductor identification shall be 
    maintained in NIDs, BETs, or fused primary station protectors in 
    accordance with construction drawings 815 and 815-1 contained in 
    Sec. 1755.510.
    
    
    Sec. 1755.509  Mobile homes.
    
        (a) Customer access location installations at mobile homes shall be 
    treated the same whether the homes are mounted on permanent foundations 
    or temporary foundations and shall be installed as specified in 
    Secs. 1755.500 through 1755.510. For the purpose of this section, 
    mobile homes include motor homes, truck campers, travel trailers, and 
    all forms of recreational vehicles. Customer access location 
    installations at mobile homes can be considerably different than 
    customer access location installations at regular homes and borrowers 
    shall be certain that the two types of installations are properly 
    applied.
        (b) The method of customer access location installation prescribed 
    by the ANSI/NFPA 70-1996, NEC for a mobile home depends on 
    how the electric power is installed at the mobile home and it can 
    involve considerable judgment on the part of the telecommunications 
    installer. The National Electrical Code and NEC 
    are registered trademarks of the National Fire Protection Association, 
    Inc., Quincy, MA 02269. The ANSI/NFPA 70-1996, NEC, is 
    incorporated by reference in accordance with 5 U.S.C. 552(a) and 1 CFR 
    part 51. Copies are available from NFPA, 1 Batterymarch Park, P. O. Box 
    9101, Quincy, Massachusetts 02269-9101, telephone number 1 (800) 344-
    3555. Copies of ANSI/NFPA 70-1996, NEC, are available for 
    inspection during normal business hours at RUS, room 2845, U.S. 
    Department of Agriculture, 1400 Independence Avenue, SW., STOP 1598, 
    Washington, DC 20250-1598 or at the Office of the Federal Register, 800 
    North Capitol Street, NW., suite 700, Washington, DC. Essentially, the 
    ANSI/NFPA 70-1996, NEC, requires primary station protectors 
    to be located where specific acceptable grounding electrodes exist. The 
    ANSI/NFPA 70-1996, NEC, allows station protector 
    installations to be at the location of the power meter or the electric 
    disconnecting means apparatus serving the mobile home providing these 
    electric facilities are installed in the manner specifically defined by 
    the ANSI/NFPA 70-1996, NEC. The ANSI/NFPA 70-1996, 
    NEC, requires the station protectors to be installed at the 
    nearest of a number of other meticulously defined ANSI/NFPA 70-1996, 
    NEC, acceptable electrodes where the protector cannot be 
    installed at the power meter or the electric disconnecting means 
    apparatus serving the mobile home. The provisions can be confusing.
        (c) To avoid the need for significant telecommunications installer 
    judgment, NIDs shall be installed at mobile homes in either of the 
    following situations:
        (1) Where the mobile home electric service equipment (power meter, 
    etc.) or the electric service disconnecting means associated with the 
    mobile home is located within 35 ft (10.7 m) of the exterior wall of 
    the mobile homes it serves, the NID shall be installed in accordance 
    with Figure 17 as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70496]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.018
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70497]]
    
        (2) Where the mobile home electric service equipment (power meter, 
    etc.) or the electric service disconnecting means associated with the 
    mobile home is located more than 35 ft (10.7 m) from the exterior wall 
    of the mobile homes it serves, the NID shall be installed in accordance 
    with Figure 18 as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70498]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.019
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70499]]
    
        (d) The service wire and station wire shall be terminated in the 
    NID in accordance with Figure 19 in paragraph (e) of this section.
        (e) Installation of the station wire and grounding conductor at the 
    mobile home shall be in accordance with Figure 20. Figures 19 and 20 
    are as follows:
    
    BILLING CODE 3410-15-P
         
    
    [[Page 70500]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.020
    
    
    
    [[Page 70501]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.021
    
    
    
    BILLING CODE 3410-15-C
    
    [[Page 70502]]
    
    Sec. 1755.510  Construction and assembly unit drawings.
    
        (a) The construction and assembly unit drawings in this section 
    shall be used by borrowers to assist the installer in making the 
    customer access location installations.
        (b) The asterisks appearing on the construction drawings indicate 
    that the items are no longer listed in the RUS Informational 
    Publication (IP) 344-2, ``List of Materials Acceptable for Use on 
    Telecommunications Systems of RUS Borrowers.'' RUS IP 344-2 can be 
    obtained from the Superintendent of Documents, P. O. Box 371954, 
    Pittsburgh, PA 15250-7954, telephone number (202) 512-1800.
        (c) Drawings BM83, 312-1, 501-1, 501-2, 503-2, 504, 505, 506, 507, 
    508-1, 510, 510-1, 510-2, 513, 702, 815, 815-1, 912, 958, and 962 are 
    as follows:
    
    BILLING CODE 3410-15-P
    
    [[Page 70503]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.022
    
    
    
    [[Page 70504]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.023
    
    
    
    [[Page 70505]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.024
    
    
    
    [[Page 70506]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.025
    
    
    
    [[Page 70507]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.026
    
    
    
    [[Page 70508]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.027
    
    
    
    [[Page 70509]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.028
    
    
    
    [[Page 70510]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.029
    
    
    
    [[Page 70511]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.030
    
    
    
    [[Page 70512]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.031
    
    
    
    [[Page 70513]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.032
    
    
    
    [[Page 70514]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.033
    
    
    
    [[Page 70515]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.034
    
    
    
    [[Page 70516]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.035
    
    
    
    [[Page 70517]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.036
    
    
    
    [[Page 70518]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.037
    
    
    
    [[Page 70519]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.038
    
    
    
    [[Page 70520]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.039
    
    
    
    [[Page 70521]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.040
    
    
    
    [[Page 70522]]
    
    [GRAPHIC] [TIFF OMITTED] TP21DE98.041
    
    
    
    [[Page 70523]]
    
        Dated: November 20, 1998.
    Jill Long Thompson,
    Under Secretary Rural Development.
    
    [FR Doc. 98-32207 Filed 12-18-98; 8:45 am]
    BILLING CODE 3410-15-C
    
    
    

Document Information

Published:
12/21/1998
Department:
Rural Utilities Service
Entry Type:
Proposed Rule
Action:
Proposed rule.
Document Number:
98-32207
Dates:
Comments concerning this proposed rule must be received by RUS or be postmarked no later February 19, 1999.
Pages:
70456-70523 (68 pages)
PDF File:
98-32207.pdf
CFR: (15)
7 CFR 1755.505(f)(8)
7 CFR 1755.510
7 CFR 1755.97
7 CFR 1755.98
7 CFR 1755.500
More ...