96-3056. Energy Conservation Program for Consumer Products: Granting of the Application for Interim Waiver and Publishing of the Petition for Waiver of Superior Fireplace Company From the DOE Vented Home Heating Equipment Test Procedure  

  • [Federal Register Volume 61, Number 31 (Wednesday, February 14, 1996)]
    [Notices]
    [Pages 5755-5758]
    From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
    [FR Doc No: 96-3056]
    
    
    
    =======================================================================
    -----------------------------------------------------------------------
    
    DEPARTMENT OF ENERGY
    
    Office of Energy Efficiency and Renewable Energy
    [Case No. DH-005]
    
    
    Energy Conservation Program for Consumer Products: Granting of 
    the Application for Interim Waiver and Publishing of the Petition for 
    Waiver of Superior Fireplace Company From the DOE Vented Home Heating 
    Equipment Test Procedure
    
    AGENCY: Office of Energy Efficiency and Renewable Energy, Department of 
    Energy.
    
    ACTION: Notice.
    
    -----------------------------------------------------------------------
    
    SUMMARY: Today's notice grants an Interim Waiver to Superior Fireplace 
    Company (Superior) from the existing Department of Energy (DOE or 
    Department) test procedure regarding pilot light energy consumption and 
    weighted average steady-state efficiency for its manually controlled 
    vented heaters, models GI-3821, DSH-36T, DVH-33R, DVH-33T, DVA-33R, and 
    DVA-33T.
        Today's notice also publishes a ``Petition for Waiver'' from 
    Superior. Superior's Petition for Waiver requests DOE to grant relief 
    from the DOE vented home heating equipment test procedure relating to 
    the use of pilot light energy consumption in calculating the Annual 
    Fuel Utilization Efficiency (AFUE) and the calculation of weighted 
    average steady state efficiency of its models GI-3821, DSH-36T, DVH-
    33R, DVH-33T, DVA-33R, and DVA-33T vented heaters. Superior seeks to 
    delete the required pilot light measurement (Qp) in the 
    calculation of AFUE when the pilot is off, and to test at a minimum 
    fuel input rate of two-thirds instead of the specified 5 
    percent of 50 percent of the maximum fuel input rate in the calculation 
    of AFUE. The Department is soliciting comments, data, and information 
    respecting the Petition for Waiver.
    
    DATES: DOE will accept comments, data, and information not later than 
    March 15, 1996.
    
    ADDRESSES: Written comments and statements shall be sent to: Department 
    of Energy, Office of Energy Efficiency and Renewable Energy, Case No. 
    DH-005, Mail Stop EE-43, Room 1J-018, Forrestal Building, 1000 
    Independence Avenue SW., Washington, D.C. 20585-0121, (202) 586-7140.
    
    FOR FURTHER INFORMATION CONTACT: William W. Hui, U.S. Department of 
    Energy, Office of Energy Efficiency and Renewable Energy, Mail Station 
    EE-431, 
    
    [[Page 5756]]
    Forrestal Building, 1000 Independence Avenue SW., Washington, D.C. 
    20585-0121, (202) 586-9145
    
    Eugene Margolis, Esq., U.S. Department of Energy, Office of General 
    Counsel, Mail Station GC-72, Forrestal Building, 1000 Independence 
    Avenue SW., Washington, D.C. 20585-0103, (202) 586-9507.
    
    SUPPLEMENTARY INFORMATION: The Energy Conservation Program for Consumer 
    Products (other than automobiles) was established pursuant to the 
    Energy Policy and Conservation Act, as amended (EPCA), which requires 
    DOE to prescribe standardized test procedures to measure the energy 
    consumption of certain consumer products, including vented home heating 
    equipment. The intent of the test procedures is to provide a comparable 
    measure of energy consumption that will assist consumers in making 
    informed purchasing decisions. These test procedures appear at Title 10 
    CFR Part 430, Subpart B.
        The Department amended the test procedure rules to provide for a 
    waiver process by adding Sec. 430.27 to Title 10 CFR Part 430, 45 FR 
    64108, September 26, 1980. Subsequently, DOE amended the waiver process 
    to allow the Assistant Secretary for Energy Efficiency and Renewable 
    Energy (Assistant Secretary) to grant an Interim Waiver from test 
    procedure requirements to manufacturers that have petitioned DOE for a 
    waiver of such prescribed test procedures. Title 10 CFR Part 430, 
    Sec. 430.27(a)(2).
        The waiver process allows the Assistant Secretary to waive 
    temporarily test procedures for a particular basic model when a 
    petitioner shows that the basic model contains one or more design 
    characteristics which prevent testing according to the prescribed test 
    procedures, or when the prescribed test procedures may evaluate the 
    basic model in a manner so unrepresentative of its true energy 
    consumption as to provide materially inaccurate comparative data. 
    Waivers generally remain in effect until final test procedure 
    amendments become effective, resolving the problem that is the subject 
    of the waiver.
        An Interim Waiver will be granted if it is determined that the 
    applicant will experience economic hardship if the Application for 
    Interim Waiver is denied, if it appears likely that the Petition for 
    Waiver will be granted, and/or the Assistant Secretary determines that 
    it would be desirable for public policy reasons to grant immediate 
    relief pending a determination on the Petition for Waiver. Title 10 CFR 
    Part 430, Sec. 430.27(g). An Interim Waiver remains in effect for a 
    period of 180 days, or until DOE issues a determination on the Petition 
    for Waiver, whichever is sooner, and may be extended for an additional 
    180 days, if necessary.
        On August 30, 1995, Superior filed an Application for Interim 
    Waiver and a Petition for Waiver regarding (a) pilot light energy 
    consumption and (b) weighted average steady state efficiency. On 
    November 30, 1995, Superior submitted a letter to DOE requesting a 
    modification to the minimum fuel input rate of the vented heaters 
    submitted for consideration in the August 30, 1995 Waiver requests. On 
    January 12, 1996, Superior Fireplace Company submitted a letter 
    providing a list of companies that make similar products, confidential 
    product performance data, and amending the list of models submitted for 
    consideration in the August 30, 1995, Waiver requests.
        Superior seeks an Interim Waiver from the DOE test provisions in 
    section 3.5 of Title 10 CFR Part 430, Subpart B, Appendix O, that 
    require measurement of energy input rate of the pilot light (Qp), 
    and the use of this data in section 4.2.6 for the calculation of AFUE, 
    where:
    
    AFUE=(4400ssuQin-max) /
    (4400ssQin-max + 2.5(4600)u Qp)
    
        Instead, Superior requests that it be allowed to delete Qp and 
    accordingly, the (2.5(4600)u Qp) term in the 
    calculation of AFUE. Superior states that instructions to turn off the 
    transient pilot by the user when the heater is not in use are in the 
    User Instruction Manual and on a label adjacent to the gas control 
    valve. Therefore, the additional energy savings that result when the 
    pilot is turned off (Qp = 0) should be credited. Since the current 
    DOE test procedure does not address pilot light energy savings, 
    Superior asks that the Interim Waiver be granted.
        Superior also seeks an Interim Waiver from the DOE test provisions 
    in section 3.1.1 of Title 10 CFR Part 430, Subpart B, Appendix O, which 
    require steady state efficiency of manually controlled vented heaters 
    with various input rates to be determined at a fuel input rate that is 
    within 5 percent of 50 percent of the maximum fuel input 
    rate, and the use of this data in section 4.2.4 to determine the 
    weighted average steady state efficiency needed in the calculation of 
    AFUE. Instead, Superior requests that it be allowed to determine steady 
    state efficiency, weighted average steady state efficiency, and AFUE at 
    a minimum fuel input rate of two-thirds of the maximum fuel input rate 
    for its manually controlled vented heaters which do not adjust to an 
    input rate as low as 50 percent. Since the current DOE test procedure 
    does not address steady state testing for manually controlled vented 
    heaters with various input rates at fuel input rates other than within 
     5 percent of 50 percent of the maximum fuel input rate, 
    Superior asks that the waiver be granted.
        Previous Petitions for Waiver to exclude the pilot light energy 
    input term in the calculation of AFUE for home heating equipment with a 
    manual transient pilot control and allowance to determine weighted 
    average steady state efficiency used in the calculation of AFUE at a 
    minimum fuel input rate of 65.3 percent of the maximum fuel input rate 
    instead of the specified  5 percent of 50 percent of the 
    maximum fuel input rate have been granted by DOE to Appalachian Stove 
    and Fabricators, Inc., 56 FR 51711, October 15, 1991, and Valor 
    Incorporated, 56 FR 51714, October 15, 1991.
        The Department published a Notice of Proposed Rulemaking on August 
    23, 1993, to amend the vented home heating equipment test procedure, 
    which would allow the above issues. 58 FR 44583.
        Thus, it appears likely that Superior's Petition for Waiver for 
    pilot light and weighted average steady state efficiency for home 
    heating equipment will be granted. In those instances where the likely 
    success of the Petition for Waiver has been demonstrated based upon DOE 
    having granted a waiver for a similar product design, it is in the 
    public interest to have similar products tested and rated for energy 
    consumption on a comparable basis.
        Therefore, based on the above, DOE is granting Superior an Interim 
    Waiver for its models GI-3821, DSH-36T, DVH-33R, DVH-33T, DVA-33R, and 
    DVA-33T vented heaters. Superior shall be permitted to test its models 
    GI-3821, DSH-36T, DVH-33R, DVH-33T, DVA-33R, and DVA-33T vented heaters 
    on the basis of the test procedures specified in Title 10 CFR Part 430, 
    Subpart B, Appendix O, with the modifications set forth below:
        (i) Delete paragraph 3.5 of Appendix O.
        (ii) Delete paragraph 4.2.4 of Appendix O and replace with the 
    following paragraph:
        4.2.4  Weighted Average Steady-State Efficiency. (a) For manually 
    controlled heaters with various input rates, the weighted average 
    steady-state efficiency (SS-WT) is:
        (1) At  5 percent of 50 percent of the maximum fuel 
    input rate as measured in either section 3.1.1 to this appendix for 
    manually controlled gas vented heaters or section 3.1.2 to this 
    appendix for 
    
    [[Page 5757]]
    manually controlled oil vented heaters, or,
        (2) At the minimum fuel input rate as measured in either section 
    3.1.1 to this appendix for manually controlled gas vented heaters or 
    section 3.1.2 to this appendix for manually controlled oil vented 
    heaters if the design of the heater is such that 5 percent 
    of 50 percent of the maximum fuel input rate can not be set, provided 
    the tested input rate is no greater than two-thirds of maximum input 
    rate of the heater.
        (b) For manually controlled heater with one single firing rate, the 
    weighted average steady-state efficiency is the steady-state efficiency 
    measured at the single firing rate.
        (iii) Delete paragraph 4.2.6 of Appendix O and replace with the 
    following paragraph:
        4.2.6  Annual Fuel Utilization Efficiency. For manually controlled 
    vented heaters, calculate the Annual Fuel Utilization Efficiency (AFUE) 
    as a percent and defined as:
    
    AFUE = u
    
    where:
    u=as defined in section 4.2.5 of this appendix.
    
        (iv) With the exception of the modification set forth above, 
    Superior shall comply in all respects with the procedures specified in 
    Appendix O of Title 10 CFR Part 430, Subpart B.
        This Interim Waiver is based upon the presumed validity of 
    statements and all allegations submitted by the company. This Interim 
    Waiver may be removed or modified at any time upon a determination that 
    the factual basis underlying the Application is incorrect.
        The Interim Waiver shall remain in effect for a period of 180 days 
    or until DOE acts on the Petition for Waiver, whichever is sooner, and 
    may be extended for an additional 180-day period, if necessary.
        Superior's Petition for Waiver requests DOE to grant relief from 
    the DOE vented home heating equipment relating to the pilot light and 
    weighted average steady state efficiency. Superior seeks (a) to exclude 
    the pilot light energy consumption in the calculation of AFUE, and (b) 
    to determine the weighted average steady state efficiency used in the 
    calculation of AFUE at a minimum fuel input rate of two-thirds of the 
    maximum fuel input rate instead of the specified 5 percent 
    of 50 percent of the maximum fuel input rate. Pursuant to paragraph (b) 
    of Title 10 CFR Part 430.27, the Department is hereby publishing the 
    ``Petition for Waiver.''
        The Petition contains confidential company information; thus, the 
    confidential product performance data provided in Superior's January 
    12, 1996 submission is not being published. The Department solicits 
    comments, data, and information respecting the Petition.
    
        Issued in Washington, DC.
        February 1, 1996.
    Christine A. Ervin,
    Assistant Secretary, Energy Efficiency and Renewable Energy.
    August 30, 1995
    The Honorable Christine Ervin,
    Assistant Secretary for Energy Efficiency & Renewable Energy, United 
    States Department of Energy, Forrestal Building, 1000 Independence 
    Avenue SW., Washington, D.C. 20585
    
    RE: Petition for Waiver and Application for Interim Waiver
    
        Dear Secretary Ervin: Superior Fireplace Company is requesting 
    you to accept two waivers as listed below, concerning Title 10 Code 
    of Federal Regulations 430.27, as amended 14 November 1986.
        These waivers are requested for model GI-3821, DSH-36T.
        1. This waiver request refers to section 3.1.1.--Gas fueled 
    vented home heating equipment and section 4.2.4--Weighted-average 
    steady-state efficiency which states that for manually controlled 
    heaters with various input rates the weighted-average steady-state 
    efficiency is measured at a fuel input rate of 5 percent 
    of 50 percent of the maximum fuel input rate. In fact the above 
    appliances have a gas control that comes with a variable pressure 
    regulator control knob which can be adjusted from the maximum input 
    rate to the minimum input rate. Specifically, Natural gas control 
    knob has adjustment of manifold pressure from 3.5'' W.C. to 2.5'' 
    W.C. and for Propane from 10.0'' W.C. to 6.4'' W.C. These pressure 
    ranges allow the users to vary the fuel input rate as shown below in 
    the table. It is impossible to achieve the fuel input rate of 50% 
    according to the manufacturer's installation instructions. Because 
    the above models cannot be operated at 50% of the maximum fuel input 
    and usually operated at maximum fuel input rate we request that this 
    requirement be modified to 80% of the difference between the maximum 
    fuel input rate and the minimum fuel input rate.
    
                                                                                                                    
    ----------------------------------------------------------------------------------------------------------------
                                                                      Percentage                                    
                                             Maximum      Minimum      maximum             Manifold pressure        
                                            rate BTUH    rate BTUH       rate                                       
    ----------------------------------------------------------------------------------------------------------------
    GI-3821-N............................        38000        30000           79  3.5-2.2 W.C.                      
    GI-3821-P............................        34000        26000           76  10-6.4 W.C.                       
    DSH-36T-N............................        27000        21000           77  3.5-2.2 W.C.                      
    DSH-36T-P............................        25000        20000           80  10-6.4 W.C.                       
    ----------------------------------------------------------------------------------------------------------------
    
        2. Second waiver refers to section 3.5--Pilot Light Measurement 
    and section 4.26--Annual Fuel Utilization Efficiency. This section 
    requires the calculation of the pilot light energy to be figured in 
    for calculation of AFUE if the pilot is in operation all the time. 
    The gas control knob on these appliances have three settings--
    ``OFF,'' ``ON'' and ``PILOT''. The pilot can be lighted with the 
    piezo igniter when the gas control knob is turned and depressed at 
    the ``PILOT'' position. Once the pilot is lighted, it will heat the 
    thermopile which generates enough voltage to the gas control valve 
    to have the pilot remain lit. The gas control knob can then be 
    turned to the ``ON'' position for the main burner to turn on. 
    Instructions and labels next to the control will require users to 
    turn the gas control knob to the ``OFF'' position during the off 
    cycle will be provided. Therefore, additional energy will be 
    conserved. Since the current test procedure does not allow any 
    credit given in the calculations for AFUE for saving energy from the 
    pilot during the off cycle, we request that the requirement to 
    include energy input to the pilot light in the AFUE calculation be 
    waived for these appliances. Copies of confidential test data 
    confirming the energy savings will be forwarded to you upon request.
        Superior Fireplace Company is confident that both waivers will 
    be granted since similar waivers have been granted in the past to 
    Appalachian Stove and Fabricators, Inc. and Valor Incorporated.
        A copy of this petition for waiver and Application for Interim 
    Waiver is being sent to the manufacturers that produce similar 
    products in the U.S.A.
    
            Sincerely,
    Hardial Gore,
    Sr. Project Engineer.
    Nov. 30, 1995
    The Honorable Christine Ervin,
    Assistant Secretary for Energy Efficiency & Renewable Energy, United 
    States Department of Energy, Forrestal Building, 1000 Independence 
    Avenue SW., Washington, D.C. 20585
    
    RE: Amendment to Petition for Waiver and Application for Interim 
    Waiver
    
    
    [[Page 5758]]
    
        Dear Secretary Ervin: In order to expedite the approval to 
    petition for waiver and application for interim waiver requested in 
    my letter dated Aug. 30th 1995, Superior Fireplaces Company is ready 
    to accept the changes to the first waiver as follows:
        Superior Fireplaces Company will adopt the test procedure 
    proposed by DOE on 23 August, 1993.58 FR 44538. Accordingly, we 
    request to calculate the weighted average steady state efficiency 
    using the minimum obtainable fuel input rate provided this rate is 
    no greater than \2/3\ the maximum input rate of the fireplace. 
    Specifically, the models included in this request will be tested at 
    \2/3\ of the maximum fuel input rate.
        The second waiver requested in my first letter will remain 
    unchanged.
        We are very confident that both of these waivers will be granted 
    since similar waivers have been granted to the other manufacturers.
    
            Sincerely,
    Hardial Gore,
    Sr. Project Engineer.
    January 12, 1996
    The Honorable Christine Ervin, Assistant Secretary for Energy, 
    Efficiency & Renewable Energy, United States Department of Energy, 
    Forrestal Building, 1000 Independence Avenue, SW., Washington, D.C. 
    20585
    
    RE: Additional information to Petition for Waiver and Application 
    for Interim Waiver
    
        Dear Secretary Ervin: Recent conversations with William Hui 
    prompted me to send you the following information requested by the 
    committee.
        Per your first request following is a list of companies that 
    Superior knows make similar products namely Heat and Glow, Majestic, 
    Heatilator, CFM, Vermont Castings, Appalachian Stove and 
    Fabricators, Inc. and Valor Incorporated.
        Per your second request below is a table that shows a general 
    trend of increase in efficiency as the input is increased. This 
    information is confidential; please do not publish. This data was 
    gathered from a DVH-33R model.
    
    CONFIDENTIAL
    
        As discussed with Mr. Hui we would like to add additional models 
    DVH-33R, DVH-33T, DVA-33R, DVA-33T to the list for approval besides 
    the GI 3821 and DSH-36T.
        If you have any questions please feel free to contact me.
    
            Sincerely,
    Hardial Gore,
    Sr. Project Engineer, Gas Products.
    [FR Doc. 96-3056 Filed 2-13-96; 8:45 am]
    BILLING CODE 6450-01-M
    
    

Document Information

Published:
02/14/1996
Department:
Energy Efficiency and Renewable Energy Office
Entry Type:
Notice
Action:
Notice.
Document Number:
96-3056
Dates:
DOE will accept comments, data, and information not later than March 15, 1996.
Pages:
5755-5758 (4 pages)
Docket Numbers:
Case No. DH-005
PDF File:
96-3056.pdf